Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,257–2,280 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 228-3P24 cooling tower (1962 tons, 8.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-3P24 — an AT cooling tower, 1962 nominal tons (8627 kW): rated to cool 5907 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 205.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6470–10784 kWEUOpen in the builder
Baltimore Aircoil PCC-0609-1218N050 evaporative condenser (3.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0609-1218N050 — a PCC evaporative condenser rejecting 3699 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 58.0 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2774–4624 kWEUOpen in the builder
EVAPCO AT 228-4K24 cooling tower (1503 tons, 6.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-4K24 — an AT cooling tower, 1503 nominal tons (6607 kW): rated to cool 4524 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 142.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4955–8259 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-6D1ES-M1 closed-circuit cooler (168 tons, 740 kW) — modelled Example modelled from published data
BAC's PFI-1012N-6D1ES-M1 — a PFi closed-circuit cooler, 168 nominal tons (740 kW): rated to cool 507 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 31.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection555–926 kWEUOpen in the builder
EVAPCO AT 228-4L24 cooling tower (1625 tons, 7.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-4L24 — an AT cooling tower, 1625 nominal tons (7142 kW): rated to cool 4890 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 153.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5356–8927 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1285-09LN cooling tower (253 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
A crossflow, induced-draft tower — the fan pulls through the fill and its motor heat is added after, which is how this model wires it. Rated to cool 759 USGPM from 95 to 85 °F at a 78 °F entering wet bulb on 26.9 m³/s of air; a 15 hp fan motor. Series 1500 is BAC's induced-draft crossflow range from 92 to 747 nominal tons a cell. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection900–1350 kWEUOpen in the builder
EVAPCO AT 228-4M24 cooling tower (1700 tons, 7.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-4M24 — an AT cooling tower, 1700 nominal tons (7475 kW): rated to cool 5118 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 162.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5606–9343 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-14R cooling tower (1130 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-14R — a Series 3000 cooling tower, 1130 nominal tons (4968 kW): rated to cool 3402 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 124.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3726–6211 kWEUOpen in the builder
EVAPCO AT 228-4N24 cooling tower (1847 tons, 8.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-4N24 — an AT cooling tower, 1847 nominal tons (8119 kW): rated to cool 5559 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 177.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6089–10148 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-N440-O cooling tower (439 tons, 1.9 MW) — modelled Example modelled from published data
BAC's VT1-N440-O — a Series V cooling tower, 439 nominal tons (1928 kW): rated to cool 1320 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1446–2410 kWEUOpen in the builder
EVAPCO AT 228-4O24 cooling tower (1946 tons, 8.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-4O24 — an AT cooling tower, 1946 nominal tons (8552 kW): rated to cool 5856 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 190.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6414–10691 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-144N-31Q closed-circuit cooler (136 tons, 596 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-144N-31Q — a Series V closed circuit closed-circuit cooler, 136 nominal tons (596 kW): rated to cool 408 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 33.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection447–745 kWEUOpen in the builder
EVAPCO AT 228-4P24 cooling tower (2060 tons, 9.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-4P24 — an AT cooling tower, 2060 nominal tons (9056 kW): rated to cool 6201 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 202.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6792–11320 kWEUOpen in the builder
Baltimore Aircoil VCA-541A evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-541A — a VCA evaporative condenser rejecting 2331 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.5 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1748–2913 kWEUOpen in the builder
EVAPCO AT 228-4Q24 cooling tower (2214 tons, 9.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-4Q24 — an AT cooling tower, 2214 nominal tons (9731 kW): rated to cool 6663 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 216.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7298–12164 kWEUOpen in the builder
Baltimore Aircoil VRC-0615B-1024N-JA evaporative condenser (3.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0615B-1024N-JA — a Vertex VRC evaporative condenser rejecting 3731 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 53.9 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2798–4663 kWEUOpen in the builder
EVAPCO AT 228-5K26 cooling tower (1956 tons, 8.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-5K26 — an AT cooling tower, 1956 nominal tons (8601 kW): rated to cool 5889 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 185.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6450–10751 kWEUOpen in the builder
Baltimore Aircoil CXVB-604-1224-40 evaporative condenser (3.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-604-1224-40 — a CXVB evaporative condenser rejecting 3659 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 83.7 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2744–4574 kWEUOpen in the builder
EVAPCO AT 228-5L26 cooling tower (2104 tons, 9.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-5L26 — an AT cooling tower, 2104 nominal tons (9249 kW): rated to cool 6333 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 198.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6937–11561 kWEUOpen in the builder
Baltimore Aircoil FXV-1218C-16Q-P closed-circuit cooler (295 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1218C-16Q-P — an FXV closed-circuit cooler, 295 nominal tons (1297 kW): rated to cool 888 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 80.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection973–1621 kWEUOpen in the builder
EVAPCO AT 228-5M26 cooling tower (2229 tons, 9.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-5M26 — an AT cooling tower, 2229 nominal tons (9797 kW): rated to cool 6708 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 210.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7348–12246 kWEUOpen in the builder
Baltimore Aircoil PCC-0614-1220N050 evaporative condenser (3.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0614-1220N050 — a PCC evaporative condenser rejecting 3730 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 68.8 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2797–4662 kWEUOpen in the builder
EVAPCO AT 228-5N26 cooling tower (2435 tons, 10.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 228-5N26 — an AT cooling tower, 2435 nominal tons (10704 kW): rated to cool 7329 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 229.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection8028–13380 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-6D1ES-O1 closed-circuit cooler (185 tons, 815 kW) — modelled Example modelled from published data
BAC's PFI-1012N-6D1ES-O1 — a PFi closed-circuit cooler, 185 nominal tons (815 kW): rated to cool 558 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 35.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection611–1019 kWEUOpen in the builder
‹ Previous1…9394959697…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers