Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 2089–2112 of 3346

EVAPCO AT 314-2K72 cooling tower (1783 tons, 7.8 MW) — modelled

EVAPCO's 314-2K72 — a AT cooling tower, 1783 nominal tons (7838 kW): rated to cool 5367 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 220.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 5879–9798 kW · EU

EVAPCO AT 314-2L72 cooling tower (1979 tons, 8.7 MW) — modelled

EVAPCO's 314-2L72 — a AT cooling tower, 1979 nominal tons (8701 kW): rated to cool 5958 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 236.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 6526–10877 kW · EU

EVAPCO AT 314-2M72 cooling tower (2088 tons, 9.2 MW) — modelled

EVAPCO's 314-2M72 — a AT cooling tower, 2088 nominal tons (9179 kW): rated to cool 6285 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 250.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 6884–11474 kW · EU

EVAPCO AT 314-2N72 cooling tower (2263 tons, 10.0 MW) — modelled

EVAPCO's 314-2N72 — a AT cooling tower, 2263 nominal tons (9950 kW): rated to cool 6813 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 275.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 7463–12438 kW · EU

EVAPCO AT 314-2O72 cooling tower (2431 tons, 10.7 MW) — modelled

EVAPCO's 314-2O72 — a AT cooling tower, 2431 nominal tons (10686 kW): rated to cool 7317 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 295.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 8015–13358 kW · EU

EVAPCO AT 314-3K72 cooling tower (2049 tons, 9.0 MW) — modelled

EVAPCO's 314-3K72 — a AT cooling tower, 2049 nominal tons (9008 kW): rated to cool 6168 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 217.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 6756–11260 kW · EU

EVAPCO AT 314-3L72 cooling tower (2249 tons, 9.9 MW) — modelled

EVAPCO's 314-3L72 — a AT cooling tower, 2249 nominal tons (9889 kW): rated to cool 6771 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 232.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 7417–12361 kW · EU

EVAPCO AT 314-3M72 cooling tower (2356 tons, 10.4 MW) — modelled

EVAPCO's 314-3M72 — a AT cooling tower, 2356 nominal tons (10358 kW): rated to cool 7092 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 246.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 7768–12947 kW · EU

EVAPCO AT 314-3N72 cooling tower (2592 tons, 11.4 MW) — modelled

EVAPCO's 314-3N72 — a AT cooling tower, 2592 nominal tons (11396 kW): rated to cool 7803 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 270.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 8547–14245 kW · EU

EVAPCO AT 314-3O72 cooling tower (2764 tons, 12.1 MW) — modelled

EVAPCO's 314-3O72 — a AT cooling tower, 2764 nominal tons (12150 kW): rated to cool 8319 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 290.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 9112–15187 kW · EU

EVAPCO AT 314-3P72 cooling tower (2934 tons, 12.9 MW) — modelled

EVAPCO's 314-3P72 — a AT cooling tower, 2934 nominal tons (12899 kW): rated to cool 8832 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 307.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 9674–16123 kW · EU

EVAPCO AT 314-4K72 cooling tower (2248 tons, 9.9 MW) — modelled

EVAPCO's 314-4K72 — a AT cooling tower, 2248 nominal tons (9880 kW): rated to cool 6765 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 213.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 7410–12350 kW · EU

EVAPCO AT 314-4L72 cooling tower (2429 tons, 10.7 MW) — modelled

EVAPCO's 314-4L72 — a AT cooling tower, 2429 nominal tons (10677 kW): rated to cool 7311 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 228.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 8008–13347 kW · EU

EVAPCO AT 314-4M72 cooling tower (2543 tons, 11.2 MW) — modelled

EVAPCO's 314-4M72 — a AT cooling tower, 2543 nominal tons (11177 kW): rated to cool 7653 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 242.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 8383–13971 kW · EU

EVAPCO AT 314-4N72 cooling tower (2761 tons, 12.1 MW) — modelled

EVAPCO's 314-4N72 — a AT cooling tower, 2761 nominal tons (12136 kW): rated to cool 8310 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 265.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 9102–15171 kW · EU

EVAPCO AT 314-4O72 cooling tower (2909 tons, 12.8 MW) — modelled

EVAPCO's 314-4O72 — a AT cooling tower, 2909 nominal tons (12789 kW): rated to cool 8757 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 285.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 9592–15987 kW · EU

EVAPCO AT 314-4P72 cooling tower (3081 tons, 13.5 MW) — modelled

EVAPCO's 314-4P72 — a AT cooling tower, 3081 nominal tons (13543 kW): rated to cool 9273 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 302.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 10157–16929 kW · EU

EVAPCO AT 314-4Q72 cooling tower (3311 tons, 14.6 MW) — modelled

EVAPCO's 314-4Q72 — a AT cooling tower, 3311 nominal tons (14555 kW): rated to cool 9966 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 323.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 10916–18194 kW · EU

EVAPCO AT 314-5K78 cooling tower (2926 tons, 12.9 MW) — modelled

EVAPCO's 314-5K78 — a AT cooling tower, 2926 nominal tons (12864 kW): rated to cool 8808 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 276.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 9648–16080 kW · EU

EVAPCO AT 314-5L78 cooling tower (3147 tons, 13.8 MW) — modelled

EVAPCO's 314-5L78 — a AT cooling tower, 3147 nominal tons (13832 kW): rated to cool 9471 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 296.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 10374–17290 kW · EU

EVAPCO AT 314-5M78 cooling tower (3333 tons, 14.7 MW) — modelled

EVAPCO's 314-5M78 — a AT cooling tower, 3333 nominal tons (14651 kW): rated to cool 10032 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 314.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 10989–18314 kW · EU

EVAPCO AT 314-5N78 cooling tower (3643 tons, 16.0 MW) — modelled

EVAPCO's 314-5N78 — a AT cooling tower, 3643 nominal tons (16014 kW): rated to cool 10965 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 343.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 12010–20017 kW · EU

EVAPCO AT 314-5O78 cooling tower (3895 tons, 17.1 MW) — modelled

EVAPCO's 314-5O78 — a AT cooling tower, 3895 nominal tons (17122 kW): rated to cool 11724 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 368.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 12842–21403 kW · EU

EVAPCO AT 342-5K26 cooling tower (2872 tons, 12.6 MW) — modelled

EVAPCO's 342-5K26 — a AT cooling tower, 2872 nominal tons (12627 kW): rated to cool 8646 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 277.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 9470–15784 kW · EU
‹ Previous1…8687888990…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers