Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1969–1992 of 3346
EVAPCO's 29-3I18 — a AT cooling tower, 403 nominal tons (1770 kW): rated to cool 1212 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3I21 — a AT cooling tower, 447 nominal tons (1963 kW): rated to cool 1344 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3I24 — a AT cooling tower, 504 nominal tons (2217 kW): rated to cool 1518 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3I28 — a AT cooling tower, 561 nominal tons (2467 kW): rated to cool 1689 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3J18 — a AT cooling tower, 469 nominal tons (2064 kW): rated to cool 1413 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3J21 — a AT cooling tower, 516 nominal tons (2270 kW): rated to cool 1554 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3J24 — a AT cooling tower, 569 nominal tons (2502 kW): rated to cool 1713 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3J28 — a AT cooling tower, 631 nominal tons (2773 kW): rated to cool 1899 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3K21 — a AT cooling tower, 576 nominal tons (2532 kW): rated to cool 1734 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3K24 — a AT cooling tower, 628 nominal tons (2760 kW): rated to cool 1890 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3K28 — a AT cooling tower, 696 nominal tons (3058 kW): rated to cool 2094 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3L24 — a AT cooling tower, 672 nominal tons (2953 kW): rated to cool 2022 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3L28 — a AT cooling tower, 754 nominal tons (3317 kW): rated to cool 2271 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-3M28 — a AT cooling tower, 799 nominal tons (3514 kW): rated to cool 2406 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 80.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4G18 — a AT cooling tower, 334 nominal tons (1468 kW): rated to cool 1005 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4G21 — a AT cooling tower, 382 nominal tons (1678 kW): rated to cool 1149 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4H18 — a AT cooling tower, 386 nominal tons (1696 kW): rated to cool 1161 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4H21 — a AT cooling tower, 444 nominal tons (1950 kW): rated to cool 1335 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4H24 — a AT cooling tower, 479 nominal tons (2107 kW): rated to cool 1443 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4H28 — a AT cooling tower, 533 nominal tons (2344 kW): rated to cool 1605 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4I18 — a AT cooling tower, 424 nominal tons (1862 kW): rated to cool 1275 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4I21 — a AT cooling tower, 480 nominal tons (2112 kW): rated to cool 1446 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4I24 — a AT cooling tower, 529 nominal tons (2327 kW): rated to cool 1593 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
EVAPCO's 29-4I28 — a AT cooling tower, 590 nominal tons (2594 kW): rated to cool 1776 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers