Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 2,521–2,544 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 29-4J21 cooling tower (545 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4J21 — an AT cooling tower, 545 nominal tons (2397 kW): rated to cool 1641 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1797–2996 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-623A evaporative condenser (2.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-623A — a VCA evaporative condenser rejecting 2684 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 53.3 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2013–3355 kW | EU | Open in the builder |
| EVAPCO AT 29-4J24 cooling tower (591 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4J24 — an AT cooling tower, 591 nominal tons (2598 kW): rated to cool 1779 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1949–3248 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0693B-1024N-HB evaporative condenser (4.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0693B-1024N-HB — a Vertex VRC evaporative condenser rejecting 4202 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 60.9 m³/s of the maker's own printed air, with a 38.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3152–5253 kW | EU | Open in the builder |
| EVAPCO AT 29-4J28 cooling tower (659 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4J28 — an AT cooling tower, 659 nominal tons (2896 kW): rated to cool 1983 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2172–3620 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-762-1224-60 evaporative condenser (4.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-762-1224-60 — a CXVB evaporative condenser rejecting 4616 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 93.0 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3462–5771 kW | EU | Open in the builder |
| EVAPCO AT 29-4K18 cooling tower (536 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4K18 — an AT cooling tower, 536 nominal tons (2357 kW): rated to cool 1614 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1768–2946 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0660-1224N050 evaporative condenser (4.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0660-1224N050 — a PCC evaporative condenser rejecting 4009 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 77.0 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3007–5011 kW | EU | Open in the builder |
| EVAPCO AT 29-4K21 cooling tower (602 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4K21 — an AT cooling tower, 602 nominal tons (2646 kW): rated to cool 1812 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1985–3308 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1024N-3D4DS-M2 closed-circuit cooler (251 tons, 1.1 MW) — modelled Example modelled from published data BAC's PFI-1024N-3D4DS-M2 — a PFi closed-circuit cooler, 251 nominal tons (1104 kW): rated to cool 756 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 65.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 828–1380 kW | EU | Open in the builder |
| EVAPCO AT 29-4K24 cooling tower (651 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4K24 — an AT cooling tower, 651 nominal tons (2861 kW): rated to cool 1959 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 62.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2146–3576 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1212-07HC cooling tower (225 tons, 990 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1212-07HC — a Series 1500 cooling tower, 225 nominal tons (990 kW): rated to cool 678 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 743–1238 kW | EU | Open in the builder |
| EVAPCO AT 29-4K28 cooling tower (724 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4K28 — an AT cooling tower, 724 nominal tons (3181 kW): rated to cool 2178 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2386–3976 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-8518-06L cooling tower (328 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-8518-06L — a Series 3000 cooling tower, 328 nominal tons (1441 kW): rated to cool 987 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1081–1802 kW | EU | Open in the builder |
| EVAPCO AT 29-4L21 cooling tower (634 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4L21 — an AT cooling tower, 634 nominal tons (2787 kW): rated to cool 1908 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2090–3483 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VTL-079-K cooling tower (79 tons, 346 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VTL-079-K — a Series V cooling tower, 79 nominal tons (346 kW): rated to cool 237 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 260–433 kW | EU | Open in the builder |
| EVAPCO AT 29-4L24 cooling tower (694 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4L24 — an AT cooling tower, 694 nominal tons (3049 kW): rated to cool 2088 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 66.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2287–3812 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-216-21O closed-circuit cooler (187 tons, 824 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-216-21O — a Series V closed circuit closed-circuit cooler, 187 nominal tons (824 kW): rated to cool 564 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 59.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 618–1030 kW | EU | Open in the builder |
| EVAPCO AT 29-4L28 cooling tower (784 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4L28 — an AT cooling tower, 784 nominal tons (3448 kW): rated to cool 2361 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2586–4310 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-626A evaporative condenser (2.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-626A — a VCA evaporative condenser rejecting 2697 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 40.2 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2023–3371 kW | EU | Open in the builder |
| EVAPCO AT 29-4M24 cooling tower (716 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4M24 — an AT cooling tower, 716 nominal tons (3146 kW): rated to cool 2154 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2359–3932 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0694B-1224N-HB evaporative condenser (4.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0694B-1224N-HB — a Vertex VRC evaporative condenser rejecting 4209 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 77.4 m³/s of the maker's own printed air, with a 38.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3157–5261 kW | EU | Open in the builder |
| EVAPCO AT 29-4M28 cooling tower (827 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 29-4M28 — an AT cooling tower, 827 nominal tons (3637 kW): rated to cool 2490 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2727–4546 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-786-1224-60 evaporative condenser (4.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-786-1224-60 — a CXVB evaporative condenser rejecting 4762 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 93.0 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3571–5952 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers