Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,089–2,112 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 217-4K14 cooling tower (712 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-4K14 — an AT cooling tower, 712 nominal tons (3128 kW): rated to cool 2142 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2346–3910 kWEUOpen in the builder
Baltimore Aircoil VCA-473A evaporative condenser (2.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-473A — a VCA evaporative condenser rejecting 2038 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.4 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1528–2547 kWEUOpen in the builder
EVAPCO AT 217-4K9 cooling tower (528 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-4K9 — an AT cooling tower, 528 nominal tons (2322 kW): rated to cool 1590 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1742–2903 kWEUOpen in the builder
Baltimore Aircoil VRC-0571B-1024N-KA evaporative condenser (3.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0571B-1024N-KA — a Vertex VRC evaporative condenser rejecting 3464 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 65.9 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2598–4329 kWEUOpen in the builder
EVAPCO AT 217-4L11 cooling tower (632 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-4L11 — an AT cooling tower, 632 nominal tons (2778 kW): rated to cool 1902 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2083–3472 kWEUOpen in the builder
Baltimore Aircoil CXVB-525-1218-30 evaporative condenser (3.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-525-1218-30 — a CXVB evaporative condenser rejecting 3181 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 62.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2386–3976 kWEUOpen in the builder
EVAPCO AT 217-4L12 cooling tower (686 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-4L12 — an AT cooling tower, 686 nominal tons (3014 kW): rated to cool 2064 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 66.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2261–3768 kWEUOpen in the builder
Baltimore Aircoil FXV-1218B-16D-N closed-circuit cooler (281 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1218B-16D-N — an FXV closed-circuit cooler, 281 nominal tons (1236 kW): rated to cool 846 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 65.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection927–1544 kWEUOpen in the builder
EVAPCO AT 217-4L14 cooling tower (770 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-4L14 — an AT cooling tower, 770 nominal tons (3387 kW): rated to cool 2319 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2540–4234 kWEUOpen in the builder
Baltimore Aircoil PCC-0580-1220N030 evaporative condenser (3.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0580-1220N030 — a PCC evaporative condenser rejecting 3523 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 52.8 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2642–4404 kWEUOpen in the builder
EVAPCO AT 217-4M12 cooling tower (707 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-4M12 — an AT cooling tower, 707 nominal tons (3106 kW): rated to cool 2127 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2330–3883 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-4D1ES-J1 closed-circuit cooler (118 tons, 517 kW) — modelled Example modelled from published data
BAC's PFI-1012N-4D1ES-J1 — a PFi closed-circuit cooler, 118 nominal tons (517 kW): rated to cool 354 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 24.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection388–646 kWEUOpen in the builder
EVAPCO AT 217-4M14 cooling tower (812 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 217-4M14 — an AT cooling tower, 812 nominal tons (3571 kW): rated to cool 2445 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2678–4464 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1285-07KN cooling tower (188 tons, 828 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1285-07KN — a Series 1500 cooling tower, 188 nominal tons (828 kW): rated to cool 567 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 20.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection621–1035 kWEUOpen in the builder
EVAPCO AT 220-2I12 cooling tower (453 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2I12 — an AT cooling tower, 453 nominal tons (1994 kW): rated to cool 1365 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1495–2492 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-13R cooling tower (1084 tons, 4.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-13R — a Series 3000 cooling tower, 1084 nominal tons (4767 kW): rated to cool 3264 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 120.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3575–5959 kWEUOpen in the builder
EVAPCO AT 220-2I18 cooling tower (578 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2I18 — an AT cooling tower, 578 nominal tons (2541 kW): rated to cool 1740 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 80.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1906–3177 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-N240-P cooling tower (239 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-N240-P — a Series V cooling tower, 239 nominal tons (1052 kW): rated to cool 720 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 27.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection789–1314 kWEUOpen in the builder
EVAPCO AT 220-2J12 cooling tower (551 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2J12 — an AT cooling tower, 551 nominal tons (2423 kW): rated to cool 1659 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 69.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1817–3029 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-144-31R closed-circuit cooler (152 tons, 670 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-144-31R — a Series V closed circuit closed-circuit cooler, 152 nominal tons (670 kW): rated to cool 459 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 43.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection503–838 kWEUOpen in the builder
EVAPCO AT 220-2J18 cooling tower (699 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2J18 — an AT cooling tower, 699 nominal tons (3071 kW): rated to cool 2103 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 91.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2304–3839 kWEUOpen in the builder
Baltimore Aircoil VCA-488A evaporative condenser (2.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-488A — a VCA evaporative condenser rejecting 2102 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 28.5 m³/s of the maker's own printed air, with a 6.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1577–2628 kWEUOpen in the builder
EVAPCO AT 220-2K12 cooling tower (609 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2K12 — an AT cooling tower, 609 nominal tons (2677 kW): rated to cool 1833 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2008–3346 kWEUOpen in the builder
Baltimore Aircoil VRC-0574B-1224N-KA evaporative condenser (3.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0574B-1224N-KA — a Vertex VRC evaporative condenser rejecting 3481 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 71.1 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2611–4351 kWEUOpen in the builder
‹ Previous1…8687888990…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers