Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,113–2,136 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 220-2K18 cooling tower (776 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2K18 — an AT cooling tower, 776 nominal tons (3413 kW): rated to cool 2337 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 100.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2560–4266 kWEUOpen in the builder
Baltimore Aircoil CXVB-528-1224-20 evaporative condenser (3.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-528-1224-20 — a CXVB evaporative condenser rejecting 3199 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 66.4 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2399–3999 kWEUOpen in the builder
EVAPCO AT 220-2L12 cooling tower (649 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2L12 — an AT cooling tower, 649 nominal tons (2852 kW): rated to cool 1953 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 81.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2139–3565 kWEUOpen in the builder
Baltimore Aircoil FXV-1218B-16Q-O closed-circuit cooler (261 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1218B-16Q-O — an FXV closed-circuit cooler, 261 nominal tons (1148 kW): rated to cool 786 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 69.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection861–1435 kWEUOpen in the builder
EVAPCO AT 220-2L18 cooling tower (837 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2L18 — an AT cooling tower, 837 nominal tons (3680 kW): rated to cool 2520 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 108.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2760–4600 kWEUOpen in the builder
Baltimore Aircoil PCC-0581-1220N040 evaporative condenser (3.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0581-1220N040 — a PCC evaporative condenser rejecting 3529 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.3 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2647–4411 kWEUOpen in the builder
EVAPCO AT 220-2M12 cooling tower (682 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2M12 — an AT cooling tower, 682 nominal tons (2997 kW): rated to cool 2052 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 86.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2248–3746 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-4D1ES-M1 closed-circuit cooler (145 tons, 635 kW) — modelled Example modelled from published data
BAC's PFI-1012N-4D1ES-M1 — a PFi closed-circuit cooler, 145 nominal tons (635 kW): rated to cool 435 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 33.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection476–794 kWEUOpen in the builder
EVAPCO AT 220-2M18 cooling tower (887 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-2M18 — an AT cooling tower, 887 nominal tons (3899 kW): rated to cool 2670 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 114.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2925–4874 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1285-07KN-2 cooling tower (377 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1285-07KN-2 — a Series 1500 cooling tower, 377 nominal tons (1656 kW): rated to cool 1134 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1242–2070 kWEUOpen in the builder
EVAPCO AT 220-3I12 cooling tower (527 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3I12 — an AT cooling tower, 527 nominal tons (2318 kW): rated to cool 1587 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1738–2897 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-13R-2 cooling tower (2168 tons, 9.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-13R-2 — a Series 3000 cooling tower, 2168 nominal tons (9530 kW): rated to cool 6525 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 240.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7147–11912 kWEUOpen in the builder
EVAPCO AT 220-3I18 cooling tower (665 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3I18 — an AT cooling tower, 665 nominal tons (2922 kW): rated to cool 2001 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2192–3653 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-N255-P cooling tower (254 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-N255-P — a Series V cooling tower, 254 nominal tons (1117 kW): rated to cool 765 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection838–1397 kWEUOpen in the builder
EVAPCO AT 220-3J12 cooling tower (616 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3J12 — an AT cooling tower, 616 nominal tons (2708 kW): rated to cool 1854 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 67.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2031–3385 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-144-41P closed-circuit cooler (137 tons, 600 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-144-41P — a Series V closed circuit closed-circuit cooler, 137 nominal tons (600 kW): rated to cool 411 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 37.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection450–750 kWEUOpen in the builder
EVAPCO AT 220-3J18 cooling tower (787 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3J18 — an AT cooling tower, 787 nominal tons (3461 kW): rated to cool 2370 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2596–4327 kWEUOpen in the builder
Baltimore Aircoil VCA-491A evaporative condenser (2.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-491A — a VCA evaporative condenser rejecting 2115 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 33.6 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1587–2644 kWEUOpen in the builder
EVAPCO AT 220-3K12 cooling tower (674 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3K12 — an AT cooling tower, 674 nominal tons (2962 kW): rated to cool 2028 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2221–3702 kWEUOpen in the builder
Baltimore Aircoil VRC-0587B-1218N-LA evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0587B-1218N-LA — a Vertex VRC evaporative condenser rejecting 3563 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 57.7 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2672–4454 kWEUOpen in the builder
EVAPCO AT 220-3K18 cooling tower (870 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3K18 — an AT cooling tower, 870 nominal tons (3825 kW): rated to cool 2619 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 99.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2869–4781 kWEUOpen in the builder
Baltimore Aircoil CXVB-545-1218-30 evaporative condenser (3.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-545-1218-30 — a CXVB evaporative condenser rejecting 3302 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 61.9 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2476–4127 kWEUOpen in the builder
EVAPCO AT 220-3L12 cooling tower (720 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3L12 — an AT cooling tower, 720 nominal tons (3163 kW): rated to cool 2166 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2373–3954 kWEUOpen in the builder
Baltimore Aircoil FXV-1218B-20D-K closed-circuit cooler (230 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1218B-20D-K — an FXV closed-circuit cooler, 230 nominal tons (1012 kW): rated to cool 693 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 47.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection759–1265 kWEUOpen in the builder
‹ Previous1…8788899091…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers