Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 2,809–2,832 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 39-4H42 cooling tower (796 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4H42 — an AT cooling tower, 796 nominal tons (3501 kW): rated to cool 2397 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2626–4376 kWEUOpen in the builder
Baltimore Aircoil PCC-0792-2412N080 evaporative condenser (4.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0792-2412N080 — a PCC evaporative condenser rejecting 4811 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 83.8 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3608–6013 kWEUOpen in the builder
EVAPCO AT 39-4I36 cooling tower (797 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4I36 — an AT cooling tower, 797 nominal tons (3505 kW): rated to cool 2400 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2629–4381 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-2D4ES-N1 closed-circuit cooler (125 tons, 548 kW) — modelled Example modelled from published data
BAC's PFI-1212N-2D4ES-N1 — a PFi closed-circuit cooler, 125 nominal tons (548 kW): rated to cool 375 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 42.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection411–685 kWEUOpen in the builder
EVAPCO AT 39-4I42 cooling tower (881 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4I42 — an AT cooling tower, 881 nominal tons (3873 kW): rated to cool 2652 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 84.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2905–4841 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-11FN cooling tower (230 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-11FN — a Series 1500 cooling tower, 230 nominal tons (1012 kW): rated to cool 693 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection759–1265 kWEUOpen in the builder
EVAPCO AT 39-4J36 cooling tower (890 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4J36 — an AT cooling tower, 890 nominal tons (3913 kW): rated to cool 2679 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2934–4891 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-1020-06G cooling tower (205 tons, 903 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-1020-06G — a Series 3000 cooling tower, 205 nominal tons (903 kW): rated to cool 618 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection677–1128 kWEUOpen in the builder
EVAPCO AT 39-4J42 cooling tower (983 tons, 4.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4J42 — an AT cooling tower, 983 nominal tons (4320 kW): rated to cool 2958 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 95.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3240–5400 kWEUOpen in the builder
Baltimore Aircoil VT0-12-E cooling tower (12 tons, 53 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
The smallest tower BAC publishes: a counterflow, centrifugal-fan, forced-draft unit rated to cool 36 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb. Drawn at the maker's own printed airflow (2.35 m³/s) and that rated water flow, this model reproduces the certified leaving-water temperature at the rated point exactly — the tower's NTU is derived from it. A centrifugal fan is what lets a Series V sit indoors or behind ductwork. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection40–65 kWEUOpen in the builder
EVAPCO AT 39-4K36 cooling tower (981 tons, 4.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4K36 — an AT cooling tower, 981 nominal tons (4311 kW): rated to cool 2952 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 93.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3233–5389 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-288N-21P closed-circuit cooler (225 tons, 990 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-288N-21P — a Series V closed circuit closed-circuit cooler, 225 nominal tons (990 kW): rated to cool 678 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 63.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection743–1238 kWEUOpen in the builder
EVAPCO AT 39-4K42 cooling tower (1080 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4K42 — an AT cooling tower, 1080 nominal tons (4749 kW): rated to cool 3252 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 104.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3562–5937 kWEUOpen in the builder
Baltimore Aircoil VCA-779A evaporative condenser (3.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-779A — a VCA evaporative condenser rejecting 3356 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 50.9 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2517–4195 kWEUOpen in the builder
EVAPCO AT 39-4L36 cooling tower (1047 tons, 4.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4L36 — an AT cooling tower, 1047 nominal tons (4600 kW): rated to cool 3150 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 100.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3450–5751 kWEUOpen in the builder
Baltimore Aircoil VRC-0810B-1224N-HB evaporative condenser (4.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0810B-1224N-HB — a Vertex VRC evaporative condenser rejecting 4914 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 67.8 m³/s of the maker's own printed air, with a 38.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3686–6143 kWEUOpen in the builder
EVAPCO AT 39-4L42 cooling tower (1170 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4L42 — an AT cooling tower, 1170 nominal tons (5144 kW): rated to cool 3522 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 111.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3858–6430 kWEUOpen in the builder
Baltimore Aircoil PCC-0812-1224N080 evaporative condenser (4.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0812-1224N080 — a PCC evaporative condenser rejecting 4932 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 79.7 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3699–6165 kWEUOpen in the builder
EVAPCO AT 39-4M36 cooling tower (1078 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4M36 — an AT cooling tower, 1078 nominal tons (4741 kW): rated to cool 3246 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 106.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3555–5926 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-2D4ES-O1 closed-circuit cooler (130 tons, 570 kW) — modelled Example modelled from published data
BAC's PFI-1212N-2D4ES-O1 — a PFi closed-circuit cooler, 130 nominal tons (570 kW): rated to cool 390 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 44.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection427–712 kWEUOpen in the builder
EVAPCO AT 39-4M42 cooling tower (1235 tons, 5.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 39-4M42 — an AT cooling tower, 1235 nominal tons (5429 kW): rated to cool 3717 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 118.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4071–6786 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1212-11GC cooling tower (247 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1212-11GC — a Series 1500 cooling tower, 247 nominal tons (1087 kW): rated to cool 744 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 27.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection815–1358 kWEUOpen in the builder
EVAPCO AT 424-2I24 cooling tower (1110 tons, 4.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 424-2I24 — an AT cooling tower, 1110 nominal tons (4881 kW): rated to cool 3342 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 133.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3661–6101 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-1020-06H cooling tower (243 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-1020-06H — a Series 3000 cooling tower, 243 nominal tons (1069 kW): rated to cool 732 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection802–1336 kWEUOpen in the builder
‹ Previous1…116117118119120…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers