Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 2,689–2,712 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 312-4M42 cooling tower (1584 tons, 7.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-4M42 — an AT cooling tower, 1584 nominal tons (6962 kW): rated to cool 4767 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 152.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5222–8703 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0750-1224N060 evaporative condenser (4.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0750-1224N060 — a PCC evaporative condenser rejecting 4556 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 73.3 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3417–5695 kW | EU | Open in the builder |
| EVAPCO AT 312-4M54 cooling tower (1929 tons, 8.5 MW) — modelled Example modelled from published data EVAPCO's 312-4M54 — an AT cooling tower, 1929 nominal tons (8478 kW): rated to cool 5805 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 188.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 6358–10597 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1024N-4D4ES-O2 closed-circuit cooler (335 tons, 1.5 MW) — modelled Example modelled from published data BAC's PFI-1024N-4D4ES-O2 — a PFi closed-circuit cooler, 335 nominal tons (1472 kW): rated to cool 1008 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 68.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1104–1840 kW | EU | Open in the builder |
| EVAPCO AT 312-4M60 cooling tower (1948 tons, 8.6 MW) — modelled Example modelled from published data EVAPCO's 312-4M60 — an AT cooling tower, 1948 nominal tons (8566 kW): rated to cool 5865 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 191.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 6424–10707 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1212-10FN cooling tower (223 tons, 981 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1212-10FN — a Series 1500 cooling tower, 223 nominal tons (981 kW): rated to cool 672 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 736–1227 kW | EU | Open in the builder |
| EVAPCO AT 312-4N36 cooling tower (1555 tons, 6.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-4N36 — an AT cooling tower, 1555 nominal tons (6835 kW): rated to cool 4680 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 153.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5126–8544 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-8518-07M-2 cooling tower (797 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-8518-07M-2 — a Series 3000 cooling tower, 797 nominal tons (3505 kW): rated to cool 2400 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 93.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2629–4381 kW | EU | Open in the builder |
| EVAPCO AT 312-4N42 cooling tower (1732 tons, 7.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 312-4N42 — an AT cooling tower, 1732 nominal tons (7615 kW): rated to cool 5214 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 166.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5711–9519 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VTL-171-L cooling tower (170 tons, 749 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VTL-171-L — a Series V cooling tower, 170 nominal tons (749 kW): rated to cool 513 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 18.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 562–937 kW | EU | Open in the builder |
| EVAPCO AT 312-4N54 cooling tower (2117 tons, 9.3 MW) — modelled Example modelled from published data EVAPCO's 312-4N54 — an AT cooling tower, 2117 nominal tons (9306 kW): rated to cool 6372 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 205.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 6980–11633 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-288-21Q closed-circuit cooler (258 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-288-21Q — a Series V closed circuit closed-circuit cooler, 258 nominal tons (1135 kW): rated to cool 777 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 82.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 851–1418 kW | EU | Open in the builder |
| EVAPCO AT 312-4N60 cooling tower (2167 tons, 9.5 MW) — modelled Example modelled from published data EVAPCO's 312-4N60 — an AT cooling tower, 2167 nominal tons (9525 kW): rated to cool 6522 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 209.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 7144–11906 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-707A evaporative condenser (3.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-707A — a VCA evaporative condenser rejecting 3046 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 44.5 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2284–3807 kW | EU | Open in the builder |
| EVAPCO AT 312-4O54 cooling tower (2273 tons, 10.0 MW) — modelled Example modelled from published data EVAPCO's 312-4O54 — an AT cooling tower, 2273 nominal tons (9994 kW): rated to cool 6843 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 220.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 7495–12492 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0763B-1224N-KA evaporative condenser (4.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0763B-1224N-KA — a Vertex VRC evaporative condenser rejecting 4627 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 63.5 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3470–5784 kW | EU | Open in the builder |
| EVAPCO AT 312-4O60 cooling tower (2344 tons, 10.3 MW) — modelled Example modelled from published data EVAPCO's 312-4O60 — an AT cooling tower, 2344 nominal tons (10305 kW): rated to cool 7056 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 224.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 7729–12881 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-94-0806-3 evaporative condenser (569 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-94-0806-3 — a CXVB evaporative condenser rejecting 569 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 9.6 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 427–712 kW | EU | Open in the builder |
| EVAPCO AT 312-4P54 cooling tower (2359 tons, 10.4 MW) — modelled Example modelled from published data EVAPCO's 312-4P54 — an AT cooling tower, 2359 nominal tons (10371 kW): rated to cool 7101 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 233.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 7778–12963 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0750-2412N060 evaporative condenser (4.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0750-2412N060 — a PCC evaporative condenser rejecting 4556 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 73.3 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3417–5695 kW | EU | Open in the builder |
| EVAPCO AT 312-4P60 cooling tower (2432 tons, 10.7 MW) — modelled Example modelled from published data EVAPCO's 312-4P60 — an AT cooling tower, 2432 nominal tons (10691 kW): rated to cool 7320 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 238.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 8018–13363 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1024N-5D2DS-M2 closed-circuit cooler (298 tons, 1.3 MW) — modelled Example modelled from published data BAC's PFI-1024N-5D2DS-M2 — a PFi closed-circuit cooler, 298 nominal tons (1310 kW): rated to cool 897 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 64.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 983–1638 kW | EU | Open in the builder |
| EVAPCO AT 314-2K72 cooling tower (1783 tons, 7.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 314-2K72 — an AT cooling tower, 1783 nominal tons (7838 kW): rated to cool 5367 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 220.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5879–9798 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1212-10GC cooling tower (240 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1212-10GC — a Series 1500 cooling tower, 240 nominal tons (1056 kW): rated to cool 723 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 792–1320 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers