Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 2,401–2,424 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 28-2H17 cooling tower (296 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-2H17 — an AT cooling tower, 296 nominal tons (1301 kW): rated to cool 891 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 976–1627 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1285-10MN-2 cooling tower (576 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1285-10MN-2 — a Series 1500 cooling tower, 576 nominal tons (2532 kW): rated to cool 1734 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1899–3166 kW | EU | Open in the builder |
| EVAPCO AT 28-2I17 cooling tower (318 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-2I17 — an AT cooling tower, 318 nominal tons (1398 kW): rated to cool 957 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1048–1747 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1424-14U-2 cooling tower (2739 tons, 12.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1424-14U-2 — a Series 3000 cooling tower, 2739 nominal tons (12040 kW): rated to cool 8244 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 298.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 9030–15050 kW | EU | Open in the builder |
| EVAPCO AT 28-3F17 cooling tower (246 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-3F17 — an AT cooling tower, 246 nominal tons (1082 kW): rated to cool 741 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 812–1353 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VTL-034-H cooling tower (34 tons, 149 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VTL-034-H — a Series V cooling tower, 34 nominal tons (149 kW): rated to cool 102 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 4.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 112–186 kW | EU | Open in the builder |
| EVAPCO AT 28-3G17 cooling tower (303 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-3G17 — an AT cooling tower, 303 nominal tons (1332 kW): rated to cool 912 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 999–1665 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-192-31Q closed-circuit cooler (204 tons, 898 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-192-31Q — a Series V closed circuit closed-circuit cooler, 204 nominal tons (898 kW): rated to cool 615 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 59.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 674–1123 kW | EU | Open in the builder |
| EVAPCO AT 28-3H17 cooling tower (330 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-3H17 — an AT cooling tower, 330 nominal tons (1450 kW): rated to cool 993 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1088–1813 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-585A evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-585A — a VCA evaporative condenser rejecting 2520 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 44.2 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1890–3151 kW | EU | Open in the builder |
| EVAPCO AT 28-3I17 cooling tower (357 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-3I17 — an AT cooling tower, 357 nominal tons (1569 kW): rated to cool 1074 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1176–1961 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0659B-1024N-KA evaporative condenser (4.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0659B-1024N-KA — a Vertex VRC evaporative condenser rejecting 3998 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 59.3 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2999–4998 kW | EU | Open in the builder |
| EVAPCO AT 28-3J17 cooling tower (392 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-3J17 — an AT cooling tower, 392 nominal tons (1722 kW): rated to cool 1179 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1291–2152 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-682-1224-30 evaporative condenser (4.1 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-682-1224-30 — a CXVB evaporative condenser rejecting 4132 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 73.8 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3099–5165 kW | EU | Open in the builder |
| EVAPCO AT 28-4F17 cooling tower (266 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-4F17 — an AT cooling tower, 266 nominal tons (1170 kW): rated to cool 801 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 877–1462 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-1218C-36H-K closed-circuit cooler (272 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-1218C-36H-K — an FXV closed-circuit cooler, 272 nominal tons (1196 kW): rated to cool 819 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 77.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 897–1495 kW | EU | Open in the builder |
| EVAPCO AT 28-4G17 cooling tower (318 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-4G17 — an AT cooling tower, 318 nominal tons (1398 kW): rated to cool 957 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1048–1747 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0640-1220N050 evaporative condenser (3.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0640-1220N050 — a PCC evaporative condenser rejecting 3888 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.3 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2916–4859 kW | EU | Open in the builder |
| EVAPCO AT 28-4H17 cooling tower (345 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-4H17 — an AT cooling tower, 345 nominal tons (1516 kW): rated to cool 1038 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1137–1895 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1024N-3D2DS-M2 closed-circuit cooler (237 tons, 1.0 MW) — modelled Example modelled from published data BAC's PFI-1024N-3D2DS-M2 — a PFi closed-circuit cooler, 237 nominal tons (1043 kW): rated to cool 714 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 70.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 782–1303 kW | EU | Open in the builder |
| EVAPCO AT 28-4I17 cooling tower (372 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-4I17 — an AT cooling tower, 372 nominal tons (1634 kW): rated to cool 1119 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 35.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1226–2043 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1285-10NN cooling tower (309 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1285-10NN — a Series 1500 cooling tower, 309 nominal tons (1358 kW): rated to cool 930 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1019–1698 kW | EU | Open in the builder |
| EVAPCO AT 28-4J17 cooling tower (413 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 28-4J17 — an AT cooling tower, 413 nominal tons (1814 kW): rated to cool 1242 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1360–2267 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1424-14W cooling tower (1389 tons, 6.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1424-14W — a Series 3000 cooling tower, 1389 nominal tons (6108 kW): rated to cool 4182 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 151.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4581–7635 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers