Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 289–312 of 3346

Baltimore Aircoil Series 3000 S3E-1222-12Q-2 cooling tower (1731 tons, 7.6 MW) — modelled

BAC's S3E-1222-12Q-2 — a Series 3000 cooling tower, 1731 nominal tons (7610 kW): rated to cool 5211 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 192.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 5708–9513 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-12R cooling tower (914 tons, 4.0 MW) — modelled

BAC's S3E-1222-12R — a Series 3000 cooling tower, 914 nominal tons (4018 kW): rated to cool 2751 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 101.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 3013–5022 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-12R-2 cooling tower (1829 tons, 8.0 MW) — modelled

BAC's S3E-1222-12R-2 — a Series 3000 cooling tower, 1829 nominal tons (8040 kW): rated to cool 5505 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 203.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 6030–10050 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-12S cooling tower (978 tons, 4.3 MW) — modelled

BAC's S3E-1222-12S — a Series 3000 cooling tower, 978 nominal tons (4298 kW): rated to cool 2943 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 108.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 3224–5373 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-12S-2 cooling tower (1954 tons, 8.6 MW) — modelled

BAC's S3E-1222-12S-2 — a Series 3000 cooling tower, 1954 nominal tons (8592 kW): rated to cool 5883 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 216.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 6444–10740 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-13P cooling tower (836 tons, 3.7 MW) — modelled

BAC's S3E-1222-13P — a Series 3000 cooling tower, 836 nominal tons (3676 kW): rated to cool 2517 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 93.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 2757–4595 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-13P-2 cooling tower (1672 tons, 7.4 MW) — modelled

BAC's S3E-1222-13P-2 — a Series 3000 cooling tower, 1672 nominal tons (7352 kW): rated to cool 5034 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 185.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 5514–9190 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-13Q cooling tower (894 tons, 3.9 MW) — modelled

BAC's S3E-1222-13Q — a Series 3000 cooling tower, 894 nominal tons (3930 kW): rated to cool 2691 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 99.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 2948–4913 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-13Q-2 cooling tower (1788 tons, 7.9 MW) — modelled

BAC's S3E-1222-13Q-2 — a Series 3000 cooling tower, 1788 nominal tons (7860 kW): rated to cool 5382 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 198.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 5895–9825 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-13R cooling tower (944 tons, 4.1 MW) — modelled

BAC's S3E-1222-13R — a Series 3000 cooling tower, 944 nominal tons (4149 kW): rated to cool 2841 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 104.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 3112–5186 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-13R-2 cooling tower (1889 tons, 8.3 MW) — modelled

BAC's S3E-1222-13R-2 — a Series 3000 cooling tower, 1889 nominal tons (8303 kW): rated to cool 5685 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 208.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 6227–10378 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-13S cooling tower (1010 tons, 4.4 MW) — modelled

BAC's S3E-1222-13S — a Series 3000 cooling tower, 1010 nominal tons (4438 kW): rated to cool 3039 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 111.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 3329–5548 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-13S-2 cooling tower (2018 tons, 8.9 MW) — modelled

BAC's S3E-1222-13S-2 — a Series 3000 cooling tower, 2018 nominal tons (8872 kW): rated to cool 6075 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 222.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 6654–11090 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14P cooling tower (869 tons, 3.8 MW) — modelled

BAC's S3E-1222-14P — a Series 3000 cooling tower, 869 nominal tons (3821 kW): rated to cool 2616 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 96.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 2865–4776 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14P-2 cooling tower (1738 tons, 7.6 MW) — modelled

BAC's S3E-1222-14P-2 — a Series 3000 cooling tower, 1738 nominal tons (7641 kW): rated to cool 5232 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 192.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 5731–9551 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14Q cooling tower (930 tons, 4.1 MW) — modelled

BAC's S3E-1222-14Q — a Series 3000 cooling tower, 930 nominal tons (4088 kW): rated to cool 2799 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 102.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 3066–5110 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14Q-2 cooling tower (1860 tons, 8.2 MW) — modelled

BAC's S3E-1222-14Q-2 — a Series 3000 cooling tower, 1860 nominal tons (8176 kW): rated to cool 5598 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 205.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 6132–10220 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14R cooling tower (982 tons, 4.3 MW) — modelled

BAC's S3E-1222-14R — a Series 3000 cooling tower, 982 nominal tons (4316 kW): rated to cool 2955 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 108.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 3237–5395 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14R-2 cooling tower (1963 tons, 8.6 MW) — modelled

BAC's S3E-1222-14R-2 — a Series 3000 cooling tower, 1963 nominal tons (8631 kW): rated to cool 5910 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 216.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 6473–10789 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14S cooling tower (1052 tons, 4.6 MW) — modelled

BAC's S3E-1222-14S — a Series 3000 cooling tower, 1052 nominal tons (4627 kW): rated to cool 3168 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 115.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 3470–5783 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14S-2 cooling tower (2105 tons, 9.3 MW) — modelled

BAC's S3E-1222-14S-2 — a Series 3000 cooling tower, 2105 nominal tons (9253 kW): rated to cool 6336 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 230.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 6940–11567 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14T-2 cooling tower (2286 tons, 10.1 MW) — modelled

BAC's S3E-1222-14T-2 — a Series 3000 cooling tower, 2286 nominal tons (10051 kW): rated to cool 6882 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 250.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 7538–12564 kW · EU

Baltimore Aircoil Series 3000 S3E-1222-14T cooling tower (1143 tons, 5.0 MW) — modelled

BAC's S3E-1222-14T — a Series 3000 cooling tower, 1143 nominal tons (5025 kW): rated to cool 3441 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 125.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 3769–6282 kW · EU

Baltimore Aircoil Series 3000 S3E-1424-07O cooling tower (619 tons, 2.7 MW) — modelled

BAC's S3E-1424-07O — a Series 3000 cooling tower, 619 nominal tons (2721 kW): rated to cool 1863 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11F-92R20) ✓
Cooling tower / heat rejection · 2041–3401 kW · EU
‹ Previous1…1112131415…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers