Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,593–2,616 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 312-2K60 cooling tower (1363 tons, 6.0 MW) — modelled Example modelled from published data
EVAPCO's 312-2K60 — an AT cooling tower, 1363 nominal tons (5994 kW): rated to cool 4104 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 174.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4495–7492 kWEUOpen in the builder
Baltimore Aircoil VCA-661A evaporative condenser (2.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-661A — a VCA evaporative condenser rejecting 2848 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 43.3 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2136–3560 kWEUOpen in the builder
EVAPCO AT 312-2L36 cooling tower (1183 tons, 5.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-2L36 — an AT cooling tower, 1183 nominal tons (5201 kW): rated to cool 3561 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 136.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3901–6501 kWEUOpen in the builder
Baltimore Aircoil VRC-0713B-1024N-JB evaporative condenser (4.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0713B-1024N-JB — a Vertex VRC evaporative condenser rejecting 4323 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 68.5 m³/s of the maker's own printed air, with a 60.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3242–5404 kWEUOpen in the builder
EVAPCO AT 312-2L42 cooling tower (1285 tons, 5.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-2L42 — an AT cooling tower, 1285 nominal tons (5648 kW): rated to cool 3867 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 148.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4236–7060 kWEUOpen in the builder
Baltimore Aircoil CXVB-87-0806-3 evaporative condenser (527 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-87-0806-3 — a CXVB evaporative condenser rejecting 527 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 11.5 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection395–659 kWEUOpen in the builder
EVAPCO AT 312-2L54 cooling tower (1581 tons, 6.9 MW) — modelled Example modelled from published data
EVAPCO's 312-2L54 — an AT cooling tower, 1581 nominal tons (6949 kW): rated to cool 4758 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 183.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5212–8686 kWEUOpen in the builder
Baltimore Aircoil PCC-0692-2412N050 evaporative condenser (4.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0692-2412N050 — a PCC evaporative condenser rejecting 4204 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 72.7 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3153–5254 kWEUOpen in the builder
EVAPCO AT 312-2L60 cooling tower (1503 tons, 6.6 MW) — modelled Example modelled from published data
EVAPCO's 312-2L60 — an AT cooling tower, 1503 nominal tons (6607 kW): rated to cool 4524 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 187.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4955–8259 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-4D1ES-J2 closed-circuit cooler (235 tons, 1.0 MW) — modelled Example modelled from published data
BAC's PFI-1024N-4D1ES-J2 — a PFi closed-circuit cooler, 235 nominal tons (1034 kW): rated to cool 708 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 49.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection776–1293 kWEUOpen in the builder
EVAPCO AT 312-2M36 cooling tower (1253 tons, 5.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-2M36 — an AT cooling tower, 1253 nominal tons (5507 kW): rated to cool 3771 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 145.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4131–6884 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-09GC cooling tower (228 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-09GC — a Series 1500 cooling tower, 228 nominal tons (1003 kW): rated to cool 687 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection753–1254 kWEUOpen in the builder
EVAPCO AT 312-2M42 cooling tower (1361 tons, 6.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-2M42 — an AT cooling tower, 1361 nominal tons (5985 kW): rated to cool 4098 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 157.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4489–7481 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-8518-06N cooling tower (387 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-8518-06N — a Series 3000 cooling tower, 387 nominal tons (1700 kW): rated to cool 1164 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1275–2125 kWEUOpen in the builder
EVAPCO AT 312-2M54 cooling tower (1664 tons, 7.3 MW) — modelled Example modelled from published data
EVAPCO's 312-2M54 — an AT cooling tower, 1664 nominal tons (7317 kW): rated to cool 5010 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 194.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5488–9146 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-103-K cooling tower (103 tons, 451 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-103-K — a Series V cooling tower, 103 nominal tons (451 kW): rated to cool 309 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 11.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection338–564 kWEUOpen in the builder
EVAPCO AT 312-2M60 cooling tower (1617 tons, 7.1 MW) — modelled Example modelled from published data
EVAPCO's 312-2M60 — an AT cooling tower, 1617 nominal tons (7107 kW): rated to cool 4866 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 198.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5330–8883 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-216-31P closed-circuit cooler (230 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-216-31P — a Series V closed circuit closed-circuit cooler, 230 nominal tons (1012 kW): rated to cool 693 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 64.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection759–1265 kWEUOpen in the builder
EVAPCO AT 312-2N54 cooling tower (1834 tons, 8.1 MW) — modelled Example modelled from published data
EVAPCO's 312-2N54 — an AT cooling tower, 1834 nominal tons (8062 kW): rated to cool 5520 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 213.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6046–10077 kWEUOpen in the builder
Baltimore Aircoil VCA-662A evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-662A — a VCA evaporative condenser rejecting 2852 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.7 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2139–3565 kWEUOpen in the builder
EVAPCO AT 312-2N60 cooling tower (1859 tons, 8.2 MW) — modelled Example modelled from published data
EVAPCO's 312-2N60 — an AT cooling tower, 1859 nominal tons (8171 kW): rated to cool 5595 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 217.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6128–10214 kWEUOpen in the builder
Baltimore Aircoil VRC-0717B-1218N-NA evaporative condenser (4.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0717B-1218N-NA — a Vertex VRC evaporative condenser rejecting 4351 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.1 m³/s of the maker's own printed air, with a 55.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3263–5439 kWEUOpen in the builder
EVAPCO AT 312-2O60 cooling tower (2016 tons, 8.9 MW) — modelled Example modelled from published data
EVAPCO's 312-2O60 — an AT cooling tower, 2016 nominal tons (8864 kW): rated to cool 6069 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 233.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6648–11079 kWEUOpen in the builder
Baltimore Aircoil CXVB-875-1236-45 evaporative condenser (5.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-875-1236-45 — a CXVB evaporative condenser rejecting 5301 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 116.8 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3976–6626 kWEUOpen in the builder
‹ Previous1…107108109110111…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers