Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,905–2,928 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 424-3N28 cooling tower (2192 tons, 9.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-3N28 — an AT cooling tower, 2192 nominal tons (9635 kW): rated to cool 6597 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 215.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7226–12043 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-288N-41P closed-circuit cooler (259 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-288N-41P — a Series V closed circuit closed-circuit cooler, 259 nominal tons (1139 kW): rated to cool 780 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 62.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection854–1424 kWEUOpen in the builder
EVAPCO AT 424-3N36 cooling tower (2605 tons, 11.5 MW) — modelled Example modelled from published data
EVAPCO's 424-3N36 — an AT cooling tower, 2605 nominal tons (11453 kW): rated to cool 7842 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 267.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection8590–14316 kWEUOpen in the builder
Baltimore Aircoil VCA-840A evaporative condenser (3.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-840A — a VCA evaporative condenser rejecting 3619 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2714–4524 kWEUOpen in the builder
EVAPCO AT 424-3N40 cooling tower (2661 tons, 11.7 MW) — modelled Example modelled from published data
EVAPCO's 424-3N40 — an AT cooling tower, 2661 nominal tons (11698 kW): rated to cool 8010 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 272.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection8774–14623 kWEUOpen in the builder
Baltimore Aircoil VRC-0865B-1036N-JA evaporative condenser (5.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0865B-1036N-JA — a Vertex VRC evaporative condenser rejecting 5247 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 77.2 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3935–6559 kWEUOpen in the builder
EVAPCO AT 424-3O36 cooling tower (2797 tons, 12.3 MW) — modelled Example modelled from published data
EVAPCO's 424-3O36 — an AT cooling tower, 2797 nominal tons (12294 kW): rated to cool 8418 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 287.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection9221–15368 kWEUOpen in the builder
Baltimore Aircoil PCC-0931-1236N040 evaporative condenser (5.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0931-1236N040 — a PCC evaporative condenser rejecting 5652 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 91.9 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4239–7066 kWEUOpen in the builder
EVAPCO AT 424-3O40 cooling tower (2890 tons, 12.7 MW) — modelled Example modelled from published data
EVAPCO's 424-3O40 — an AT cooling tower, 2890 nominal tons (12706 kW): rated to cool 8700 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 291.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection9530–15883 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-3D2DS-N1 closed-circuit cooler (148 tons, 648 kW) — modelled Example modelled from published data
BAC's PFI-1212N-3D2DS-N1 — a PFi closed-circuit cooler, 148 nominal tons (648 kW): rated to cool 444 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 43.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection486–811 kWEUOpen in the builder
EVAPCO AT 424-4I24 cooling tower (1336 tons, 5.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-4I24 — an AT cooling tower, 1336 nominal tons (5871 kW): rated to cool 4020 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 129.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4403–7339 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-12GC cooling tower (256 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-12GC — a Series 1500 cooling tower, 256 nominal tons (1126 kW): rated to cool 771 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection845–1408 kWEUOpen in the builder
EVAPCO AT 424-4I28 cooling tower (1429 tons, 6.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-4I28 — an AT cooling tower, 1429 nominal tons (6283 kW): rated to cool 4302 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 136.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4712–7854 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-1020-07J cooling tower (309 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-1020-07J — a Series 3000 cooling tower, 309 nominal tons (1358 kW): rated to cool 930 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1019–1698 kWEUOpen in the builder
EVAPCO AT 424-4J24 cooling tower (1537 tons, 6.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-4J24 — an AT cooling tower, 1537 nominal tons (6756 kW): rated to cool 4626 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 147.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5067–8445 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-288N-41Q closed-circuit cooler (287 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-288N-41Q — a Series V closed circuit closed-circuit cooler, 287 nominal tons (1262 kW): rated to cool 864 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 67.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection946–1577 kWEUOpen in the builder
EVAPCO AT 424-4J28 cooling tower (1648 tons, 7.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-4J28 — an AT cooling tower, 1648 nominal tons (7247 kW): rated to cool 4962 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 155.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5435–9059 kWEUOpen in the builder
Baltimore Aircoil VCA-858A evaporative condenser (3.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-858A — a VCA evaporative condenser rejecting 3697 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 56.6 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2772–4621 kWEUOpen in the builder
EVAPCO AT 424-4J36 cooling tower (1998 tons, 8.8 MW) — modelled Example modelled from published data
EVAPCO's 424-4J36 — an AT cooling tower, 1998 nominal tons (8785 kW): rated to cool 6015 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 193.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6589–10981 kWEUOpen in the builder
Baltimore Aircoil VRC-0871B-1036N-HB evaporative condenser (5.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0871B-1036N-HB — a Vertex VRC evaporative condenser rejecting 5281 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 100.5 m³/s of the maker's own printed air, with a 51.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3961–6601 kWEUOpen in the builder
EVAPCO AT 424-4K24 cooling tower (1672 tons, 7.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-4K24 — an AT cooling tower, 1672 nominal tons (7352 kW): rated to cool 5034 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 161.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5514–9190 kWEUOpen in the builder
Baltimore Aircoil PCC-0938-2418N040 evaporative condenser (5.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0938-2418N040 — a PCC evaporative condenser rejecting 5698 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 91.9 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4273–7122 kWEUOpen in the builder
EVAPCO AT 424-4K28 cooling tower (1827 tons, 8.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-4K28 — an AT cooling tower, 1827 nominal tons (8031 kW): rated to cool 5499 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 170.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6023–10039 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-3D2DS-O1 closed-circuit cooler (153 tons, 675 kW) — modelled Example modelled from published data
BAC's PFI-1212N-3D2DS-O1 — a PFi closed-circuit cooler, 153 nominal tons (675 kW): rated to cool 462 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 46.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection506–843 kWEUOpen in the builder
‹ Previous1…120121122123124…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers