Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,641–2,664 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 312-3L60 cooling tower (1739 tons, 7.6 MW) — modelled Example modelled from published data
EVAPCO's 312-3L60 — an AT cooling tower, 1739 nominal tons (7646 kW): rated to cool 5235 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 184.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5734–9557 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-8518-06O cooling tower (405 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-8518-06O — a Series 3000 cooling tower, 405 nominal tons (1779 kW): rated to cool 1218 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 49.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1334–2224 kWEUOpen in the builder
EVAPCO AT 312-3M36 cooling tower (1393 tons, 6.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-3M36 — an AT cooling tower, 1393 nominal tons (6125 kW): rated to cool 4194 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 142.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4594–7656 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-126-M cooling tower (126 tons, 552 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-126-M — a Series V cooling tower, 126 nominal tons (552 kW): rated to cool 378 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection414–690 kWEUOpen in the builder
EVAPCO AT 312-3M42 cooling tower (1514 tons, 6.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-3M42 — an AT cooling tower, 1514 nominal tons (6655 kW): rated to cool 4557 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 154.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4991–8319 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-216-41P closed-circuit cooler (244 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-216-41P — a Series V closed circuit closed-circuit cooler, 244 nominal tons (1073 kW): rated to cool 735 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 63.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection805–1342 kWEUOpen in the builder
EVAPCO AT 312-3M54 cooling tower (1845 tons, 8.1 MW) — modelled Example modelled from published data
EVAPCO's 312-3M54 — an AT cooling tower, 1845 nominal tons (8110 kW): rated to cool 5553 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 191.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6082–10137 kWEUOpen in the builder
Baltimore Aircoil VCA-680A evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-680A — a VCA evaporative condenser rejecting 2930 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 52.3 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2197–3662 kWEUOpen in the builder
EVAPCO AT 312-3M60 cooling tower (1853 tons, 8.1 MW) — modelled Example modelled from published data
EVAPCO's 312-3M60 — an AT cooling tower, 1853 nominal tons (8145 kW): rated to cool 5577 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 194.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6109–10181 kWEUOpen in the builder
Baltimore Aircoil VRC-0727B-1024N-LA evaporative condenser (4.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0727B-1024N-LA — a Vertex VRC evaporative condenser rejecting 4411 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 67.9 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3308–5514 kWEUOpen in the builder
EVAPCO AT 312-3N42 cooling tower (1656 tons, 7.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-3N42 — an AT cooling tower, 1656 nominal tons (7282 kW): rated to cool 4986 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 169.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5461–9102 kWEUOpen in the builder
Baltimore Aircoil CXVB-914-1236-30 evaporative condenser (5.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-914-1236-30 — a CXVB evaporative condenser rejecting 5537 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 99.3 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4153–6922 kWEUOpen in the builder
EVAPCO AT 312-3N54 cooling tower (2029 tons, 8.9 MW) — modelled Example modelled from published data
EVAPCO's 312-3N54 — an AT cooling tower, 2029 nominal tons (8920 kW): rated to cool 6108 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 209.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6690–11151 kWEUOpen in the builder
Baltimore Aircoil PCC-0730-1224N060 evaporative condenser (4.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0730-1224N060 — a PCC evaporative condenser rejecting 4434 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 76.9 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3326–5543 kWEUOpen in the builder
EVAPCO AT 312-3N60 cooling tower (2076 tons, 9.1 MW) — modelled Example modelled from published data
EVAPCO's 312-3N60 — an AT cooling tower, 2076 nominal tons (9126 kW): rated to cool 6249 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 213.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6845–11408 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-4D3ES-L2 closed-circuit cooler (283 tons, 1.2 MW) — modelled Example modelled from published data
BAC's PFI-1024N-4D3ES-L2 — a PFi closed-circuit cooler, 283 nominal tons (1244 kW): rated to cool 852 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 57.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection933–1555 kWEUOpen in the builder
EVAPCO AT 312-3O54 cooling tower (2175 tons, 9.6 MW) — modelled Example modelled from published data
EVAPCO's 312-3O54 — an AT cooling tower, 2175 nominal tons (9560 kW): rated to cool 6546 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 224.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7170–11950 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-09HN cooling tower (286 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-09HN — a Series 1500 cooling tower, 286 nominal tons (1257 kW): rated to cool 861 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 31.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection943–1572 kWEUOpen in the builder
EVAPCO AT 312-3O60 cooling tower (2252 tons, 9.9 MW) — modelled Example modelled from published data
EVAPCO's 312-3O60 — an AT cooling tower, 2252 nominal tons (9902 kW): rated to cool 6780 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 228.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7426–12377 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-8518-06O-2 cooling tower (810 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-8518-06O-2 — a Series 3000 cooling tower, 810 nominal tons (3562 kW): rated to cool 2439 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 98.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2672–4453 kWEUOpen in the builder
EVAPCO AT 312-4I36 cooling tower (1018 tons, 4.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-4I36 — an AT cooling tower, 1018 nominal tons (4473 kW): rated to cool 3063 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 99.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3355–5592 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-137-M cooling tower (137 tons, 600 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-137-M — a Series V cooling tower, 137 nominal tons (600 kW): rated to cool 411 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection450–750 kWEUOpen in the builder
EVAPCO AT 312-4I42 cooling tower (1119 tons, 4.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-4I42 — an AT cooling tower, 1119 nominal tons (4920 kW): rated to cool 3369 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 107.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3690–6150 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-216-41Q closed-circuit cooler (270 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-216-41Q — a Series V closed circuit closed-circuit cooler, 270 nominal tons (1187 kW): rated to cool 813 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 68.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection891–1484 kWEUOpen in the builder
‹ Previous1…109110111112113…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers