Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 289–312 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
American Cooling Tower ACX-2085-1 cooling tower (902 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2085-1 — an ACX cooling tower, 902 nominal tons (3965 kW): rated to cool 2715 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 107.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2974–4956 kWNAOpen in the builder
Baltimore Aircoil VCL-038 evaporative condenser (164 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-038 — a Series V EC evaporative condenser rejecting 164 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 6.0 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection123–205 kWEUOpen in the builder
EVAPCO AT 112-2J14 cooling tower (358 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-2J14 — an AT cooling tower, 358 nominal tons (1573 kW): rated to cool 1077 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1180–1966 kWEUOpen in the builder
American Cooling Tower ACX-2086-1 cooling tower (958 tons, 4.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2086-1 — an ACX cooling tower, 958 nominal tons (4211 kW): rated to cool 2883 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 114.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3158–5263 kWNAOpen in the builder
Baltimore Aircoil VCA-1052A evaporative condenser (4.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1052A — a VCA evaporative condenser rejecting 4532 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 84.7 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3399–5665 kWEUOpen in the builder
EVAPCO ATWB 10-7M36 closed-circuit cooler (876 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 10-7M36 — an ATWB closed-circuit cooler, 876 nominal tons (3853 kW): rated to cool 2199 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 87.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2890–4816 kWEUOpen in the builder
American Cooling Tower ACX-2087-1 cooling tower (1032 tons, 4.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2087-1 — an ACX cooling tower, 1032 nominal tons (4535 kW): rated to cool 3105 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 123.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3401–5668 kWNAOpen in the builder
Baltimore Aircoil VRC-0243B-1212N-HA evaporative condenser (1.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0243B-1212N-HA — a Vertex VRC evaporative condenser rejecting 1473 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 28.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1105–1842 kWEUOpen in the builder
EVAPCO AT 112-2J18 cooling tower (438 tons, 1.9 MW) — modelled Example modelled from published data
EVAPCO's 112-2J18 — an AT cooling tower, 438 nominal tons (1923 kW): rated to cool 1317 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1443–2404 kWEUOpen in the builder
American Cooling Tower ACX-2088-1 cooling tower (1134 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2088-1 — an ACX cooling tower, 1134 nominal tons (4986 kW): rated to cool 3414 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 135.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3740–6233 kWNAOpen in the builder
Baltimore Aircoil CXVB-1089-1236-60 evaporative condenser (6.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-1089-1236-60 — a CXVB evaporative condenser rejecting 6598 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 123.8 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4948–8247 kWEUOpen in the builder
EVAPCO ATWB 10-7N36 closed-circuit cooler (959 tons, 4.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 10-7N36 — an ATWB closed-circuit cooler, 959 nominal tons (4214 kW): rated to cool 2405 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 94.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3161–5268 kWEUOpen in the builder
American Cooling Tower ACX-2090-1 cooling tower (583 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2090-1 — an ACX cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1922–3204 kWNAOpen in the builder
Baltimore Aircoil CXVT-1400-2424-80 evaporative condenser (8.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1400-2424-80 — a CXVT evaporative condenser rejecting 8504 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 172.0 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection6378–10630 kWEUOpen in the builder
EVAPCO AT 112-2K12 cooling tower (363 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-2K12 — an AT cooling tower, 363 nominal tons (1595 kW): rated to cool 1092 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1196–1994 kWEUOpen in the builder
American Cooling Tower ACX-2091-1 cooling tower (641 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2091-1 — an ACX cooling tower, 641 nominal tons (2817 kW): rated to cool 1929 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2113–3522 kWNAOpen in the builder
Baltimore Aircoil FXT-0706B-G cooling tower (74 tons, 324 kW) — modelled Example modelled from published data
BAC's FXT-0706B-G — an FXT cooling tower, 74 nominal tons (324 kW): rated to cool 222 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 10.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection243–405 kWEUOpen in the builder
EVAPCO ATWB 12-3K14 closed-circuit cooler (259 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-3K14 — an ATWB closed-circuit cooler, 259 nominal tons (1137 kW): rated to cool 649 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 41.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection852–1421 kWEUOpen in the builder
American Cooling Tower ACX-2092-1 cooling tower (691 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2092-1 — an ACX cooling tower, 691 nominal tons (3036 kW): rated to cool 2079 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 81.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2277–3795 kWNAOpen in the builder
Baltimore Aircoil FXV-0806B-16D-L closed-circuit cooler (57 tons, 250 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0806B-16D-L — an FXV closed-circuit cooler, 57 nominal tons (250 kW): rated to cool 171 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 19.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection187–312 kWEUOpen in the builder
EVAPCO AT 112-2K14 cooling tower (393 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-2K14 — an AT cooling tower, 393 nominal tons (1726 kW): rated to cool 1182 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1295–2158 kWEUOpen in the builder
American Cooling Tower ACX-2093-1 cooling tower (734 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2093-1 — an ACX cooling tower, 734 nominal tons (3225 kW): rated to cool 2208 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 86.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2419–4031 kWNAOpen in the builder
Baltimore Aircoil Nexus NXF-0403N-CS2TT-H6 closed-circuit cooler (120 tons, 526 kW) — modelled Example modelled from published data
BAC's NXF-0403N-CS2TT-H6 — a Nexus closed-circuit cooler, 120 nominal tons (526 kW): rated to cool 360 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 23.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection394–657 kWEUOpen in the builder
EVAPCO ATWB 12-3K28 closed-circuit cooler (517 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-3K28 — an ATWB closed-circuit cooler, 517 nominal tons (2273 kW): rated to cool 1297 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 83.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1705–2841 kWEUOpen in the builder
‹ Previous1…1112131415…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers