Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 2,041–2,064 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 217-3J14 cooling tower (619 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-3J14 — an AT cooling tower, 619 nominal tons (2721 kW): rated to cool 1863 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2041–3401 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1285-06KN-2 cooling tower (345 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1285-06KN-2 — a Series 1500 cooling tower, 345 nominal tons (1516 kW): rated to cool 1038 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1137–1895 kW | EU | Open in the builder |
| EVAPCO AT 217-3J9 cooling tower (462 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-3J9 — an AT cooling tower, 462 nominal tons (2033 kW): rated to cool 1392 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1525–2541 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1424-12T-2 cooling tower (2406 tons, 10.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1424-12T-2 — a Series 3000 cooling tower, 2406 nominal tons (10577 kW): rated to cool 7242 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 263.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 7932–13221 kW | EU | Open in the builder |
| EVAPCO AT 217-3K11 cooling tower (574 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-3K11 — an AT cooling tower, 574 nominal tons (2524 kW): rated to cool 1728 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1893–3155 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M984-O cooling tower (981 tons, 4.3 MW) — modelled Example modelled from published data BAC's VT1-M984-O — a Series V cooling tower, 981 nominal tons (4311 kW): rated to cool 2952 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 91.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3233–5389 kW | EU | Open in the builder |
| EVAPCO AT 217-3K12 cooling tower (620 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-3K12 — an AT cooling tower, 620 nominal tons (2725 kW): rated to cool 1866 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2044–3407 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-144-21R closed-circuit cooler (141 tons, 618 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-144-21R — a Series V closed circuit closed-circuit cooler, 141 nominal tons (618 kW): rated to cool 423 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 43.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 463–772 kW | EU | Open in the builder |
| EVAPCO AT 217-3K14 cooling tower (683 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-3K14 — an AT cooling tower, 683 nominal tons (3001 kW): rated to cool 2055 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2251–3752 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-464A evaporative condenser (2.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-464A — a VCA evaporative condenser rejecting 1999 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 29.6 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1499–2499 kW | EU | Open in the builder |
| EVAPCO AT 217-3L12 cooling tower (663 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-3L12 — an AT cooling tower, 663 nominal tons (2914 kW): rated to cool 1995 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 67.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2185–3642 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0564B-1218N-JB evaporative condenser (3.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0564B-1218N-JB — a Vertex VRC evaporative condenser rejecting 3419 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 63.0 m³/s of the maker's own printed air, with a 40.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2564–4273 kW | EU | Open in the builder |
| EVAPCO AT 217-3L14 cooling tower (742 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-3L14 — an AT cooling tower, 742 nominal tons (3260 kW): rated to cool 2232 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2445–4075 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-513-1218-22.5 evaporative condenser (3.1 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-513-1218-22.5 — a CXVB evaporative condenser rejecting 3108 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 56.3 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2331–3885 kW | EU | Open in the builder |
| EVAPCO AT 217-3M14 cooling tower (784 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-3M14 — an AT cooling tower, 784 nominal tons (3448 kW): rated to cool 2361 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 80.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2586–4310 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-1212C-36T-P closed-circuit cooler (284 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-1212C-36T-P — an FXV closed-circuit cooler, 284 nominal tons (1249 kW): rated to cool 855 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 51.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 937–1561 kW | EU | Open in the builder |
| EVAPCO AT 217-4G11 cooling tower (384 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-4G11 — an AT cooling tower, 384 nominal tons (1687 kW): rated to cool 1155 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1265–2109 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0567-1220N030 evaporative condenser (3.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0567-1220N030 — a PCC evaporative condenser rejecting 3444 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 55.1 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2583–4305 kW | EU | Open in the builder |
| EVAPCO AT 217-4G9 cooling tower (329 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-4G9 — an AT cooling tower, 329 nominal tons (1446 kW): rated to cool 990 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1084–1807 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1012N-4D1DS-J1 closed-circuit cooler (109 tons, 478 kW) — modelled Example modelled from published data BAC's PFI-1012N-4D1DS-J1 — a PFi closed-circuit cooler, 109 nominal tons (478 kW): rated to cool 327 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 25.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 358–597 kW | EU | Open in the builder |
| EVAPCO AT 217-4H11 cooling tower (443 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-4H11 — an AT cooling tower, 443 nominal tons (1945 kW): rated to cool 1332 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1459–2432 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1285-06LN cooling tower (197 tons, 868 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1285-06LN — a Series 1500 cooling tower, 197 nominal tons (868 kW): rated to cool 594 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 22.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 651–1084 kW | EU | Open in the builder |
| EVAPCO AT 217-4H12 cooling tower (472 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 217-4H12 — an AT cooling tower, 472 nominal tons (2077 kW): rated to cool 1422 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1558–2596 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1424-13Q cooling tower (1028 tons, 4.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1424-13Q — a Series 3000 cooling tower, 1028 nominal tons (4517 kW): rated to cool 3093 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 114.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3388–5647 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers