Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,737–2,760 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 314-4M72 cooling tower (2543 tons, 11.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-4M72 — an AT cooling tower, 2543 nominal tons (11177 kW): rated to cool 7653 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 242.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection8383–13971 kWEUOpen in the builder
Baltimore Aircoil VCA-750A evaporative condenser (3.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-750A — a VCA evaporative condenser rejecting 3231 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 59.8 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2423–4039 kWEUOpen in the builder
EVAPCO AT 314-4N72 cooling tower (2761 tons, 12.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-4N72 — an AT cooling tower, 2761 nominal tons (12136 kW): rated to cool 8310 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 265.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection9102–15171 kWEUOpen in the builder
Baltimore Aircoil VRC-0767B-1224N-JB evaporative condenser (4.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0767B-1224N-JB — a Vertex VRC evaporative condenser rejecting 4653 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 89.9 m³/s of the maker's own printed air, with a 60.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3490–5816 kWEUOpen in the builder
EVAPCO AT 314-4O72 cooling tower (2909 tons, 12.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-4O72 — an AT cooling tower, 2909 nominal tons (12789 kW): rated to cool 8757 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 285.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection9592–15987 kWEUOpen in the builder
Baltimore Aircoil CXVB-964-1236-45 evaporative condenser (5.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-964-1236-45 — a CXVB evaporative condenser rejecting 5840 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 113.6 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4380–7300 kWEUOpen in the builder
EVAPCO AT 314-4P72 cooling tower (3081 tons, 13.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-4P72 — an AT cooling tower, 3081 nominal tons (13543 kW): rated to cool 9273 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 302.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection10157–16929 kWEUOpen in the builder
Baltimore Aircoil PCC-0762-2418N030 evaporative condenser (4.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0762-2418N030 — a PCC evaporative condenser rejecting 4629 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 98.4 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3472–5786 kWEUOpen in the builder
EVAPCO AT 314-4Q72 cooling tower (3311 tons, 14.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-4Q72 — an AT cooling tower, 3311 nominal tons (14555 kW): rated to cool 9966 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 323.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection10916–18194 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-6D1ES-M2 closed-circuit cooler (337 tons, 1.5 MW) — modelled Example modelled from published data
BAC's PFI-1024N-6D1ES-M2 — a PFi closed-circuit cooler, 337 nominal tons (1481 kW): rated to cool 1014 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 62.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1111–1851 kWEUOpen in the builder
EVAPCO AT 314-5K78 cooling tower (2926 tons, 12.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-5K78 — an AT cooling tower, 2926 nominal tons (12864 kW): rated to cool 8808 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 276.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection9648–16080 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-10HC cooling tower (275 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-10HC — a Series 1500 cooling tower, 275 nominal tons (1209 kW): rated to cool 828 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection907–1512 kWEUOpen in the builder
EVAPCO AT 314-5L78 cooling tower (3147 tons, 13.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-5L78 — an AT cooling tower, 3147 nominal tons (13832 kW): rated to cool 9471 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 296.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection10374–17290 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-8518-07O cooling tower (450 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-8518-07O — a Series 3000 cooling tower, 450 nominal tons (1976 kW): rated to cool 1353 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1482–2470 kWEUOpen in the builder
EVAPCO AT 314-5M78 cooling tower (3333 tons, 14.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-5M78 — an AT cooling tower, 3333 nominal tons (14651 kW): rated to cool 10032 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 314.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection10989–18314 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-209-O cooling tower (208 tons, 916 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-209-O — a Series V cooling tower, 208 nominal tons (916 kW): rated to cool 627 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection687–1145 kWEUOpen in the builder
EVAPCO AT 314-5N78 cooling tower (3643 tons, 16.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-5N78 — an AT cooling tower, 3643 nominal tons (16014 kW): rated to cool 10965 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 343.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection12010–20017 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-288-31Q closed-circuit cooler (280 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-288-31Q — a Series V closed circuit closed-circuit cooler, 280 nominal tons (1231 kW): rated to cool 843 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 81.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection923–1539 kWEUOpen in the builder
EVAPCO AT 314-5O78 cooling tower (3895 tons, 17.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 314-5O78 — an AT cooling tower, 3895 nominal tons (17122 kW): rated to cool 11724 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 368.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection12842–21403 kWEUOpen in the builder
Baltimore Aircoil VCA-751A evaporative condenser (3.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-751A — a VCA evaporative condenser rejecting 3231 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 50.4 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2423–4039 kWEUOpen in the builder
EVAPCO AT 342-5K26 cooling tower (2872 tons, 12.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 342-5K26 — an AT cooling tower, 2872 nominal tons (12627 kW): rated to cool 8646 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 277.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection9470–15784 kWEUOpen in the builder
Baltimore Aircoil VRC-0768B-1224N-LA evaporative condenser (4.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0768B-1224N-LA — a Vertex VRC evaporative condenser rejecting 4662 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 76.9 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3496–5827 kWEUOpen in the builder
EVAPCO AT 342-5L26 cooling tower (3090 tons, 13.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 342-5L26 — an AT cooling tower, 3090 nominal tons (13582 kW): rated to cool 9300 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 298.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection10187–16978 kWEUOpen in the builder
Baltimore Aircoil CXVB-966-1236-30 evaporative condenser (5.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-966-1236-30 — a CXVB evaporative condenser rejecting 5852 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 97.2 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4389–7315 kWEUOpen in the builder
‹ Previous1…113114115116117…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers