Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,137–2,160 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 220-3L18 cooling tower (938 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3L18 — an AT cooling tower, 938 nominal tons (4123 kW): rated to cool 2823 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 106.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3092–5154 kWEUOpen in the builder
Baltimore Aircoil PCC-0586-1224N030 evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0586-1224N030 — a PCC evaporative condenser rejecting 3560 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.9 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2670–4450 kWEUOpen in the builder
EVAPCO AT 220-3M12 cooling tower (757 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3M12 — an AT cooling tower, 757 nominal tons (3330 kW): rated to cool 2280 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 84.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2497–4162 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-4D2ES-N1 closed-circuit cooler (155 tons, 683 kW) — modelled Example modelled from published data
BAC's PFI-1012N-4D2ES-N1 — a PFi closed-circuit cooler, 155 nominal tons (683 kW): rated to cool 468 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 34.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection513–854 kWEUOpen in the builder
EVAPCO AT 220-3M18 cooling tower (994 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3M18 — an AT cooling tower, 994 nominal tons (4368 kW): rated to cool 2991 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 112.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3276–5460 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1285-07LN cooling tower (216 tons, 951 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1285-07LN — a Series 1500 cooling tower, 216 nominal tons (951 kW): rated to cool 651 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection713–1188 kWEUOpen in the builder
EVAPCO AT 220-3N18 cooling tower (1089 tons, 4.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-3N18 — an AT cooling tower, 1089 nominal tons (4789 kW): rated to cool 3279 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 123.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3592–5986 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-13S cooling tower (1157 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-13S — a Series 3000 cooling tower, 1157 nominal tons (5087 kW): rated to cool 3483 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 127.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3815–6358 kWEUOpen in the builder
EVAPCO AT 220-4I12 cooling tower (553 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-4I12 — an AT cooling tower, 553 nominal tons (2432 kW): rated to cool 1665 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1824–3040 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-N301-Q cooling tower (300 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-N301-Q — a Series V cooling tower, 300 nominal tons (1319 kW): rated to cool 903 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection989–1648 kWEUOpen in the builder
EVAPCO AT 220-4I18 cooling tower (725 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-4I18 — an AT cooling tower, 725 nominal tons (3185 kW): rated to cool 2181 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2389–3982 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-144-41Q closed-circuit cooler (150 tons, 662 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-144-41Q — a Series V closed circuit closed-circuit cooler, 150 nominal tons (662 kW): rated to cool 453 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 40.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection496–827 kWEUOpen in the builder
EVAPCO AT 220-4J12 cooling tower (642 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-4J12 — an AT cooling tower, 642 nominal tons (2822 kW): rated to cool 1932 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 66.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2116–3527 kWEUOpen in the builder
Baltimore Aircoil VCA-507A evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-507A — a VCA evaporative condenser rejecting 2184 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 47.4 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1638–2730 kWEUOpen in the builder
EVAPCO AT 220-4J18 cooling tower (836 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-4J18 — an AT cooling tower, 836 nominal tons (3676 kW): rated to cool 2517 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 89.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2757–4595 kWEUOpen in the builder
Baltimore Aircoil VRC-0595B-1024N-JB evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0595B-1024N-JB — a Vertex VRC evaporative condenser rejecting 3608 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 91.3 m³/s of the maker's own printed air, with a 60.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2706–4510 kWEUOpen in the builder
EVAPCO AT 220-4K12 cooling tower (699 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-4K12 — an AT cooling tower, 699 nominal tons (3071 kW): rated to cool 2103 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 73.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2304–3839 kWEUOpen in the builder
Baltimore Aircoil CXVB-567-1218-37.5 evaporative condenser (3.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-567-1218-37.5 — a CXVB evaporative condenser rejecting 3435 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 66.7 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2576–4294 kWEUOpen in the builder
EVAPCO AT 220-4K18 cooling tower (918 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-4K18 — an AT cooling tower, 918 nominal tons (4035 kW): rated to cool 2763 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 97.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3026–5044 kWEUOpen in the builder
Baltimore Aircoil FXV-1218B-23Q-O closed-circuit cooler (317 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1218B-23Q-O — an FXV closed-circuit cooler, 317 nominal tons (1393 kW): rated to cool 954 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 68.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1045–1742 kWEUOpen in the builder
EVAPCO AT 220-4L12 cooling tower (744 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-4L12 — an AT cooling tower, 744 nominal tons (3269 kW): rated to cool 2238 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2451–4086 kWEUOpen in the builder
Baltimore Aircoil PCC-0586-2412N030 evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0586-2412N030 — a PCC evaporative condenser rejecting 3560 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.9 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2670–4450 kWEUOpen in the builder
EVAPCO AT 220-4L18 cooling tower (984 tons, 4.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 220-4L18 — an AT cooling tower, 984 nominal tons (4324 kW): rated to cool 2961 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 104.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3243–5406 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-4D3ES-L1 closed-circuit cooler (142 tons, 622 kW) — modelled Example modelled from published data
BAC's PFI-1012N-4D3ES-L1 — a PFi closed-circuit cooler, 142 nominal tons (622 kW): rated to cool 426 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 28.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection467–778 kWEUOpen in the builder
‹ Previous1…8889909192…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers