Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,497–2,520 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 29-3M28 cooling tower (799 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-3M28 — an AT cooling tower, 799 nominal tons (3514 kW): rated to cool 2406 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 80.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2635–4392 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-8518-05M cooling tower (321 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-8518-05M — a Series 3000 cooling tower, 321 nominal tons (1411 kW): rated to cool 966 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1058–1764 kWEUOpen in the builder
EVAPCO AT 29-4G18 cooling tower (334 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4G18 — an AT cooling tower, 334 nominal tons (1468 kW): rated to cool 1005 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1101–1835 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-066-J cooling tower (66 tons, 289 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-066-J — a Series V cooling tower, 66 nominal tons (289 kW): rated to cool 198 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection217–361 kWEUOpen in the builder
EVAPCO AT 29-4G21 cooling tower (382 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4G21 — an AT cooling tower, 382 nominal tons (1678 kW): rated to cool 1149 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1259–2098 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-192-51Q closed-circuit cooler (227 tons, 999 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-192-51Q — a Series V closed circuit closed-circuit cooler, 227 nominal tons (999 kW): rated to cool 684 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 58.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection749–1249 kWEUOpen in the builder
EVAPCO AT 29-4H18 cooling tower (386 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4H18 — an AT cooling tower, 386 nominal tons (1696 kW): rated to cool 1161 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1272–2119 kWEUOpen in the builder
Baltimore Aircoil VCA-620A evaporative condenser (2.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-620A — a VCA evaporative condenser rejecting 2671 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 47.4 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2003–3339 kWEUOpen in the builder
EVAPCO AT 29-4H21 cooling tower (444 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4H21 — an AT cooling tower, 444 nominal tons (1950 kW): rated to cool 1335 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1462–2437 kWEUOpen in the builder
Baltimore Aircoil VRC-0680B-1218N-MA evaporative condenser (4.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0680B-1218N-MA — a Vertex VRC evaporative condenser rejecting 4123 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 59.5 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3092–5154 kWEUOpen in the builder
EVAPCO AT 29-4H24 cooling tower (479 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4H24 — an AT cooling tower, 479 nominal tons (2107 kW): rated to cool 1443 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1581–2634 kWEUOpen in the builder
Baltimore Aircoil CXVB-75-0806-3 evaporative condenser (454 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-75-0806-3 — a CXVB evaporative condenser rejecting 454 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 10.5 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection341–568 kWEUOpen in the builder
EVAPCO AT 29-4H28 cooling tower (533 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4H28 — an AT cooling tower, 533 nominal tons (2344 kW): rated to cool 1605 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1758–2930 kWEUOpen in the builder
Baltimore Aircoil PCC-0659-1220N050 evaporative condenser (4.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0659-1220N050 — a PCC evaporative condenser rejecting 4003 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 61.6 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3002–5004 kWEUOpen in the builder
EVAPCO AT 29-4I18 cooling tower (424 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4I18 — an AT cooling tower, 424 nominal tons (1862 kW): rated to cool 1275 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1397–2328 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-3D4DS-L2 closed-circuit cooler (235 tons, 1.0 MW) — modelled Example modelled from published data
BAC's PFI-1024N-3D4DS-L2 — a PFi closed-circuit cooler, 235 nominal tons (1034 kW): rated to cool 708 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 60.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection776–1293 kWEUOpen in the builder
EVAPCO AT 29-4I21 cooling tower (480 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4I21 — an AT cooling tower, 480 nominal tons (2112 kW): rated to cool 1446 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1584–2640 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-07GN cooling tower (207 tons, 911 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-07GN — a Series 1500 cooling tower, 207 nominal tons (911 kW): rated to cool 624 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection683–1139 kWEUOpen in the builder
EVAPCO AT 29-4I24 cooling tower (529 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4I24 — an AT cooling tower, 529 nominal tons (2327 kW): rated to cool 1593 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1745–2908 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-8518-05M-2 cooling tower (641 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-8518-05M-2 — a Series 3000 cooling tower, 641 nominal tons (2817 kW): rated to cool 1929 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2113–3522 kWEUOpen in the builder
EVAPCO AT 29-4I28 cooling tower (590 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4I28 — an AT cooling tower, 590 nominal tons (2594 kW): rated to cool 1776 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1945–3242 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-072-K cooling tower (72 tons, 315 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-072-K — a Series V cooling tower, 72 nominal tons (315 kW): rated to cool 216 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection237–394 kWEUOpen in the builder
EVAPCO AT 29-4J18 cooling tower (489 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 29-4J18 — an AT cooling tower, 489 nominal tons (2151 kW): rated to cool 1473 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1613–2689 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-216-21N closed-circuit cooler (171 tons, 754 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-216-21N — a Series V closed circuit closed-circuit cooler, 171 nominal tons (754 kW): rated to cool 516 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 55.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection565–942 kWEUOpen in the builder
‹ Previous1…103104105106107…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers