Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 289–312 of 3346
BAC's S3E-1222-12Q-2 — a Series 3000 cooling tower, 1731 nominal tons (7610 kW): rated to cool 5211 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 192.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-12R — a Series 3000 cooling tower, 914 nominal tons (4018 kW): rated to cool 2751 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 101.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-12R-2 — a Series 3000 cooling tower, 1829 nominal tons (8040 kW): rated to cool 5505 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 203.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-12S — a Series 3000 cooling tower, 978 nominal tons (4298 kW): rated to cool 2943 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 108.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-12S-2 — a Series 3000 cooling tower, 1954 nominal tons (8592 kW): rated to cool 5883 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 216.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-13P — a Series 3000 cooling tower, 836 nominal tons (3676 kW): rated to cool 2517 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 93.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-13P-2 — a Series 3000 cooling tower, 1672 nominal tons (7352 kW): rated to cool 5034 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 185.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-13Q — a Series 3000 cooling tower, 894 nominal tons (3930 kW): rated to cool 2691 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 99.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-13Q-2 — a Series 3000 cooling tower, 1788 nominal tons (7860 kW): rated to cool 5382 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 198.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-13R — a Series 3000 cooling tower, 944 nominal tons (4149 kW): rated to cool 2841 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 104.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-13R-2 — a Series 3000 cooling tower, 1889 nominal tons (8303 kW): rated to cool 5685 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 208.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-13S — a Series 3000 cooling tower, 1010 nominal tons (4438 kW): rated to cool 3039 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 111.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-13S-2 — a Series 3000 cooling tower, 2018 nominal tons (8872 kW): rated to cool 6075 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 222.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14P — a Series 3000 cooling tower, 869 nominal tons (3821 kW): rated to cool 2616 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 96.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14P-2 — a Series 3000 cooling tower, 1738 nominal tons (7641 kW): rated to cool 5232 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 192.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14Q — a Series 3000 cooling tower, 930 nominal tons (4088 kW): rated to cool 2799 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 102.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14Q-2 — a Series 3000 cooling tower, 1860 nominal tons (8176 kW): rated to cool 5598 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 205.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14R — a Series 3000 cooling tower, 982 nominal tons (4316 kW): rated to cool 2955 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 108.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14R-2 — a Series 3000 cooling tower, 1963 nominal tons (8631 kW): rated to cool 5910 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 216.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14S — a Series 3000 cooling tower, 1052 nominal tons (4627 kW): rated to cool 3168 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 115.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14S-2 — a Series 3000 cooling tower, 2105 nominal tons (9253 kW): rated to cool 6336 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 230.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14T-2 — a Series 3000 cooling tower, 2286 nominal tons (10051 kW): rated to cool 6882 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 250.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1222-14T — a Series 3000 cooling tower, 1143 nominal tons (5025 kW): rated to cool 3441 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 125.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's S3E-1424-07O — a Series 3000 cooling tower, 619 nominal tons (2721 kW): rated to cool 1863 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers