Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 2,161–2,184 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 220-4M12 cooling tower (782 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 220-4M12 — an AT cooling tower, 782 nominal tons (3439 kW): rated to cool 2355 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 83.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2580–4299 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1285-07LN-2 cooling tower (433 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1285-07LN-2 — a Series 1500 cooling tower, 433 nominal tons (1902 kW): rated to cool 1302 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1426–2377 kW | EU | Open in the builder |
| EVAPCO AT 220-4M18 cooling tower (1041 tons, 4.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 220-4M18 — an AT cooling tower, 1041 nominal tons (4574 kW): rated to cool 3132 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 110.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3431–5718 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1424-13S-2 cooling tower (2314 tons, 10.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1424-13S-2 — a Series 3000 cooling tower, 2314 nominal tons (10174 kW): rated to cool 6966 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 255.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 7630–12717 kW | EU | Open in the builder |
| EVAPCO AT 220-4N12 cooling tower (817 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 220-4N12 — an AT cooling tower, 817 nominal tons (3593 kW): rated to cool 2460 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 87.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2695–4491 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-N325-P cooling tower (324 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT1-N325-P — a Series V cooling tower, 324 nominal tons (1424 kW): rated to cool 975 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1068–1780 kW | EU | Open in the builder |
| EVAPCO AT 220-4N18 cooling tower (1136 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 220-4N18 — an AT cooling tower, 1136 nominal tons (4995 kW): rated to cool 3420 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 121.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3746–6243 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-144-41R closed-circuit cooler (163 tons, 719 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-144-41R — a Series V closed circuit closed-circuit cooler, 163 nominal tons (719 kW): rated to cool 492 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 42.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 539–898 kW | EU | Open in the builder |
| EVAPCO AT 224-2J18 cooling tower (874 tons, 3.8 MW) — modelled Example modelled from published data EVAPCO's 224-2J18 — an AT cooling tower, 874 nominal tons (3842 kW): rated to cool 2631 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 103.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2882–4803 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-510A evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-510A — a VCA evaporative condenser rejecting 2197 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.2 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1648–2746 kW | EU | Open in the builder |
| EVAPCO AT 224-2K18 cooling tower (991 tons, 4.4 MW) — modelled Example modelled from published data EVAPCO's 224-2K18 — an AT cooling tower, 991 nominal tons (4355 kW): rated to cool 2982 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 113.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3266–5444 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0597B-1224N-JA evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0597B-1224N-JA — a Vertex VRC evaporative condenser rejecting 3619 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2714–4524 kW | EU | Open in the builder |
| EVAPCO AT 224-2K20 cooling tower (890 tons, 3.9 MW) — modelled Example modelled from published data EVAPCO's 224-2K20 — an AT cooling tower, 890 nominal tons (3913 kW): rated to cool 2679 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 115.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2934–4891 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-571-1224-30 evaporative condenser (3.5 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-571-1224-30 — a CXVB evaporative condenser rejecting 3459 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 76.0 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2595–4324 kW | EU | Open in the builder |
| EVAPCO AT 224-2L18 cooling tower (1048 tons, 4.6 MW) — modelled Example modelled from published data EVAPCO's 224-2L18 — an AT cooling tower, 1048 nominal tons (4605 kW): rated to cool 3153 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 121.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3454–5756 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-1218B-23T-O closed-circuit cooler (333 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-1218B-23T-O — an FXV closed-circuit cooler, 333 nominal tons (1463 kW): rated to cool 1002 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 68.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1098–1829 kW | EU | Open in the builder |
| EVAPCO AT 224-2L20 cooling tower (983 tons, 4.3 MW) — modelled Example modelled from published data EVAPCO's 224-2L20 — an AT cooling tower, 983 nominal tons (4320 kW): rated to cool 2958 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 123.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3240–5400 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0590-1024N060 evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0590-1024N060 — a PCC evaporative condenser rejecting 3584 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 74.6 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2688–4480 kW | EU | Open in the builder |
| EVAPCO AT 224-2M18 cooling tower (1103 tons, 4.9 MW) — modelled Example modelled from published data EVAPCO's 224-2M18 — an AT cooling tower, 1103 nominal tons (4850 kW): rated to cool 3321 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 129.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3638–6063 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1012N-4D3ES-N1 closed-circuit cooler (159 tons, 701 kW) — modelled Example modelled from published data BAC's PFI-1012N-4D3ES-N1 — a PFi closed-circuit cooler, 159 nominal tons (701 kW): rated to cool 480 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 33.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 526–876 kW | EU | Open in the builder |
| EVAPCO AT 224-2M20 cooling tower (1057 tons, 4.6 MW) — modelled Example modelled from published data EVAPCO's 224-2M20 — an AT cooling tower, 1057 nominal tons (4649 kW): rated to cool 3183 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 131.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3486–5811 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1285-07MN cooling tower (235 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1285-07MN — a Series 1500 cooling tower, 235 nominal tons (1034 kW): rated to cool 708 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 776–1293 kW | EU | Open in the builder |
| EVAPCO AT 224-2N18 cooling tower (1215 tons, 5.3 MW) — modelled Example modelled from published data EVAPCO's 224-2N18 — an AT cooling tower, 1215 nominal tons (5341 kW): rated to cool 3657 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 141.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4006–6676 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1424-13T cooling tower (1246 tons, 5.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1424-13T — a Series 3000 cooling tower, 1246 nominal tons (5477 kW): rated to cool 3750 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 135.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4108–6846 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers