Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,449–2,472 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 29-2J24 cooling tower (505 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2J24 — an AT cooling tower, 505 nominal tons (2221 kW): rated to cool 1521 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1666–2777 kWEUOpen in the builder
Baltimore Aircoil VCA-602A evaporative condenser (2.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-602A — a VCA evaporative condenser rejecting 2593 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 40.2 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1945–3242 kWEUOpen in the builder
EVAPCO AT 29-2J28 cooling tower (561 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2J28 — an AT cooling tower, 561 nominal tons (2467 kW): rated to cool 1689 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 66.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1850–3083 kWEUOpen in the builder
Baltimore Aircoil VRC-0662B-1218N-JB evaporative condenser (4.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0662B-1218N-JB — a Vertex VRC evaporative condenser rejecting 4015 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 54.6 m³/s of the maker's own printed air, with a 40.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3012–5019 kWEUOpen in the builder
EVAPCO AT 29-2K24 cooling tower (557 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2K24 — an AT cooling tower, 557 nominal tons (2449 kW): rated to cool 1677 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1837–3061 kWEUOpen in the builder
Baltimore Aircoil CXVB-711-1224-50 evaporative condenser (4.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-711-1224-50 — a CXVB evaporative condenser rejecting 4308 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 88.8 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3231–5384 kWEUOpen in the builder
EVAPCO AT 29-2K28 cooling tower (620 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2K28 — an AT cooling tower, 620 nominal tons (2725 kW): rated to cool 1866 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2044–3407 kWEUOpen in the builder
Baltimore Aircoil PCC-0646-2012N060 evaporative condenser (3.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0646-2012N060 — a PCC evaporative condenser rejecting 3924 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 67.1 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2943–4905 kWEUOpen in the builder
EVAPCO AT 29-2L28 cooling tower (676 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-2L28 — an AT cooling tower, 676 nominal tons (2971 kW): rated to cool 2034 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 77.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2228–3713 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-3D2ES-M2 closed-circuit cooler (256 tons, 1.1 MW) — modelled Example modelled from published data
BAC's PFI-1024N-3D2ES-M2 — a PFi closed-circuit cooler, 256 nominal tons (1126 kW): rated to cool 771 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 67.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection845–1408 kWEUOpen in the builder
EVAPCO AT 29-3G18 cooling tower (311 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3G18 — an AT cooling tower, 311 nominal tons (1367 kW): rated to cool 936 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1025–1709 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-07EN cooling tower (166 tons, 732 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-07EN — a Series 1500 cooling tower, 166 nominal tons (732 kW): rated to cool 501 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 19.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection549–915 kWEUOpen in the builder
EVAPCO AT 29-3G21 cooling tower (346 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3G21 — an AT cooling tower, 346 nominal tons (1520 kW): rated to cool 1041 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1140–1900 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-8518-05L cooling tower (292 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-8518-05L — a Series 3000 cooling tower, 292 nominal tons (1284 kW): rated to cool 879 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection963–1605 kWEUOpen in the builder
EVAPCO AT 29-3H18 cooling tower (367 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3H18 — an AT cooling tower, 367 nominal tons (1612 kW): rated to cool 1104 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1209–2015 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-051-G cooling tower (51 tons, 223 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-051-G — a Series V cooling tower, 51 nominal tons (223 kW): rated to cool 153 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 6.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection168–279 kWEUOpen in the builder
EVAPCO AT 29-3H21 cooling tower (409 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3H21 — an AT cooling tower, 409 nominal tons (1796 kW): rated to cool 1230 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1347–2245 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-192-41Q closed-circuit cooler (218 tons, 960 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-192-41Q — a Series V closed circuit closed-circuit cooler, 218 nominal tons (960 kW): rated to cool 657 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 58.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection720–1199 kWEUOpen in the builder
EVAPCO AT 29-3H24 cooling tower (450 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3H24 — an AT cooling tower, 450 nominal tons (1980 kW): rated to cool 1356 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1485–2475 kWEUOpen in the builder
Baltimore Aircoil VCA-605A evaporative condenser (2.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-605A — a VCA evaporative condenser rejecting 2607 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 47.6 m³/s of the maker's own printed air, with a 8.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1955–3258 kWEUOpen in the builder
EVAPCO AT 29-3H28 cooling tower (500 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3H28 — an AT cooling tower, 500 nominal tons (2199 kW): rated to cool 1506 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1650–2749 kWEUOpen in the builder
Baltimore Aircoil VRC-0665B-1024N-JB evaporative condenser (4.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0665B-1024N-JB — a Vertex VRC evaporative condenser rejecting 4032 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 82.7 m³/s of the maker's own printed air, with a 60.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3024–5040 kWEUOpen in the builder
EVAPCO AT 29-3I18 cooling tower (403 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3I18 — an AT cooling tower, 403 nominal tons (1770 kW): rated to cool 1212 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1328–2213 kWEUOpen in the builder
Baltimore Aircoil CXVB-719-1236-30 evaporative condenser (4.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-719-1236-30 — a CXVB evaporative condenser rejecting 4356 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 102.5 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3267–5445 kWEUOpen in the builder
‹ Previous1…101102103104105…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers