Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,665–2,688 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 312-4J36 cooling tower (1170 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-4J36 — an AT cooling tower, 1170 nominal tons (5144 kW): rated to cool 3522 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 112.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3858–6430 kWEUOpen in the builder
Baltimore Aircoil VCA-684A evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-684A — a VCA evaporative condenser rejecting 2947 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 56.4 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2210–3684 kWEUOpen in the builder
EVAPCO AT 312-4J42 cooling tower (1289 tons, 5.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-4J42 — an AT cooling tower, 1289 nominal tons (5665 kW): rated to cool 3879 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 122.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4249–7081 kWEUOpen in the builder
Baltimore Aircoil VRC-0747B-1236N-HA evaporative condenser (4.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0747B-1236N-HA — a Vertex VRC evaporative condenser rejecting 4532 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 84.7 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3399–5665 kWEUOpen in the builder
EVAPCO AT 312-4J54 cooling tower (1555 tons, 6.8 MW) — modelled Example modelled from published data
EVAPCO's 312-4J54 — an AT cooling tower, 1555 nominal tons (6835 kW): rated to cool 4680 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 151.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5126–8544 kWEUOpen in the builder
Baltimore Aircoil CXVB-918-1236-30 evaporative condenser (5.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-918-1236-30 — a CXVB evaporative condenser rejecting 5562 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 98.0 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4171–6952 kWEUOpen in the builder
EVAPCO AT 312-4K36 cooling tower (1273 tons, 5.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-4K36 — an AT cooling tower, 1273 nominal tons (5595 kW): rated to cool 3831 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 123.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4196–6994 kWEUOpen in the builder
Baltimore Aircoil PCC-0730-2412N060 evaporative condenser (4.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0730-2412N060 — a PCC evaporative condenser rejecting 4434 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 76.9 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3326–5543 kWEUOpen in the builder
EVAPCO AT 312-4K42 cooling tower (1390 tons, 6.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-4K42 — an AT cooling tower, 1390 nominal tons (6112 kW): rated to cool 4185 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 134.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4584–7640 kWEUOpen in the builder
Baltimore Aircoil PFI-1024N-4D3ES-N2 closed-circuit cooler (319 tons, 1.4 MW) — modelled Example modelled from published data
BAC's PFI-1024N-4D3ES-N2 — a PFi closed-circuit cooler, 319 nominal tons (1402 kW): rated to cool 960 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 67.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1052–1753 kWEUOpen in the builder
EVAPCO AT 312-4K54 cooling tower (1719 tons, 7.6 MW) — modelled Example modelled from published data
EVAPCO's 312-4K54 — an AT cooling tower, 1719 nominal tons (7558 kW): rated to cool 5175 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 165.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5668–9447 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-10EN cooling tower (203 tons, 894 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-10EN — a Series 1500 cooling tower, 203 nominal tons (894 kW): rated to cool 612 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 22.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection670–1117 kWEUOpen in the builder
EVAPCO AT 312-4K60 cooling tower (1701 tons, 7.5 MW) — modelled Example modelled from published data
EVAPCO's 312-4K60 — an AT cooling tower, 1701 nominal tons (7479 kW): rated to cool 5121 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 168.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5609–9349 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-8518-07M cooling tower (399 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-8518-07M — a Series 3000 cooling tower, 399 nominal tons (1753 kW): rated to cool 1200 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1314–2191 kWEUOpen in the builder
EVAPCO AT 312-4L36 cooling tower (1370 tons, 6.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-4L36 — an AT cooling tower, 1370 nominal tons (6024 kW): rated to cool 4125 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 132.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4518–7530 kWEUOpen in the builder
Baltimore Aircoil Series V VTL-152-M cooling tower (151 tons, 666 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VTL-152-M — a Series V cooling tower, 151 nominal tons (666 kW): rated to cool 456 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection499–832 kWEUOpen in the builder
EVAPCO AT 312-4L42 cooling tower (1490 tons, 6.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-4L42 — an AT cooling tower, 1490 nominal tons (6550 kW): rated to cool 4485 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 143.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4913–8188 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-288-21P closed-circuit cooler (231 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-288-21P — a Series V closed circuit closed-circuit cooler, 231 nominal tons (1016 kW): rated to cool 696 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 76.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection762–1271 kWEUOpen in the builder
EVAPCO AT 312-4L54 cooling tower (1822 tons, 8.0 MW) — modelled Example modelled from published data
EVAPCO's 312-4L54 — an AT cooling tower, 1822 nominal tons (8009 kW): rated to cool 5484 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 177.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6007–10011 kWEUOpen in the builder
Baltimore Aircoil VCA-688A evaporative condenser (3.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-688A — a VCA evaporative condenser rejecting 2964 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 51.7 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2223–3705 kWEUOpen in the builder
EVAPCO AT 312-4L60 cooling tower (1838 tons, 8.1 MW) — modelled Example modelled from published data
EVAPCO's 312-4L60 — an AT cooling tower, 1838 nominal tons (8079 kW): rated to cool 5532 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 181.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6059–10099 kWEUOpen in the builder
Baltimore Aircoil VRC-0755B-1224N-HB evaporative condenser (4.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0755B-1224N-HB — a Vertex VRC evaporative condenser rejecting 4583 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 72.9 m³/s of the maker's own printed air, with a 38.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3437–5728 kWEUOpen in the builder
EVAPCO AT 312-4M36 cooling tower (1453 tons, 6.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 312-4M36 — an AT cooling tower, 1453 nominal tons (6388 kW): rated to cool 4374 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 139.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4791–7985 kWEUOpen in the builder
Baltimore Aircoil CXVB-933-1236-30 evaporative condenser (5.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-933-1236-30 — a CXVB evaporative condenser rejecting 5652 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 97.2 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4239–7066 kWEUOpen in the builder
‹ Previous1…110111112113114…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers