Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 2,953–2,976 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 424-4N36 cooling tower (2727 tons, 12.0 MW) — modelled Example modelled from published data EVAPCO's 424-4N36 — an AT cooling tower, 2727 nominal tons (11987 kW): rated to cool 8208 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 263.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 8991–14984 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0980-1236N080 evaporative condenser (6.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0980-1236N080 — a PCC evaporative condenser rejecting 5954 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 129.9 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4465–7442 kW | EU | Open in the builder |
| EVAPCO AT 424-4N40 cooling tower (2789 tons, 12.3 MW) — modelled Example modelled from published data EVAPCO's 424-4N40 — an AT cooling tower, 2789 nominal tons (12259 kW): rated to cool 8394 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 267.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 9194–15324 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1212N-3D2ES-M1 closed-circuit cooler (152 tons, 670 kW) — modelled Example modelled from published data BAC's PFI-1212N-3D2ES-M1 — a PFi closed-circuit cooler, 152 nominal tons (670 kW): rated to cool 459 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 39.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 503–838 kW | EU | Open in the builder |
| EVAPCO AT 424-4O36 cooling tower (2928 tons, 12.9 MW) — modelled Example modelled from published data EVAPCO's 424-4O36 — an AT cooling tower, 2928 nominal tons (12872 kW): rated to cool 8814 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 282.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 9654–16091 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1212-12HN cooling tower (322 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1212-12HN — a Series 1500 cooling tower, 322 nominal tons (1415 kW): rated to cool 969 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1061–1769 kW | EU | Open in the builder |
| EVAPCO AT 424-4O40 cooling tower (3018 tons, 13.3 MW) — modelled Example modelled from published data EVAPCO's 424-4O40 — an AT cooling tower, 3018 nominal tons (13267 kW): rated to cool 9084 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 287.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 9950–16584 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1222-06H cooling tower (278 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-06H — a Series 3000 cooling tower, 278 nominal tons (1222 kW): rated to cool 837 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 917–1528 kW | EU | Open in the builder |
| EVAPCO AT 424-4P36 cooling tower (3039 tons, 13.4 MW) — modelled Example modelled from published data EVAPCO's 424-4P36 — an AT cooling tower, 3039 nominal tons (13359 kW): rated to cool 9147 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 299.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 10019–16699 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-432-21O closed-circuit cooler (375 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-432-21O — a Series V closed circuit closed-circuit cooler, 375 nominal tons (1647 kW): rated to cool 1128 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 118.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1236–2059 kW | EU | Open in the builder |
| EVAPCO AT 424-4P40 cooling tower (3131 tons, 13.8 MW) — modelled Example modelled from published data EVAPCO's 424-4P40 — an AT cooling tower, 3131 nominal tons (13762 kW): rated to cool 9423 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 304.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 10321–17202 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-887A evaporative condenser (3.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-887A — a VCA evaporative condenser rejecting 3821 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 63.5 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2866–4777 kW | EU | Open in the builder |
| EVAPCO AT 428-5K52 cooling tower (3844 tons, 16.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 428-5K52 — an AT cooling tower, 3844 nominal tons (16899 kW): rated to cool 11571 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 352.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 12674–21124 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0889B-1224N-MA evaporative condenser (5.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0889B-1224N-MA — a Vertex VRC evaporative condenser rejecting 5394 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 80.4 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4045–6742 kW | EU | Open in the builder |
| EVAPCO AT 428-5L52 cooling tower (4134 tons, 18.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 428-5L52 — an AT cooling tower, 4134 nominal tons (18174 kW): rated to cool 12444 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 377.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 13630–22717 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0982-2420N040 evaporative condenser (6.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0982-2420N040 — a PCC evaporative condenser rejecting 5965 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 104.1 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4474–7456 kW | EU | Open in the builder |
| EVAPCO AT 428-5M52 cooling tower (4380 tons, 19.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 428-5M52 — an AT cooling tower, 4380 nominal tons (19256 kW): rated to cool 13185 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 400.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 14442–24070 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1212N-3D3ES-N1 closed-circuit cooler (161 tons, 710 kW) — modelled Example modelled from published data BAC's PFI-1212N-3D3ES-N1 — a PFi closed-circuit cooler, 161 nominal tons (710 kW): rated to cool 486 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 40.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 532–887 kW | EU | Open in the builder |
| EVAPCO AT 428-5N52 cooling tower (4790 tons, 21.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 428-5N52 — an AT cooling tower, 4790 nominal tons (21057 kW): rated to cool 14418 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 437.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 15793–26321 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1212-12JN cooling tower (367 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1212-12JN — a Series 1500 cooling tower, 367 nominal tons (1612 kW): rated to cool 1104 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1209–2015 kW | EU | Open in the builder |
| EVAPCO AT 428-5O52 cooling tower (5124 tons, 22.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 428-5O52 — an AT cooling tower, 5124 nominal tons (22525 kW): rated to cool 15423 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 468.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 16894–28156 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1222-06J cooling tower (317 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-06J — a Series 3000 cooling tower, 317 nominal tons (1393 kW): rated to cool 954 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1045–1742 kW | EU | Open in the builder |
| EVAPCO AT 456-5K26 cooling tower (3789 tons, 16.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 456-5K26 — an AT cooling tower, 3789 nominal tons (16658 kW): rated to cool 11406 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 352.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 12494–20823 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-432-21P closed-circuit cooler (433 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-432-21P — a Series V closed circuit closed-circuit cooler, 433 nominal tons (1902 kW): rated to cool 1302 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 129.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1426–2377 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers