Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,993–2,016 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 217-2H9 cooling tower (323 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2H9 — an AT cooling tower, 323 nominal tons (1420 kW): rated to cool 972 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1065–1774 kWEUOpen in the builder
Baltimore Aircoil CXVB-473-1224-20 evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-473-1224-20 — a CXVB evaporative condenser rejecting 2866 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 67.8 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2149–3582 kWEUOpen in the builder
EVAPCO AT 217-2I11 cooling tower (407 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2I11 — an AT cooling tower, 407 nominal tons (1788 kW): rated to cool 1224 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1341–2235 kWEUOpen in the builder
Baltimore Aircoil FXV-1212C-32Q-P closed-circuit cooler (265 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212C-32Q-P — an FXV closed-circuit cooler, 265 nominal tons (1165 kW): rated to cool 798 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 51.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection874–1457 kWEUOpen in the builder
EVAPCO AT 217-2I12 cooling tower (446 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2I12 — an AT cooling tower, 446 nominal tons (1958 kW): rated to cool 1341 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1469–2448 kWEUOpen in the builder
Baltimore Aircoil PCC-0562-1024N050 evaporative condenser (3.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0562-1024N050 — a PCC evaporative condenser rejecting 3414 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 70.6 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2560–4267 kWEUOpen in the builder
EVAPCO AT 217-2I14 cooling tower (492 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2I14 — an AT cooling tower, 492 nominal tons (2164 kW): rated to cool 1482 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1623–2706 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-3D4DS-L1 closed-circuit cooler (118 tons, 517 kW) — modelled Example modelled from published data
BAC's PFI-1012N-3D4DS-L1 — a PFi closed-circuit cooler, 118 nominal tons (517 kW): rated to cool 354 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection388–646 kWEUOpen in the builder
EVAPCO AT 217-2I9 cooling tower (355 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2I9 — an AT cooling tower, 355 nominal tons (1560 kW): rated to cool 1068 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1170–1950 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1285-06JN-2 cooling tower (315 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1285-06JN-2 — a Series 1500 cooling tower, 315 nominal tons (1385 kW): rated to cool 948 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 35.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1038–1731 kWEUOpen in the builder
EVAPCO AT 217-2J11 cooling tower (465 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2J11 — an AT cooling tower, 465 nominal tons (2046 kW): rated to cool 1401 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1535–2558 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-12S-2 cooling tower (2235 tons, 9.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-12S-2 — a Series 3000 cooling tower, 2235 nominal tons (9823 kW): rated to cool 6726 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 248.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7367–12279 kWEUOpen in the builder
EVAPCO AT 217-2J12 cooling tower (497 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2J12 — an AT cooling tower, 497 nominal tons (2186 kW): rated to cool 1497 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1640–2733 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M840-R cooling tower (837 tons, 3.7 MW) — modelled Example modelled from published data
BAC's VT1-M840-R — a Series V cooling tower, 837 nominal tons (3680 kW): rated to cool 2520 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2760–4600 kWEUOpen in the builder
EVAPCO AT 217-2J14 cooling tower (549 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2J14 — an AT cooling tower, 549 nominal tons (2414 kW): rated to cool 1653 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 66.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1811–3018 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-144-21P closed-circuit cooler (116 tons, 508 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-144-21P — a Series V closed circuit closed-circuit cooler, 116 nominal tons (508 kW): rated to cool 348 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection381–635 kWEUOpen in the builder
EVAPCO AT 217-2J9 cooling tower (415 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2J9 — an AT cooling tower, 415 nominal tons (1823 kW): rated to cool 1248 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1367–2278 kWEUOpen in the builder
Baltimore Aircoil VCA-451A evaporative condenser (1.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-451A — a VCA evaporative condenser rejecting 1943 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 34.5 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1457–2429 kWEUOpen in the builder
EVAPCO AT 217-2K12 cooling tower (548 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2K12 — an AT cooling tower, 548 nominal tons (2410 kW): rated to cool 1650 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1807–3012 kWEUOpen in the builder
Baltimore Aircoil VRC-0553B-1018N-LA evaporative condenser (3.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0553B-1018N-LA — a Vertex VRC evaporative condenser rejecting 3356 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 50.9 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2517–4195 kWEUOpen in the builder
EVAPCO AT 217-2K14 cooling tower (606 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2K14 — an AT cooling tower, 606 nominal tons (2664 kW): rated to cool 1824 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1998–3330 kWEUOpen in the builder
Baltimore Aircoil CXVB-482-1218-22.5 evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-482-1218-22.5 — a CXVB evaporative condenser rejecting 2920 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 56.8 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2190–3650 kWEUOpen in the builder
EVAPCO AT 217-2L14 cooling tower (662 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-2L14 — an AT cooling tower, 662 nominal tons (2909 kW): rated to cool 1992 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 77.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2182–3637 kWEUOpen in the builder
Baltimore Aircoil FXV-1212C-36D-L closed-circuit cooler (220 tons, 968 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212C-36D-L — an FXV closed-circuit cooler, 220 nominal tons (968 kW): rated to cool 663 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 37.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection726–1210 kWEUOpen in the builder
‹ Previous1…8283848586…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers