Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 313–336 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
American Cooling Tower ACX-2094-1 cooling tower (807 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2094-1 — an ACX cooling tower, 807 nominal tons (3549 kW): rated to cool 2430 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 95.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2662–4436 kWNAOpen in the builder
Baltimore Aircoil PCC-0106-0412N010 evaporative condenser (644 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0106-0412N010 — a PCC evaporative condenser rejecting 644 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 14.4 m³/s of the maker's own printed air, with a 0.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection483–805 kWEUOpen in the builder
EVAPCO AT 112-2K18 cooling tower (495 tons, 2.2 MW) — modelled Example modelled from published data
EVAPCO's 112-2K18 — an AT cooling tower, 495 nominal tons (2178 kW): rated to cool 1491 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1633–2722 kWEUOpen in the builder
American Cooling Tower ACX-2095-1 cooling tower (869 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2095-1 — an ACX cooling tower, 869 nominal tons (3821 kW): rated to cool 2616 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 102.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2865–4776 kWNAOpen in the builder
Baltimore Aircoil PFI-0406N-5D1EZ-G1 closed-circuit cooler (27 tons, 118 kW) — modelled Example modelled from published data
BAC's PFI-0406N-5D1EZ-G1 — a PFi closed-circuit cooler, 27 nominal tons (118 kW): rated to cool 81 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 5.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection89–148 kWEUOpen in the builder
EVAPCO ATWB 12-3L14 closed-circuit cooler (279 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-3L14 — an ATWB closed-circuit cooler, 279 nominal tons (1228 kW): rated to cool 701 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 44.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection921–1535 kWEUOpen in the builder
American Cooling Tower ACX-2096-1 cooling tower (923 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2096-1 — an ACX cooling tower, 923 nominal tons (4057 kW): rated to cool 2778 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 108.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3043–5071 kWNAOpen in the builder
Baltimore Aircoil PT2-0709A-2L cooling tower (198 tons, 872 kW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0709A-2L — a PT2 cooling tower, 198 nominal tons (872 kW): rated to cool 597 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 22.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection654–1090 kWEUOpen in the builder
EVAPCO AT 112-2K20 cooling tower (457 tons, 2.0 MW) — modelled Example modelled from published data
EVAPCO's 112-2K20 — an AT cooling tower, 457 nominal tons (2011 kW): rated to cool 1377 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1508–2514 kWEUOpen in the builder
American Cooling Tower ACX-2097-1 cooling tower (995 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2097-1 — an ACX cooling tower, 995 nominal tons (4373 kW): rated to cool 2994 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 117.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3279–5466 kWNAOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-07LC-2 cooling tower (662 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-07LC-2 — a Series 1500 cooling tower, 662 nominal tons (2909 kW): rated to cool 1992 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2182–3637 kWEUOpen in the builder
EVAPCO ATWB 12-3L20 closed-circuit cooler (387 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-3L20 — an ATWB closed-circuit cooler, 387 nominal tons (1699 kW): rated to cool 970 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 58.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1274–2124 kWEUOpen in the builder
American Cooling Tower ACX-2098-1 cooling tower (1093 tons, 4.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2098-1 — an ACX cooling tower, 1093 nominal tons (4806 kW): rated to cool 3291 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 128.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3605–6008 kWNAOpen in the builder
Baltimore Aircoil Series 3000 S3E-1020-06O-2 cooling tower (869 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1020-06O-2 — a Series 3000 cooling tower, 869 nominal tons (3821 kW): rated to cool 2616 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 104.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2865–4776 kWEUOpen in the builder
EVAPCO AT 112-2L12 cooling tower (390 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-2L12 — an AT cooling tower, 390 nominal tons (1713 kW): rated to cool 1173 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1285–2141 kWEUOpen in the builder
American Cooling Tower ACX-2100-1 cooling tower (655 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2100-1 — an ACX cooling tower, 655 nominal tons (2879 kW): rated to cool 1971 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 77.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2159–3598 kWNAOpen in the builder
Baltimore Aircoil Series V VT0-145-M cooling tower (145 tons, 635 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-145-M — a Series V cooling tower, 145 nominal tons (635 kW): rated to cool 435 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 15.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection476–794 kWEUOpen in the builder
EVAPCO ATWB 12-3L28 closed-circuit cooler (559 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-3L28 — an ATWB closed-circuit cooler, 559 nominal tons (2456 kW): rated to cool 1402 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 89.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1842–3070 kWEUOpen in the builder
American Cooling Tower ACX-2101-1 cooling tower (720 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2101-1 — an ACX cooling tower, 720 nominal tons (3163 kW): rated to cool 2166 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2373–3954 kWNAOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-009-32G closed-circuit cooler (8 tons, 35 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-009-32G — a Series V closed circuit closed-circuit cooler, 8 nominal tons (35 kW): rated to cool 24 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 2.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection26–44 kWEUOpen in the builder
EVAPCO AT 112-2L14 cooling tower (424 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-2L14 — an AT cooling tower, 424 nominal tons (1862 kW): rated to cool 1275 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 49.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1397–2328 kWEUOpen in the builder
American Cooling Tower ACX-2102-1 cooling tower (775 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2102-1 — an ACX cooling tower, 775 nominal tons (3409 kW): rated to cool 2334 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 91.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2557–4261 kWNAOpen in the builder
Baltimore Aircoil VCL-044 evaporative condenser (190 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-044 — a Series V EC evaporative condenser rejecting 190 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 6.0 m³/s of the maker's own printed air, with a 1.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection142–237 kWEUOpen in the builder
EVAPCO ATWB 12-3L40 closed-circuit cooler (768 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-3L40 — an ATWB closed-circuit cooler, 768 nominal tons (3374 kW): rated to cool 1925 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 117.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2531–4218 kWEUOpen in the builder
‹ Previous1…1213141516…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers