EVAPCO AT 26-4J17 cooling tower (343 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 26-4J17 — an AT cooling tower, 343 nominal tons (1507 kW): rated to cool 1032 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1130–1884 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-N510-P cooling tower (508 tons, 2.2 MW) — modelled Example modelled from published data
BAC's VT1-N510-P — a Series V cooling tower, 508 nominal tons (2235 kW): rated to cool 1530 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1676–2793 kWEUOpen in the builder
EVAPCO AT 27-2G36 cooling tower (443 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2G36 — an AT cooling tower, 443 nominal tons (1945 kW): rated to cool 1332 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 62.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1459–2432 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-144N-41P closed-circuit cooler (130 tons, 570 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-144N-41P — a Series V closed circuit closed-circuit cooler, 130 nominal tons (570 kW): rated to cool 390 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 31.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection427–712 kWEUOpen in the builder
EVAPCO AT 27-2H24 cooling tower (322 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2H24 — an AT cooling tower, 322 nominal tons (1415 kW): rated to cool 969 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 43.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1061–1769 kWEUOpen in the builder
Baltimore Aircoil VCA-560A evaporative condenser (2.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-560A — a VCA evaporative condenser rejecting 2413 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 45.2 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1809–3016 kWEUOpen in the builder
EVAPCO AT 27-2H28 cooling tower (342 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2H28 — an AT cooling tower, 342 nominal tons (1503 kW): rated to cool 1029 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 48.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1127–1879 kWEUOpen in the builder
Baltimore Aircoil VRC-0630B-1218N-MA evaporative condenser (3.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0630B-1218N-MA — a Vertex VRC evaporative condenser rejecting 3821 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 63.5 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2866–4777 kWEUOpen in the builder
EVAPCO AT 27-2H36 cooling tower (529 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2H36 — an AT cooling tower, 529 nominal tons (2327 kW): rated to cool 1593 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1745–2908 kWEUOpen in the builder
Baltimore Aircoil CXVB-628-1218-60 evaporative condenser (3.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-628-1218-60 — a CXVB evaporative condenser rejecting 3805 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 78.0 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2853–4756 kWEUOpen in the builder
EVAPCO AT 27-2I24 cooling tower (355 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2I24 — an AT cooling tower, 355 nominal tons (1560 kW): rated to cool 1068 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1170–1950 kWEUOpen in the builder
Baltimore Aircoil FXV-1218C-23Q-P closed-circuit cooler (361 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1218C-23Q-P — an FXV closed-circuit cooler, 361 nominal tons (1586 kW): rated to cool 1086 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 78.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1190–1983 kWEUOpen in the builder
EVAPCO AT 27-2I28 cooling tower (485 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2I28 — an AT cooling tower, 485 nominal tons (2134 kW): rated to cool 1461 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1600–2667 kWEUOpen in the builder
Baltimore Aircoil PCC-0618-2412N040 evaporative condenser (3.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0618-2412N040 — a PCC evaporative condenser rejecting 3754 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 72.1 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2815–4692 kWEUOpen in the builder
EVAPCO AT 27-2I36 cooling tower (586 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2I36 — an AT cooling tower, 586 nominal tons (2576 kW): rated to cool 1764 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1932–3220 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-2D2ES-L2 closed-circuit cooler (178 tons, 784 kW) — modelled Example modelled from published data
BAC's PFI-1024N-2D2ES-L2 — a PFi closed-circuit cooler, 178 nominal tons (784 kW): rated to cool 537 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 64.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection588–980 kWEUOpen in the builder
EVAPCO AT 27-2J24 cooling tower (409 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2J24 — an AT cooling tower, 409 nominal tons (1796 kW): rated to cool 1230 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1347–2245 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1285-09MN-2 cooling tower (550 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1285-09MN-2 — a Series 1500 cooling tower, 550 nominal tons (2419 kW): rated to cool 1656 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1814–3023 kWEUOpen in the builder
EVAPCO AT 27-2J28 cooling tower (431 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2J28 — an AT cooling tower, 431 nominal tons (1893 kW): rated to cool 1296 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1420–2366 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-14S-2 cooling tower (2423 tons, 10.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-14S-2 — a Series 3000 cooling tower, 2423 nominal tons (10651 kW): rated to cool 7293 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 265.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7988–13314 kWEUOpen in the builder
EVAPCO AT 27-2J36 cooling tower (674 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2J36 — an AT cooling tower, 674 nominal tons (2962 kW): rated to cool 2028 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 88.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2221–3702 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-016-E cooling tower (16 tons, 70 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-016-E — a Series V cooling tower, 16 nominal tons (70 kW): rated to cool 48 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 3.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection53–88 kWEUOpen in the builder
EVAPCO AT 27-2K24 cooling tower (451 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 27-2K24 — an AT cooling tower, 451 nominal tons (1985 kW): rated to cool 1359 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1489–2481 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-144N-41Q closed-circuit cooler (144 tons, 631 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-144N-41Q — a Series V closed circuit closed-circuit cooler, 144 nominal tons (631 kW): rated to cool 432 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 33.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection473–789 kWEUOpen in the builder