Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 241–264 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| American Cooling Tower ACX-1066-1 cooling tower (735 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓ American Cooling Tower's ACX-1066-1 — an ACX cooling tower, 735 nominal tons (3229 kW): rated to cool 2211 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2422–4036 kW | NA | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-009-22F closed-circuit cooler (6 tons, 26 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-009-22F — a Series V closed circuit closed-circuit cooler, 6 nominal tons (26 kW): rated to cool 18 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 2.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 20–33 kW | EU | Open in the builder |
| EVAPCO AT 110-4L18 cooling tower (491 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 110-4L18 — an AT cooling tower, 491 nominal tons (2160 kW): rated to cool 1479 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1620–2700 kW | EU | Open in the builder |
| American Cooling Tower ACX-1067-1 cooling tower (780 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓ American Cooling Tower's ACX-1067-1 — an ACX cooling tower, 780 nominal tons (3431 kW): rated to cool 2349 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 96.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2573–4288 kW | NA | Open in the builder |
| Baltimore Aircoil VCL-035 evaporative condenser (151 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCL-035 — a Series V EC evaporative condenser rejecting 151 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 3.8 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 113–189 kW | EU | Open in the builder |
| EVAPCO ATWB 10-6K36 closed-circuit cooler (710 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 10-6K36 — an ATWB closed-circuit cooler, 710 nominal tons (3121 kW): rated to cool 1781 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 79.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2341–3901 kW | EU | Open in the builder |
| American Cooling Tower ACX-1068-1 cooling tower (838 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓ American Cooling Tower's ACX-1068-1 — an ACX cooling tower, 838 nominal tons (3685 kW): rated to cool 2523 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 99.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2764–4606 kW | NA | Open in the builder |
| Baltimore Aircoil VCA-1026A evaporative condenser (4.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-1026A — a VCA evaporative condenser rejecting 4420 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 77.2 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3315–5525 kW | EU | Open in the builder |
| EVAPCO AT 110-4M12 cooling tower (392 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 110-4M12 — an AT cooling tower, 392 nominal tons (1722 kW): rated to cool 1179 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1291–2152 kW | EU | Open in the builder |
| American Cooling Tower ACX-2070-1 cooling tower (539 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓ American Cooling Tower's ACX-2070-1 — an ACX cooling tower, 539 nominal tons (2370 kW): rated to cool 1623 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1778–2963 kW | NA | Open in the builder |
| Baltimore Aircoil VRC-0242B-1012N-HA evaporative condenser (1.5 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0242B-1012N-HA — a Vertex VRC evaporative condenser rejecting 1465 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 26.1 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1099–1831 kW | EU | Open in the builder |
| EVAPCO ATWB 10-6L36 closed-circuit cooler (762 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 10-6L36 — an ATWB closed-circuit cooler, 762 nominal tons (3352 kW): rated to cool 1912 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 85.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2514–4189 kW | EU | Open in the builder |
| American Cooling Tower ACX-2071-1 cooling tower (594 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓ American Cooling Tower's ACX-2071-1 — an ACX cooling tower, 594 nominal tons (2611 kW): rated to cool 1788 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1958–3264 kW | NA | Open in the builder |
| Baltimore Aircoil CXVB-106-0806-3 evaporative condenser (642 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-106-0806-3 — a CXVB evaporative condenser rejecting 642 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 11.0 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 482–803 kW | EU | Open in the builder |
| EVAPCO AT 110-4M18 cooling tower (520 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 110-4M18 — an AT cooling tower, 520 nominal tons (2287 kW): rated to cool 1566 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 55.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1715–2859 kW | EU | Open in the builder |
| American Cooling Tower ACX-2072-1 cooling tower (639 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓ American Cooling Tower's ACX-2072-1 — an ACX cooling tower, 639 nominal tons (2808 kW): rated to cool 1923 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2106–3511 kW | NA | Open in the builder |
| Baltimore Aircoil CXVT-1352-2424-50 evaporative condenser (8.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVT-1352-2424-50 — a CXVT evaporative condenser rejecting 8213 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 146.1 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 6160–10266 kW | EU | Open in the builder |
| EVAPCO ATWB 10-6M36 closed-circuit cooler (808 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 10-6M36 — an ATWB closed-circuit cooler, 808 nominal tons (3551 kW): rated to cool 2026 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 90.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2664–4439 kW | EU | Open in the builder |
| American Cooling Tower ACX-2073-1 cooling tower (679 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓ American Cooling Tower's ACX-2073-1 — an ACX cooling tower, 679 nominal tons (2984 kW): rated to cool 2043 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 81.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2238–3730 kW | NA | Open in the builder |
| Baltimore Aircoil FXT-0706B-F cooling tower (64 tons, 280 kW) — modelled Example modelled from published data BAC's FXT-0706B-F — an FXT cooling tower, 64 nominal tons (280 kW): rated to cool 192 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 210–351 kW | EU | Open in the builder |
| EVAPCO AT 110-4N12 cooling tower (409 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 110-4N12 — an AT cooling tower, 409 nominal tons (1796 kW): rated to cool 1230 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 43.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1347–2245 kW | EU | Open in the builder |
| American Cooling Tower ACX-2074-1 cooling tower (748 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓ American Cooling Tower's ACX-2074-1 — an ACX cooling tower, 748 nominal tons (3286 kW): rated to cool 2250 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 89.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2465–4108 kW | NA | Open in the builder |
| Baltimore Aircoil FXV-0806B-12D-L closed-circuit cooler (47 tons, 206 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0806B-12D-L — an FXV closed-circuit cooler, 47 nominal tons (206 kW): rated to cool 141 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 19.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 154–257 kW | EU | Open in the builder |
| EVAPCO ATWB 10-6N36 closed-circuit cooler (885 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 10-6N36 — an ATWB closed-circuit cooler, 885 nominal tons (3888 kW): rated to cool 2219 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 97.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2916–4860 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers