Copeland YB83KAE-TFD (R452A scroll, 60 Hz, MT)
R452A compressor — 22.7 kW cooling, 10.85 kW input, COP 2.09 at -15/40 °C (evaporating/condensing), inside its published envelope.
Copeland YB83KAE-TFD (R454A scroll, 50 Hz, MT)
R454A compressor — 20.1 kW cooling, 8.38 kW input, COP 2.39 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YB83KAE-TFD (R454A scroll, 60 Hz, MT)
R454A compressor — 24.1 kW cooling, 10.05 kW input, COP 2.39 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YB83KAE-TFD (R454C scroll, 50 Hz, MT)
R454C compressor — 17.4 kW cooling, 7.10 kW input, COP 2.45 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YB83KAE-TFD (R454C scroll, 60 Hz, MT)
R454C compressor — 20.9 kW cooling, 8.52 kW input, COP 2.45 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YB83KAE-TFD (R455A scroll, 50 Hz, MT)
R455A compressor — 18.8 kW cooling, 7.50 kW input, COP 2.51 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YB83KAE-TFD (R455A scroll, 60 Hz, MT)
R455A compressor — 22.6 kW cooling, 9.00 kW input, COP 2.51 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YB83KAE-TFD (R513A scroll, 50 Hz, HT)
R513A compressor — 23.3 kW cooling, 8.24 kW input, COP 2.83 at the AHRI 7.2/54.4 °C rating point.
Copeland YB83KAE-TFD (R513A scroll, 60 Hz, HT)
R513A compressor — 28.0 kW cooling, 9.89 kW input, COP 2.83 at the AHRI 7.2/54.4 °C rating point.
Copeland YB97K1G-TFD (R290 scroll, 50 Hz, MT)
R290 compressor — 35.6 kW cooling, 11.69 kW input, COP 3.04 at the AHRI 7.2/54.4 °C rating point.
Copeland YB97K1G-TFD (R290 scroll, 60 Hz, MT)
R290 compressor — 42.7 kW cooling, 14.02 kW input, COP 3.04 at the AHRI 7.2/54.4 °C rating point.
Copeland YBD100KAE-TFD (R134A scroll, 50 Hz, HT)
R134a compressor — 27.7 kW cooling, 9.72 kW input, COP 2.85 at the AHRI 7.2/54.4 °C rating point.
Copeland YBD100KAE-TFD (R134A scroll, 60 Hz, HT)
R134a compressor — 34.0 kW cooling, 11.36 kW input, COP 3.00 at the AHRI 7.2/54.4 °C rating point.
Copeland YBD100KAE-TFD (R407C scroll, 50 Hz, HT)
R407C compressor — 40.5 kW cooling, 13.65 kW input, COP 2.97 at the AHRI 7.2/54.4 °C rating point.
Copeland YBD100KAE-TFD (R407C scroll, 60 Hz, HT)
R407C compressor — 49.0 kW cooling, 16.41 kW input, COP 2.98 at the AHRI 7.2/54.4 °C rating point.
Copeland YBD100KAE-TFD (R513A scroll, 50 Hz, HT)
R513A compressor — 27.8 kW cooling, 10.18 kW input, COP 2.73 at the AHRI 7.2/54.4 °C rating point.
Copeland YBD100KAE-TFD (R513A scroll, 60 Hz, HT)
R513A compressor — 33.3 kW cooling, 12.22 kW input, COP 2.73 at the AHRI 7.2/54.4 °C rating point.
Copeland YBD17K1E-TFD (R1234yf scroll, 60 Hz, MT)
R1234yf compressor — 3.5 kW cooling, 1.38 kW input, COP 2.57 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YBD17K1E-TFD (R134A scroll, 60 Hz, MT)
R134a compressor — 3.3 kW cooling, 1.34 kW input, COP 2.45 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YBD17K1E-TFD (R404A scroll, 60 Hz, MT)
R404A compressor — 6.0 kW cooling, 2.37 kW input, COP 2.55 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YBD17K1E-TFD (R407A scroll, 60 Hz, MT)
R407A compressor — 5.5 kW cooling, 2.10 kW input, COP 2.60 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YBD17K1E-TFD (R407C scroll, 60 Hz, MT)
R407C compressor — 5.0 kW cooling, 1.96 kW input, COP 2.56 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YBD17K1E-TFD (R407F scroll, 60 Hz, MT)
R407F compressor — 5.8 kW cooling, 2.24 kW input, COP 2.60 at -15/35 °C (evaporating/condensing), inside its published envelope.
Copeland YBD17K1E-TFD (R448A scroll, 50 Hz, MT)
R448A compressor — 4.6 kW cooling, 1.78 kW input, COP 2.57 at -15/35 °C (evaporating/condensing), inside its published envelope.