992 listing(s) in HVAC Builder's catalog from EVAPCO's published data and 992 system(s) modelled on it — 0 built by hand and 992 derived from the listings themselves — selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; EVAPCO has not claimed it.

Are you EVAPCO?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Listings

All kindsCooling tower 992
Any certificationCTI STD-201 (validation C13A-99R28) 822
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 745–768 of 992

EVAPCO AT 29-3K24 cooling tower

Cooling tower — 2760 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 63.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-3K28 cooling tower

Cooling tower — 3058 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 71.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-3L24 cooling tower

Cooling tower — 2953 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 68.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-3L28 cooling tower

Cooling tower — 3317 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 76.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-3M28 cooling tower

Cooling tower — 3514 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 80.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4G18 cooling tower

Cooling tower — 1468 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 32.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4G21 cooling tower

Cooling tower — 1678 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 36.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4H18 cooling tower

Cooling tower — 1696 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 37.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4H21 cooling tower

Cooling tower — 1950 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 42.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4H24 cooling tower

Cooling tower — 2107 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 45.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4H28 cooling tower

Cooling tower — 2344 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 51.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4I18 cooling tower

Cooling tower — 1862 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 41.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4I21 cooling tower

Cooling tower — 2112 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 46.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4I24 cooling tower

Cooling tower — 2327 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 50.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4I28 cooling tower

Cooling tower — 2594 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 56.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4J18 cooling tower

Cooling tower — 2151 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 46.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4J21 cooling tower

Cooling tower — 2397 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 52.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4J24 cooling tower

Cooling tower — 2598 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 57.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4J28 cooling tower

Cooling tower — 2896 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 64.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4K18 cooling tower

Cooling tower — 2357 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 50.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4K21 cooling tower

Cooling tower — 2646 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 57.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4K24 cooling tower

Cooling tower — 2861 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 62.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4K28 cooling tower

Cooling tower — 3181 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 70.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 29-4L21 cooling tower

Cooling tower — 2787 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 61.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower
‹ Previous1…3031323334…42Next ›

How the model reads against EVAPCO's data

Cooling-tower model, zero fitted parameters856mean −0.03 K, RMS 0.064 K, worst 0.24 K — NTU from the vendor's own Eurovent column, the shipped default exponent (−0.7, the joint minimum with Marley's table)
Cooling-tower model against a fourth maker's whole open-tower range, nothing fitted to it45 945 over 992 machinesmean −0.083 K, RMS 0.220 K, worst 1.89 K on leaving water. 0.098 K at the 78 °F rating wet bulb, where the NTU is derived, rising to 0.283 and 0.288 K at 50 and 90 °F. The fill's loading exponent was swept on either half of the range and the shipped default (−0.7, the joint minimum of EVAPCO's own LPT bulletin and Marley's table) is the minimum for this range too, so it carries no constant of its own — unlike BAC's five, which wanted −0.9 to −1.3

From the validation page; every row is held by a test.

Worked cases that run EVAPCO machines

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.