Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,833–2,856 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 424-2I28 cooling tower (1155 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2I28 — an AT cooling tower, 1155 nominal tons (5078 kW): rated to cool 3477 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 141.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3809–6348 kWEUOpen in the builder
Baltimore Aircoil VT1-600-P cooling tower (600 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
A 600-ton counterflow Series V — centrifugal fans, forced draft, 1 800 USGPM cooled from 95 to 85 °F at a 78 °F entering wet bulb on 61.9 m³/s of air. Its liquid-to-gas ratio of about 1.6 is the highest of the five published here, which is why its derived NTU is the highest too: a counterflow tower works its fill harder per unit of air than a crossflow one. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2200–3200 kWEUOpen in the builder
EVAPCO AT 424-2J24 cooling tower (1323 tons, 5.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2J24 — an AT cooling tower, 1323 nominal tons (5814 kW): rated to cool 3981 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 152.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4361–7268 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-288N-21Q closed-circuit cooler (252 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-288N-21Q — a Series V closed circuit closed-circuit cooler, 252 nominal tons (1108 kW): rated to cool 759 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 68.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection831–1386 kWEUOpen in the builder
EVAPCO AT 424-2J28 cooling tower (1400 tons, 6.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2J28 — an AT cooling tower, 1400 nominal tons (6156 kW): rated to cool 4215 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 160.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4617–7695 kWEUOpen in the builder
Baltimore Aircoil VCA-785A evaporative condenser (3.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-785A — a VCA evaporative condenser rejecting 3382 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 57.9 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2537–4228 kWEUOpen in the builder
EVAPCO AT 424-2J36 cooling tower (1681 tons, 7.4 MW) — modelled Example modelled from published data
EVAPCO's 424-2J36 — an AT cooling tower, 1681 nominal tons (7391 kW): rated to cool 5061 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 199.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5544–9239 kWEUOpen in the builder
Baltimore Aircoil VRC-0824B-1224N-MA evaporative condenser (5.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0824B-1224N-MA — a Vertex VRC evaporative condenser rejecting 4997 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 84.7 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3748–6247 kWEUOpen in the builder
EVAPCO AT 424-2K24 cooling tower (1444 tons, 6.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2K24 — an AT cooling tower, 1444 nominal tons (6349 kW): rated to cool 4347 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 166.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4761–7936 kWEUOpen in the builder
Baltimore Aircoil PCC-0812-2412N080 evaporative condenser (4.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0812-2412N080 — a PCC evaporative condenser rejecting 4932 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 79.7 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3699–6165 kWEUOpen in the builder
EVAPCO AT 424-2K28 cooling tower (1559 tons, 6.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2K28 — an AT cooling tower, 1559 nominal tons (6852 kW): rated to cool 4692 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 176.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5139–8566 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-3D1DS-M1 closed-circuit cooler (136 tons, 596 kW) — modelled Example modelled from published data
BAC's PFI-1212N-3D1DS-M1 — a PFi closed-circuit cooler, 136 nominal tons (596 kW): rated to cool 408 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 42.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection447–745 kWEUOpen in the builder
EVAPCO AT 424-2K36 cooling tower (1908 tons, 8.4 MW) — modelled Example modelled from published data
EVAPCO's 424-2K36 — an AT cooling tower, 1908 nominal tons (8386 kW): rated to cool 5742 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 218.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6289–10482 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-11GN cooling tower (262 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-11GN — a Series 1500 cooling tower, 262 nominal tons (1152 kW): rated to cool 789 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection864–1440 kWEUOpen in the builder
EVAPCO AT 424-2K40 cooling tower (1727 tons, 7.6 MW) — modelled Example modelled from published data
EVAPCO's 424-2K40 — an AT cooling tower, 1727 nominal tons (7593 kW): rated to cool 5199 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 222.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5695–9491 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-1020-06J cooling tower (278 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-1020-06J — a Series 3000 cooling tower, 278 nominal tons (1222 kW): rated to cool 837 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection917–1528 kWEUOpen in the builder
EVAPCO AT 424-2L24 cooling tower (1550 tons, 6.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2L24 — an AT cooling tower, 1550 nominal tons (6813 kW): rated to cool 4665 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 179.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5110–8516 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-288N-21R closed-circuit cooler (276 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-288N-21R — a Series V closed circuit closed-circuit cooler, 276 nominal tons (1214 kW): rated to cool 831 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 73.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection910–1517 kWEUOpen in the builder
EVAPCO AT 424-2L28 cooling tower (1683 tons, 7.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2L28 — an AT cooling tower, 1683 nominal tons (7400 kW): rated to cool 5067 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 188.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5550–9250 kWEUOpen in the builder
Baltimore Aircoil VCA-804A evaporative condenser (3.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-804A — a VCA evaporative condenser rejecting 3464 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 65.9 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2598–4330 kWEUOpen in the builder
EVAPCO AT 424-2L36 cooling tower (2016 tons, 8.9 MW) — modelled Example modelled from published data
EVAPCO's 424-2L36 — an AT cooling tower, 2016 nominal tons (8864 kW): rated to cool 6069 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 235.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6648–11079 kWEUOpen in the builder
Baltimore Aircoil VRC-0825B-1236N-JA evaporative condenser (5.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0825B-1236N-JA — a Vertex VRC evaporative condenser rejecting 5006 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 96.9 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3755–6258 kWEUOpen in the builder
EVAPCO AT 424-2L40 cooling tower (1913 tons, 8.4 MW) — modelled Example modelled from published data
EVAPCO's 424-2L40 — an AT cooling tower, 1913 nominal tons (8408 kW): rated to cool 5757 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 239.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6306–10510 kWEUOpen in the builder
Baltimore Aircoil PCC-0855-1240N030 evaporative condenser (5.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0855-1240N030 — a PCC evaporative condenser rejecting 5194 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 104.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3896–6493 kWEUOpen in the builder
‹ Previous1…117118119120121…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers