Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,473–2,496 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 29-3I21 cooling tower (447 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3I21 — an AT cooling tower, 447 nominal tons (1963 kW): rated to cool 1344 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1472–2454 kWEUOpen in the builder
Baltimore Aircoil PCC-0656-1024N060 evaporative condenser (4.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0656-1024N060 — a PCC evaporative condenser rejecting 3985 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 63.4 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2989–4981 kWEUOpen in the builder
EVAPCO AT 29-3I24 cooling tower (504 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3I24 — an AT cooling tower, 504 nominal tons (2217 kW): rated to cool 1518 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1663–2771 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-3D2ES-O2 closed-circuit cooler (278 tons, 1.2 MW) — modelled Example modelled from published data
BAC's PFI-1024N-3D2ES-O2 — a PFi closed-circuit cooler, 278 nominal tons (1222 kW): rated to cool 837 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 77.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection917–1528 kWEUOpen in the builder
EVAPCO AT 29-3I28 cooling tower (561 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3I28 — an AT cooling tower, 561 nominal tons (2467 kW): rated to cool 1689 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1850–3083 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-07FN cooling tower (182 tons, 802 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-07FN — a Series 1500 cooling tower, 182 nominal tons (802 kW): rated to cool 549 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 20.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection601–1002 kWEUOpen in the builder
EVAPCO AT 29-3J18 cooling tower (469 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3J18 — an AT cooling tower, 469 nominal tons (2064 kW): rated to cool 1413 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1548–2580 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-8518-05L-2 cooling tower (583 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-8518-05L-2 — a Series 3000 cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 73.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1922–3204 kWEUOpen in the builder
EVAPCO AT 29-3J21 cooling tower (516 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3J21 — an AT cooling tower, 516 nominal tons (2270 kW): rated to cool 1554 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1702–2837 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-059-H cooling tower (59 tons, 259 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-059-H — a Series V cooling tower, 59 nominal tons (259 kW): rated to cool 177 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 7.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection194–323 kWEUOpen in the builder
EVAPCO AT 29-3J24 cooling tower (569 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3J24 — an AT cooling tower, 569 nominal tons (2502 kW): rated to cool 1713 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1876–3127 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-192-51P closed-circuit cooler (206 tons, 907 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-192-51P — a Series V closed circuit closed-circuit cooler, 206 nominal tons (907 kW): rated to cool 621 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 54.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection680–1134 kWEUOpen in the builder
EVAPCO AT 29-3J28 cooling tower (631 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3J28 — an AT cooling tower, 631 nominal tons (2773 kW): rated to cool 1899 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2080–3467 kWEUOpen in the builder
Baltimore Aircoil VCA-609A evaporative condenser (2.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-609A — a VCA evaporative condenser rejecting 2624 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.6 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1968–3279 kWEUOpen in the builder
EVAPCO AT 29-3K21 cooling tower (576 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3K21 — an AT cooling tower, 576 nominal tons (2532 kW): rated to cool 1734 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1899–3166 kWEUOpen in the builder
Baltimore Aircoil VRC-0672B-1024N-LA evaporative condenser (4.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0672B-1024N-LA — a Vertex VRC evaporative condenser rejecting 4075 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.8 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3057–5094 kWEUOpen in the builder
EVAPCO AT 29-3K24 cooling tower (628 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3K24 — an AT cooling tower, 628 nominal tons (2760 kW): rated to cool 1890 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2070–3450 kWEUOpen in the builder
Baltimore Aircoil CXVB-739-1224-50 evaporative condenser (4.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-739-1224-50 — a CXVB evaporative condenser rejecting 4477 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 88.3 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3358–5597 kWEUOpen in the builder
EVAPCO AT 29-3K28 cooling tower (696 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3K28 — an AT cooling tower, 696 nominal tons (3058 kW): rated to cool 2094 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2294–3823 kWEUOpen in the builder
Baltimore Aircoil PCC-0656-2012N060 evaporative condenser (4.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0656-2012N060 — a PCC evaporative condenser rejecting 3985 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 63.4 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2989–4981 kWEUOpen in the builder
EVAPCO AT 29-3L24 cooling tower (672 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3L24 — an AT cooling tower, 672 nominal tons (2953 kW): rated to cool 2022 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2215–3691 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-3D3DS-N2 closed-circuit cooler (259 tons, 1.1 MW) — modelled Example modelled from published data
BAC's PFI-1024N-3D3DS-N2 — a PFi closed-circuit cooler, 259 nominal tons (1139 kW): rated to cool 780 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 73.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection854–1424 kWEUOpen in the builder
EVAPCO AT 29-3L28 cooling tower (754 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3L28 — an AT cooling tower, 754 nominal tons (3317 kW): rated to cool 2271 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2488–4146 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-07GC cooling tower (196 tons, 863 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-07GC — a Series 1500 cooling tower, 196 nominal tons (863 kW): rated to cool 591 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 22.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection647–1079 kWEUOpen in the builder
‹ Previous1…102103104105106…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers