Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1993–2016 of 3346

EVAPCO AT 29-4J18 cooling tower (489 tons, 2.2 MW) — modelled

EVAPCO's 29-4J18 — a AT cooling tower, 489 nominal tons (2151 kW): rated to cool 1473 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1613–2689 kW · EU

EVAPCO AT 29-4J21 cooling tower (545 tons, 2.4 MW) — modelled

EVAPCO's 29-4J21 — a AT cooling tower, 545 nominal tons (2397 kW): rated to cool 1641 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1797–2996 kW · EU

EVAPCO AT 29-4J24 cooling tower (591 tons, 2.6 MW) — modelled

EVAPCO's 29-4J24 — a AT cooling tower, 591 nominal tons (2598 kW): rated to cool 1779 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1949–3248 kW · EU

EVAPCO AT 29-4J28 cooling tower (659 tons, 2.9 MW) — modelled

EVAPCO's 29-4J28 — a AT cooling tower, 659 nominal tons (2896 kW): rated to cool 1983 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2172–3620 kW · EU

EVAPCO AT 29-4K18 cooling tower (536 tons, 2.4 MW) — modelled

EVAPCO's 29-4K18 — a AT cooling tower, 536 nominal tons (2357 kW): rated to cool 1614 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1768–2946 kW · EU

EVAPCO AT 29-4K21 cooling tower (602 tons, 2.6 MW) — modelled

EVAPCO's 29-4K21 — a AT cooling tower, 602 nominal tons (2646 kW): rated to cool 1812 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1985–3308 kW · EU

EVAPCO AT 29-4K24 cooling tower (651 tons, 2.9 MW) — modelled

EVAPCO's 29-4K24 — a AT cooling tower, 651 nominal tons (2861 kW): rated to cool 1959 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 62.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2146–3576 kW · EU

EVAPCO AT 29-4K28 cooling tower (724 tons, 3.2 MW) — modelled

EVAPCO's 29-4K28 — a AT cooling tower, 724 nominal tons (3181 kW): rated to cool 2178 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2386–3976 kW · EU

EVAPCO AT 29-4L21 cooling tower (634 tons, 2.8 MW) — modelled

EVAPCO's 29-4L21 — a AT cooling tower, 634 nominal tons (2787 kW): rated to cool 1908 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2090–3483 kW · EU

EVAPCO AT 29-4L24 cooling tower (694 tons, 3.0 MW) — modelled

EVAPCO's 29-4L24 — a AT cooling tower, 694 nominal tons (3049 kW): rated to cool 2088 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 66.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2287–3812 kW · EU

EVAPCO AT 29-4L28 cooling tower (784 tons, 3.4 MW) — modelled

EVAPCO's 29-4L28 — a AT cooling tower, 784 nominal tons (3448 kW): rated to cool 2361 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2586–4310 kW · EU

EVAPCO AT 29-4M24 cooling tower (716 tons, 3.1 MW) — modelled

EVAPCO's 29-4M24 — a AT cooling tower, 716 nominal tons (3146 kW): rated to cool 2154 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2359–3932 kW · EU

EVAPCO AT 29-4M28 cooling tower (827 tons, 3.6 MW) — modelled

EVAPCO's 29-4M28 — a AT cooling tower, 827 nominal tons (3637 kW): rated to cool 2490 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2727–4546 kW · EU

EVAPCO AT 310-2I36 cooling tower (670 tons, 2.9 MW) — modelled

EVAPCO's 310-2I36 — a AT cooling tower, 670 nominal tons (2944 kW): rated to cool 2016 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 91.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2208–3680 kW · EU

EVAPCO AT 310-2J36 cooling tower (814 tons, 3.6 MW) — modelled

EVAPCO's 310-2J36 — a AT cooling tower, 814 nominal tons (3580 kW): rated to cool 2451 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 104.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2685–4474 kW · EU

EVAPCO AT 310-2K36 cooling tower (900 tons, 4.0 MW) — modelled

EVAPCO's 310-2K36 — a AT cooling tower, 900 nominal tons (3956 kW): rated to cool 2709 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 114.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2967–4945 kW · EU

EVAPCO AT 310-2L36 cooling tower (960 tons, 4.2 MW) — modelled

EVAPCO's 310-2L36 — a AT cooling tower, 960 nominal tons (4219 kW): rated to cool 2889 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 122.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3164–5274 kW · EU

EVAPCO AT 310-2M36 cooling tower (1009 tons, 4.4 MW) — modelled

EVAPCO's 310-2M36 — a AT cooling tower, 1009 nominal tons (4434 kW): rated to cool 3036 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 130.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3325–5542 kW · EU

EVAPCO AT 310-3I36 cooling tower (779 tons, 3.4 MW) — modelled

EVAPCO's 310-3I36 — a AT cooling tower, 779 nominal tons (3426 kW): rated to cool 2346 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2570–4283 kW · EU

EVAPCO AT 310-3J36 cooling tower (911 tons, 4.0 MW) — modelled

EVAPCO's 310-3J36 — a AT cooling tower, 911 nominal tons (4005 kW): rated to cool 2742 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 102.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3003–5006 kW · EU

EVAPCO AT 310-3K36 cooling tower (997 tons, 4.4 MW) — modelled

EVAPCO's 310-3K36 — a AT cooling tower, 997 nominal tons (4381 kW): rated to cool 3000 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 112.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3286–5477 kW · EU

EVAPCO AT 310-3L36 cooling tower (1064 tons, 4.7 MW) — modelled

EVAPCO's 310-3L36 — a AT cooling tower, 1064 nominal tons (4679 kW): rated to cool 3204 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 120.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3509–5849 kW · EU

EVAPCO AT 310-3M36 cooling tower (1122 tons, 4.9 MW) — modelled

EVAPCO's 310-3M36 — a AT cooling tower, 1122 nominal tons (4933 kW): rated to cool 3378 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 127.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3700–6167 kW · EU

EVAPCO AT 310-4I36 cooling tower (818 tons, 3.6 MW) — modelled

EVAPCO's 310-4I36 — a AT cooling tower, 818 nominal tons (3597 kW): rated to cool 2463 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 88.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2698–4496 kW · EU
‹ Previous1…8283848586…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers