Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 2,209–2,232 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 224-3O20 cooling tower (1477 tons, 6.5 MW) — modelled Example modelled from published data EVAPCO's 224-3O20 — an AT cooling tower, 1477 nominal tons (6493 kW): rated to cool 4446 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 150.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4870–8117 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-513A evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-513A — a VCA evaporative condenser rejecting 2210 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1658–2763 kW | EU | Open in the builder |
| EVAPCO AT 224-4J18 cooling tower (1032 tons, 4.5 MW) — modelled Example modelled from published data EVAPCO's 224-4J18 — an AT cooling tower, 1032 nominal tons (4535 kW): rated to cool 3105 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 100.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3401–5668 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0601B-1024N-HB evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0601B-1024N-HB — a Vertex VRC evaporative condenser rejecting 3648 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 71.2 m³/s of the maker's own printed air, with a 38.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2736–4560 kW | EU | Open in the builder |
| EVAPCO AT 224-4K18 cooling tower (1141 tons, 5.0 MW) — modelled Example modelled from published data EVAPCO's 224-4K18 — an AT cooling tower, 1141 nominal tons (5017 kW): rated to cool 3435 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 109.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3763–6271 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-595-1224-20 evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-595-1224-20 — a CXVB evaporative condenser rejecting 3605 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 65.8 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2704–4506 kW | EU | Open in the builder |
| EVAPCO AT 224-4K20 cooling tower (1115 tons, 4.9 MW) — modelled Example modelled from published data EVAPCO's 224-4K20 — an AT cooling tower, 1115 nominal tons (4903 kW): rated to cool 3357 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 111.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3677–6128 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-1218B-24T-O closed-circuit cooler (346 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-1218B-24T-O — an FXV closed-circuit cooler, 346 nominal tons (1520 kW): rated to cool 1041 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 68.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1140–1900 kW | EU | Open in the builder |
| EVAPCO AT 224-4L18 cooling tower (1209 tons, 5.3 MW) — modelled Example modelled from published data EVAPCO's 224-4L18 — an AT cooling tower, 1209 nominal tons (5315 kW): rated to cool 3639 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 117.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3986–6643 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0590-2012N060 evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0590-2012N060 — a PCC evaporative condenser rejecting 3584 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 74.6 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2688–4480 kW | EU | Open in the builder |
| EVAPCO AT 224-4L20 cooling tower (1206 tons, 5.3 MW) — modelled Example modelled from published data EVAPCO's 224-4L20 — an AT cooling tower, 1206 nominal tons (5301 kW): rated to cool 3630 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 119.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3976–6627 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1012N-5D2DS-M1 closed-circuit cooler (150 tons, 657 kW) — modelled Example modelled from published data BAC's PFI-1012N-5D2DS-M1 — a PFi closed-circuit cooler, 150 nominal tons (657 kW): rated to cool 450 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 32.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 493–822 kW | EU | Open in the builder |
| EVAPCO AT 224-4M18 cooling tower (1279 tons, 5.6 MW) — modelled Example modelled from published data EVAPCO's 224-4M18 — an AT cooling tower, 1279 nominal tons (5621 kW): rated to cool 3849 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 124.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4216–7027 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1285-09KN cooling tower (222 tons, 977 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1285-09KN — a Series 1500 cooling tower, 222 nominal tons (977 kW): rated to cool 669 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 733–1221 kW | EU | Open in the builder |
| EVAPCO AT 224-4M20 cooling tower (1280 tons, 5.6 MW) — modelled Example modelled from published data EVAPCO's 224-4M20 — an AT cooling tower, 1280 nominal tons (5626 kW): rated to cool 3852 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 126.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4219–7032 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1424-14Q cooling tower (1071 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1424-14Q — a Series 3000 cooling tower, 1071 nominal tons (4710 kW): rated to cool 3225 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 118.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3532–5887 kW | EU | Open in the builder |
| EVAPCO AT 224-4N18 cooling tower (1404 tons, 6.2 MW) — modelled Example modelled from published data EVAPCO's 224-4N18 — an AT cooling tower, 1404 nominal tons (6173 kW): rated to cool 4227 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 136.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4630–7717 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-N395-R cooling tower (394 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT1-N395-R — a Series V cooling tower, 394 nominal tons (1731 kW): rated to cool 1185 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1298–2163 kW | EU | Open in the builder |
| EVAPCO AT 224-4N20 cooling tower (1423 tons, 6.3 MW) — modelled Example modelled from published data EVAPCO's 224-4N20 — an AT cooling tower, 1423 nominal tons (6257 kW): rated to cool 4284 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 138.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4692–7821 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-144N-21R closed-circuit cooler (139 tons, 609 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-144N-21R — a Series V closed circuit closed-circuit cooler, 139 nominal tons (609 kW): rated to cool 417 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 36.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 457–761 kW | EU | Open in the builder |
| EVAPCO AT 224-4O18 cooling tower (1508 tons, 6.6 MW) — modelled Example modelled from published data EVAPCO's 224-4O18 — an AT cooling tower, 1508 nominal tons (6629 kW): rated to cool 4539 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 146.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4972–8286 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-526A evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-526A — a VCA evaporative condenser rejecting 2266 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 42.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1700–2833 kW | EU | Open in the builder |
| EVAPCO AT 224-4O20 cooling tower (1540 tons, 6.8 MW) — modelled Example modelled from published data EVAPCO's 224-4O20 — an AT cooling tower, 1540 nominal tons (6769 kW): rated to cool 4635 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 148.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5077–8462 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0609B-1024N-KA evaporative condenser (3.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0609B-1024N-KA — a Vertex VRC evaporative condenser rejecting 3696 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 56.6 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2772–4620 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers