Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,425–2,448 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 29-2G18 cooling tower (273 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2G18 — an AT cooling tower, 273 nominal tons (1200 kW): rated to cool 822 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection900–1501 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-039-H cooling tower (39 tons, 171 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-039-H — a Series V cooling tower, 39 nominal tons (171 kW): rated to cool 117 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 4.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection128–214 kWEUOpen in the builder
EVAPCO AT 29-2G21 cooling tower (314 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2G21 — an AT cooling tower, 314 nominal tons (1380 kW): rated to cool 945 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1035–1725 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-192-41O closed-circuit cooler (173 tons, 762 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-192-41O — a Series V closed circuit closed-circuit cooler, 173 nominal tons (762 kW): rated to cool 522 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 49.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection572–953 kWEUOpen in the builder
EVAPCO AT 29-2H18 cooling tower (328 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2H18 — an AT cooling tower, 328 nominal tons (1441 kW): rated to cool 987 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1081–1802 kWEUOpen in the builder
Baltimore Aircoil VCA-600A evaporative condenser (2.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-600A — a VCA evaporative condenser rejecting 2585 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 49.7 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1939–3231 kWEUOpen in the builder
EVAPCO AT 29-2H21 cooling tower (378 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2H21 — an AT cooling tower, 378 nominal tons (1661 kW): rated to cool 1137 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 43.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1245–2076 kWEUOpen in the builder
Baltimore Aircoil VRC-0661B-1236N-GA evaporative condenser (4.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0661B-1236N-GA — a Vertex VRC evaporative condenser rejecting 4008 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 71.5 m³/s of the maker's own printed air, with a 13.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3006–5010 kWEUOpen in the builder
EVAPCO AT 29-2H24 cooling tower (399 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2H24 — an AT cooling tower, 399 nominal tons (1753 kW): rated to cool 1200 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1314–2191 kWEUOpen in the builder
Baltimore Aircoil CXVB-682-1224-40 evaporative condenser (4.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-682-1224-40 — a CXVB evaporative condenser rejecting 4132 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 82.4 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3099–5165 kWEUOpen in the builder
EVAPCO AT 29-2H28 cooling tower (445 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2H28 — an AT cooling tower, 445 nominal tons (1954 kW): rated to cool 1338 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1466–2443 kWEUOpen in the builder
Baltimore Aircoil FXV-1218C-36T-L closed-circuit cooler (332 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1218C-36T-L — an FXV closed-circuit cooler, 332 nominal tons (1459 kW): rated to cool 999 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 56.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1094–1824 kWEUOpen in the builder
EVAPCO AT 29-2I18 cooling tower (361 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2I18 — an AT cooling tower, 361 nominal tons (1586 kW): rated to cool 1086 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1190–1983 kWEUOpen in the builder
Baltimore Aircoil PCC-0646-1024N060 evaporative condenser (3.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0646-1024N060 — a PCC evaporative condenser rejecting 3924 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 67.1 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2943–4905 kWEUOpen in the builder
EVAPCO AT 29-2I21 cooling tower (407 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2I21 — an AT cooling tower, 407 nominal tons (1788 kW): rated to cool 1224 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1341–2235 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-3D2ES-L2 closed-circuit cooler (242 tons, 1.1 MW) — modelled Example modelled from published data
BAC's PFI-1024N-3D2ES-L2 — a PFi closed-circuit cooler, 242 nominal tons (1065 kW): rated to cool 729 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 61.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection799–1331 kWEUOpen in the builder
EVAPCO AT 29-2I24 cooling tower (452 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2I24 — an AT cooling tower, 452 nominal tons (1989 kW): rated to cool 1362 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1492–2486 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1285-10NN-2 cooling tower (618 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1285-10NN-2 — a Series 1500 cooling tower, 618 nominal tons (2716 kW): rated to cool 1860 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2037–3396 kWEUOpen in the builder
EVAPCO AT 29-2I28 cooling tower (504 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2I28 — an AT cooling tower, 504 nominal tons (2217 kW): rated to cool 1518 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1663–2771 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-14W-2 cooling tower (2778 tons, 12.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-14W-2 — a Series 3000 cooling tower, 2778 nominal tons (12211 kW): rated to cool 8361 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 303.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection9158–15264 kWEUOpen in the builder
EVAPCO AT 29-2J18 cooling tower (421 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2J18 — an AT cooling tower, 421 nominal tons (1849 kW): rated to cool 1266 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 48.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1387–2311 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-045-H cooling tower (45 tons, 197 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-045-H — a Series V cooling tower, 45 nominal tons (197 kW): rated to cool 135 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection148–246 kWEUOpen in the builder
EVAPCO AT 29-2J21 cooling tower (465 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2J21 — an AT cooling tower, 465 nominal tons (2046 kW): rated to cool 1401 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1535–2558 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-192-41P closed-circuit cooler (197 tons, 868 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-192-41P — a Series V closed circuit closed-circuit cooler, 197 nominal tons (868 kW): rated to cool 594 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 54.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection651–1084 kWEUOpen in the builder
‹ Previous1…100101102103104…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers