Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 2209–2232 of 3346

EVAPCO AT 424-4N28 cooling tower (2275 tons, 10.0 MW) — modelled

EVAPCO's 424-4N28 — a AT cooling tower, 2275 nominal tons (10003 kW): rated to cool 6849 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 211.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 7502–12503 kW · EU

EVAPCO AT 424-4N36 cooling tower (2727 tons, 12.0 MW) — modelled

EVAPCO's 424-4N36 — a AT cooling tower, 2727 nominal tons (11987 kW): rated to cool 8208 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 263.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 8991–14984 kW · EU

EVAPCO AT 424-4N40 cooling tower (2789 tons, 12.3 MW) — modelled

EVAPCO's 424-4N40 — a AT cooling tower, 2789 nominal tons (12259 kW): rated to cool 8394 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 267.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 9194–15324 kW · EU

EVAPCO AT 424-4O36 cooling tower (2928 tons, 12.9 MW) — modelled

EVAPCO's 424-4O36 — a AT cooling tower, 2928 nominal tons (12872 kW): rated to cool 8814 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 282.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 9654–16091 kW · EU

EVAPCO AT 424-4O40 cooling tower (3018 tons, 13.3 MW) — modelled

EVAPCO's 424-4O40 — a AT cooling tower, 3018 nominal tons (13267 kW): rated to cool 9084 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 287.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 9950–16584 kW · EU

EVAPCO AT 424-4P36 cooling tower (3039 tons, 13.4 MW) — modelled

EVAPCO's 424-4P36 — a AT cooling tower, 3039 nominal tons (13359 kW): rated to cool 9147 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 299.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 10019–16699 kW · EU

EVAPCO AT 424-4P40 cooling tower (3131 tons, 13.8 MW) — modelled

EVAPCO's 424-4P40 — a AT cooling tower, 3131 nominal tons (13762 kW): rated to cool 9423 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 304.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 10321–17202 kW · EU

EVAPCO AT 428-5K52 cooling tower (3844 tons, 16.9 MW) — modelled

EVAPCO's 428-5K52 — a AT cooling tower, 3844 nominal tons (16899 kW): rated to cool 11571 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 352.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 12674–21124 kW · EU

EVAPCO AT 428-5L52 cooling tower (4134 tons, 18.2 MW) — modelled

EVAPCO's 428-5L52 — a AT cooling tower, 4134 nominal tons (18174 kW): rated to cool 12444 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 377.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 13630–22717 kW · EU

EVAPCO AT 428-5M52 cooling tower (4380 tons, 19.3 MW) — modelled

EVAPCO's 428-5M52 — a AT cooling tower, 4380 nominal tons (19256 kW): rated to cool 13185 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 400.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 14442–24070 kW · EU

EVAPCO AT 428-5N52 cooling tower (4790 tons, 21.1 MW) — modelled

EVAPCO's 428-5N52 — a AT cooling tower, 4790 nominal tons (21057 kW): rated to cool 14418 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 437.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 15793–26321 kW · EU

EVAPCO AT 428-5O52 cooling tower (5124 tons, 22.5 MW) — modelled

EVAPCO's 428-5O52 — a AT cooling tower, 5124 nominal tons (22525 kW): rated to cool 15423 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 468.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 16894–28156 kW · EU

EVAPCO AT 456-5K26 cooling tower (3789 tons, 16.7 MW) — modelled

EVAPCO's 456-5K26 — a AT cooling tower, 3789 nominal tons (16658 kW): rated to cool 11406 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 352.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 12494–20823 kW · EU

EVAPCO AT 456-5L26 cooling tower (4076 tons, 17.9 MW) — modelled

EVAPCO's 456-5L26 — a AT cooling tower, 4076 nominal tons (17920 kW): rated to cool 12270 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 378.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 13440–22400 kW · EU

EVAPCO AT 456-5M26 cooling tower (4321 tons, 19.0 MW) — modelled

EVAPCO's 456-5M26 — a AT cooling tower, 4321 nominal tons (18993 kW): rated to cool 13005 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 400.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 14245–23742 kW · EU

EVAPCO AT 456-5N26 cooling tower (4727 tons, 20.8 MW) — modelled

EVAPCO's 456-5N26 — a AT cooling tower, 4727 nominal tons (20781 kW): rated to cool 14229 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 437.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 15586–25976 kW · EU

EVAPCO AT 456-5O26 cooling tower (5058 tons, 22.2 MW) — modelled

EVAPCO's 456-5O26 — a AT cooling tower, 5058 nominal tons (22236 kW): rated to cool 15225 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 469.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 16677–27794 kW · EU

EVAPCO ATWB 10-3I12 closed-circuit cooler (155 tons, 681 kW) — modelled

EVAPCO's 10-3I12 — a ATWB closed-circuit cooler, 155 nominal tons (681 kW): rated to cool 389 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 26.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13F-09R12) ✓
Cooling tower / heat rejection · 511–851 kW · EU

EVAPCO ATWB 10-3I36 closed-circuit cooler (461 tons, 2.0 MW) — modelled

EVAPCO's 10-3I36 — a ATWB closed-circuit cooler, 461 nominal tons (2025 kW): rated to cool 1155 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 69.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13F-09R12) ✓
Cooling tower / heat rejection · 1519–2531 kW · EU

EVAPCO ATWB 10-3J36 closed-circuit cooler (529 tons, 2.3 MW) — modelled

EVAPCO's 10-3J36 — a ATWB closed-circuit cooler, 529 nominal tons (2326 kW): rated to cool 1327 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 79.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13F-09R12) ✓
Cooling tower / heat rejection · 1744–2907 kW · EU

EVAPCO ATWB 10-3K12 closed-circuit cooler (198 tons, 871 kW) — modelled

EVAPCO's 10-3K12 — a ATWB closed-circuit cooler, 198 nominal tons (871 kW): rated to cool 497 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 32.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13F-09R12) ✓
Cooling tower / heat rejection · 653–1088 kW · EU

EVAPCO ATWB 10-3K36 closed-circuit cooler (583 tons, 2.6 MW) — modelled

EVAPCO's 10-3K36 — a ATWB closed-circuit cooler, 583 nominal tons (2561 kW): rated to cool 1462 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 87.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13F-09R12) ✓
Cooling tower / heat rejection · 1921–3202 kW · EU

EVAPCO ATWB 10-3L36 closed-circuit cooler (627 tons, 2.8 MW) — modelled

EVAPCO's 10-3L36 — a ATWB closed-circuit cooler, 627 nominal tons (2758 kW): rated to cool 1574 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 93.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13F-09R12) ✓
Cooling tower / heat rejection · 2069–3448 kW · EU

EVAPCO ATWB 10-3M36 closed-circuit cooler (666 tons, 2.9 MW) — modelled

EVAPCO's 10-3M36 — a ATWB closed-circuit cooler, 666 nominal tons (2929 kW): rated to cool 1671 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 98.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13F-09R12) ✓
Cooling tower / heat rejection · 2197–3661 kW · EU
‹ Previous1…9192939495…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers