Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 265–288 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
American Cooling Tower ACX-2075-1 cooling tower (804 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2075-1 — an ACX cooling tower, 804 nominal tons (3536 kW): rated to cool 2421 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 96.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2652–4420 kWNAOpen in the builder
Baltimore Aircoil Nexus NXF-0403N-CS2TT-H5 closed-circuit cooler (100 tons, 438 kW) — modelled Example modelled from published data
BAC's NXF-0403N-CS2TT-H5 — a Nexus closed-circuit cooler, 100 nominal tons (438 kW): rated to cool 300 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 19.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection329–548 kWEUOpen in the builder
EVAPCO AT 110-4N18 cooling tower (568 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 110-4N18 — an AT cooling tower, 568 nominal tons (2497 kW): rated to cool 1710 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1873–3122 kWEUOpen in the builder
American Cooling Tower ACX-2076-1 cooling tower (854 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2076-1 — an ACX cooling tower, 854 nominal tons (3755 kW): rated to cool 2571 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 102.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2816–4694 kWNAOpen in the builder
Baltimore Aircoil PCC-0090-0412N010 evaporative condenser (547 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0090-0412N010 — a PCC evaporative condenser rejecting 547 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 15.8 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection410–683 kWEUOpen in the builder
EVAPCO ATWB 10-7I36 closed-circuit cooler (618 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 10-7I36 — an ATWB closed-circuit cooler, 618 nominal tons (2717 kW): rated to cool 1550 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 61.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2037–3396 kWEUOpen in the builder
American Cooling Tower ACX-2077-1 cooling tower (920 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2077-1 — an ACX cooling tower, 920 nominal tons (4044 kW): rated to cool 2769 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 110.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3033–5055 kWNAOpen in the builder
Baltimore Aircoil PFI-0406N-4D2DZ-G1 closed-circuit cooler (23 tons, 101 kW) — modelled Example modelled from published data
BAC's PFI-0406N-4D2DZ-G1 — a PFi closed-circuit cooler, 23 nominal tons (101 kW): rated to cool 69 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 6.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection76–126 kWEUOpen in the builder
EVAPCO AT 112-2I12 cooling tower (279 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-2I12 — an AT cooling tower, 279 nominal tons (1227 kW): rated to cool 840 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection920–1533 kWEUOpen in the builder
American Cooling Tower ACX-2080-1 cooling tower (605 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2080-1 — an ACX cooling tower, 605 nominal tons (2659 kW): rated to cool 1821 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1995–3324 kWNAOpen in the builder
Baltimore Aircoil PT2-0709A-1K cooling tower (158 tons, 697 kW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0709A-1K — a PT2 cooling tower, 158 nominal tons (697 kW): rated to cool 477 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection522–871 kWEUOpen in the builder
EVAPCO ATWB 10-7J36 closed-circuit cooler (704 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 10-7J36 — an ATWB closed-circuit cooler, 704 nominal tons (3095 kW): rated to cool 1766 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 69.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2321–3869 kWEUOpen in the builder
American Cooling Tower ACX-2081-1 cooling tower (666 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2081-1 — an ACX cooling tower, 666 nominal tons (2927 kW): rated to cool 2004 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2195–3658 kWNAOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-07LC cooling tower (331 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-07LC — a Series 1500 cooling tower, 331 nominal tons (1455 kW): rated to cool 996 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1091–1818 kWEUOpen in the builder
EVAPCO AT 112-2I14 cooling tower (298 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-2I14 — an AT cooling tower, 298 nominal tons (1310 kW): rated to cool 897 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection983–1638 kWEUOpen in the builder
American Cooling Tower ACX-2082-1 cooling tower (717 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2082-1 — an ACX cooling tower, 717 nominal tons (3150 kW): rated to cool 2157 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2363–3938 kWNAOpen in the builder
Baltimore Aircoil Series 3000 S3E-1020-06O cooling tower (435 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1020-06O — a Series 3000 cooling tower, 435 nominal tons (1910 kW): rated to cool 1308 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1433–2388 kWEUOpen in the builder
EVAPCO ATWB 10-7K36 closed-circuit cooler (772 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 10-7K36 — an ATWB closed-circuit cooler, 772 nominal tons (3392 kW): rated to cool 1935 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 76.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2544–4240 kWEUOpen in the builder
American Cooling Tower ACX-2083-1 cooling tower (761 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2083-1 — an ACX cooling tower, 761 nominal tons (3347 kW): rated to cool 2292 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 91.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2511–4184 kWNAOpen in the builder
Baltimore Aircoil Series V VT0-14-F cooling tower (14 tons, 61 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-14-F — a Series V cooling tower, 14 nominal tons (61 kW): rated to cool 42 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 2.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection46–77 kWEUOpen in the builder
EVAPCO AT 112-2J12 cooling tower (333 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-2J12 — an AT cooling tower, 333 nominal tons (1463 kW): rated to cool 1002 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1098–1829 kWEUOpen in the builder
American Cooling Tower ACX-2084-1 cooling tower (837 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-2084-1 — an ACX cooling tower, 837 nominal tons (3680 kW): rated to cool 2520 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 100.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2760–4600 kWNAOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-009-22G closed-circuit cooler (7 tons, 31 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-009-22G — a Series V closed circuit closed-circuit cooler, 7 nominal tons (31 kW): rated to cool 21 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 2.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection23–38 kWEUOpen in the builder
EVAPCO ATWB 10-7L36 closed-circuit cooler (828 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 10-7L36 — an ATWB closed-circuit cooler, 828 nominal tons (3639 kW): rated to cool 2076 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 82.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2729–4549 kWEUOpen in the builder
‹ Previous1…1011121314…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers