Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 2,617–2,640 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 312-3I36 cooling tower (957 tons, 4.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-3I36 — an AT cooling tower, 957 nominal tons (4206 kW): rated to cool 2880 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 100.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3155–5258 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0710-1224N050 evaporative condenser (4.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0710-1224N050 — a PCC evaporative condenser rejecting 4313 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 69.3 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3235–5391 kW | EU | Open in the builder |
| EVAPCO AT 312-3I42 cooling tower (1042 tons, 4.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-3I42 — an AT cooling tower, 1042 nominal tons (4579 kW): rated to cool 3135 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 109.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3434–5723 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1024N-4D1ES-M2 closed-circuit cooler (289 tons, 1.3 MW) — modelled Example modelled from published data BAC's PFI-1024N-4D1ES-M2 — a PFi closed-circuit cooler, 289 nominal tons (1271 kW): rated to cool 870 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 67.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 953–1588 kW | EU | Open in the builder |
| EVAPCO AT 312-3J36 cooling tower (1118 tons, 4.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-3J36 — an AT cooling tower, 1118 nominal tons (4916 kW): rated to cool 3366 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 114.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3687–6145 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1212-09GN cooling tower (242 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1212-09GN — a Series 1500 cooling tower, 242 nominal tons (1065 kW): rated to cool 729 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 799–1331 kW | EU | Open in the builder |
| EVAPCO AT 312-3J42 cooling tower (1225 tons, 5.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-3J42 — an AT cooling tower, 1225 nominal tons (5385 kW): rated to cool 3687 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 124.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4039–6731 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-8518-06N-2 cooling tower (773 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-8518-06N-2 — a Series 3000 cooling tower, 773 nominal tons (3400 kW): rated to cool 2328 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 92.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2550–4250 kW | EU | Open in the builder |
| EVAPCO AT 312-3J54 cooling tower (1468 tons, 6.5 MW) — modelled Example modelled from published data EVAPCO's 312-3J54 — an AT cooling tower, 1468 nominal tons (6454 kW): rated to cool 4419 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 153.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4840–8067 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VTL-116-L cooling tower (116 tons, 508 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VTL-116-L — a Series V cooling tower, 116 nominal tons (508 kW): rated to cool 348 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 13.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 381–635 kW | EU | Open in the builder |
| EVAPCO AT 312-3K36 cooling tower (1220 tons, 5.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-3K36 — an AT cooling tower, 1220 nominal tons (5363 kW): rated to cool 3672 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 125.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4022–6704 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-216-41O closed-circuit cooler (214 tons, 942 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-216-41O — a Series V closed circuit closed-circuit cooler, 214 nominal tons (942 kW): rated to cool 645 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 57.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 706–1177 kW | EU | Open in the builder |
| EVAPCO AT 312-3K42 cooling tower (1326 tons, 5.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-3K42 — an AT cooling tower, 1326 nominal tons (5827 kW): rated to cool 3990 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 136.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4370–7284 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-664A evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-664A — a VCA evaporative condenser rejecting 2861 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 46.0 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2146–3576 kW | EU | Open in the builder |
| EVAPCO AT 312-3K54 cooling tower (1643 tons, 7.2 MW) — modelled Example modelled from published data EVAPCO's 312-3K54 — an AT cooling tower, 1643 nominal tons (7221 kW): rated to cool 4944 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 168.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5415–9026 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0724B-1036N-HA evaporative condenser (4.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0724B-1036N-HA — a Vertex VRC evaporative condenser rejecting 4394 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 82.3 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3296–5493 kW | EU | Open in the builder |
| EVAPCO AT 312-3K60 cooling tower (1595 tons, 7.0 MW) — modelled Example modelled from published data EVAPCO's 312-3K60 — an AT cooling tower, 1595 nominal tons (7010 kW): rated to cool 4800 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 171.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5258–8763 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-888-1236-30 evaporative condenser (5.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-888-1236-30 — a CXVB evaporative condenser rejecting 5380 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 99.3 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4035–6725 kW | EU | Open in the builder |
| EVAPCO AT 312-3L36 cooling tower (1312 tons, 5.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-3L36 — an AT cooling tower, 1312 nominal tons (5766 kW): rated to cool 3948 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 134.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4324–7207 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0710-2412N050 evaporative condenser (4.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0710-2412N050 — a PCC evaporative condenser rejecting 4313 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 69.3 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3235–5391 kW | EU | Open in the builder |
| EVAPCO AT 312-3L42 cooling tower (1423 tons, 6.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-3L42 — an AT cooling tower, 1423 nominal tons (6257 kW): rated to cool 4284 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 146.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4692–7821 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1024N-4D2ES-N2 closed-circuit cooler (310 tons, 1.4 MW) — modelled Example modelled from published data BAC's PFI-1024N-4D2ES-N2 — a PFi closed-circuit cooler, 310 nominal tons (1363 kW): rated to cool 933 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 69.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1022–1703 kW | EU | Open in the builder |
| EVAPCO AT 312-3L54 cooling tower (1746 tons, 7.7 MW) — modelled Example modelled from published data EVAPCO's 312-3L54 — an AT cooling tower, 1746 nominal tons (7676 kW): rated to cool 5256 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 180.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5757–9595 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1212-09HC cooling tower (262 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1212-09HC — a Series 1500 cooling tower, 262 nominal tons (1152 kW): rated to cool 789 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 864–1440 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers