Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,857–2,880 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 424-2M24 cooling tower (1642 tons, 7.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2M24 — an AT cooling tower, 1642 nominal tons (7216 kW): rated to cool 4941 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 189.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5412–9020 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-3D1DS-N1 closed-circuit cooler (143 tons, 627 kW) — modelled Example modelled from published data
BAC's PFI-1212N-3D1DS-N1 — a PFi closed-circuit cooler, 143 nominal tons (627 kW): rated to cool 429 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection470–783 kWEUOpen in the builder
EVAPCO AT 424-2M28 cooling tower (1832 tons, 8.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2M28 — an AT cooling tower, 1832 nominal tons (8053 kW): rated to cool 5514 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 200.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6040–10066 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-11HC cooling tower (284 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-11HC — a Series 1500 cooling tower, 284 nominal tons (1249 kW): rated to cool 855 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection937–1561 kWEUOpen in the builder
EVAPCO AT 424-2M36 cooling tower (2126 tons, 9.3 MW) — modelled Example modelled from published data
EVAPCO's 424-2M36 — an AT cooling tower, 2126 nominal tons (9345 kW): rated to cool 6399 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 249.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7009–11682 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-1020-06K cooling tower (306 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-1020-06K — a Series 3000 cooling tower, 306 nominal tons (1345 kW): rated to cool 921 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1009–1681 kWEUOpen in the builder
EVAPCO AT 424-2M40 cooling tower (2057 tons, 9.0 MW) — modelled Example modelled from published data
EVAPCO's 424-2M40 — an AT cooling tower, 2057 nominal tons (9043 kW): rated to cool 6192 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 253.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6782–11304 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-288N-31P closed-circuit cooler (243 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-288N-31P — a Series V closed circuit closed-circuit cooler, 243 nominal tons (1069 kW): rated to cool 732 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 63.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection802–1336 kWEUOpen in the builder
EVAPCO AT 424-2N36 cooling tower (2342 tons, 10.3 MW) — modelled Example modelled from published data
EVAPCO's 424-2N36 — an AT cooling tower, 2342 nominal tons (10296 kW): rated to cool 7050 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 273.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7722–12870 kWEUOpen in the builder
Baltimore Aircoil VCA-808A evaporative condenser (3.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-808A — a VCA evaporative condenser rejecting 3481 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 71.1 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2611–4351 kWEUOpen in the builder
EVAPCO AT 424-2N40 cooling tower (2371 tons, 10.4 MW) — modelled Example modelled from published data
EVAPCO's 424-2N40 — an AT cooling tower, 2371 nominal tons (10423 kW): rated to cool 7137 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 277.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection7817–13029 kWEUOpen in the builder
Baltimore Aircoil VRC-0831B-1224N-LA evaporative condenser (5.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0831B-1224N-LA — a Vertex VRC evaporative condenser rejecting 5041 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 72.7 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3781–6301 kWEUOpen in the builder
EVAPCO AT 424-2O40 cooling tower (2575 tons, 11.3 MW) — modelled Example modelled from published data
EVAPCO's 424-2O40 — an AT cooling tower, 2575 nominal tons (11321 kW): rated to cool 7752 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 297.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection8491–14152 kWEUOpen in the builder
Baltimore Aircoil PCC-0862-2420N030 evaporative condenser (5.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0862-2420N030 — a PCC evaporative condenser rejecting 5236 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 104.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3927–6545 kWEUOpen in the builder
EVAPCO AT 424-3I24 cooling tower (1253 tons, 5.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-3I24 — an AT cooling tower, 1253 nominal tons (5507 kW): rated to cool 3771 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 131.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4131–6884 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-3D1DS-P1 closed-circuit cooler (156 tons, 688 kW) — modelled Example modelled from published data
BAC's PFI-1212N-3D1DS-P1 — a PFi closed-circuit cooler, 156 nominal tons (688 kW): rated to cool 471 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 52.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection516–860 kWEUOpen in the builder
EVAPCO AT 424-3I28 cooling tower (1318 tons, 5.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-3I28 — an AT cooling tower, 1318 nominal tons (5792 kW): rated to cool 3966 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 139.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4344–7240 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-11HN cooling tower (310 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-11HN — a Series 1500 cooling tower, 310 nominal tons (1363 kW): rated to cool 933 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1022–1703 kWEUOpen in the builder
EVAPCO AT 424-3J24 cooling tower (1466 tons, 6.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-3J24 — an AT cooling tower, 1466 nominal tons (6445 kW): rated to cool 4413 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 149.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4834–8056 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-1020-06L cooling tower (349 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-1020-06L — a Series 3000 cooling tower, 349 nominal tons (1533 kW): rated to cool 1050 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1150–1917 kWEUOpen in the builder
EVAPCO AT 424-3J28 cooling tower (1558 tons, 6.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-3J28 — an AT cooling tower, 1558 nominal tons (6848 kW): rated to cool 4689 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 158.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5136–8560 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-288N-31Q closed-circuit cooler (270 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-288N-31Q — a Series V closed circuit closed-circuit cooler, 270 nominal tons (1187 kW): rated to cool 813 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 67.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection891–1484 kWEUOpen in the builder
EVAPCO AT 424-3J36 cooling tower (1877 tons, 8.3 MW) — modelled Example modelled from published data
EVAPCO's 424-3J36 — an AT cooling tower, 1877 nominal tons (8250 kW): rated to cool 5649 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 196.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6188–10313 kWEUOpen in the builder
Baltimore Aircoil VCA-814A evaporative condenser (3.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-814A — a VCA evaporative condenser rejecting 3507 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 61.7 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2630–4384 kWEUOpen in the builder
‹ Previous1…118119120121122…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers