Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 385–408 of 3346
BAC's XES3E-1222-07M — a Series 3000 cooling tower, 485 nominal tons (2134 kW): rated to cool 1461 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-10K — a Series 3000 cooling tower, 489 nominal tons (2151 kW): rated to cool 1473 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-10L — a Series 3000 cooling tower, 557 nominal tons (2449 kW): rated to cool 1677 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-10M — a Series 3000 cooling tower, 609 nominal tons (2677 kW): rated to cool 1833 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 69.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-10N — a Series 3000 cooling tower, 653 nominal tons (2870 kW): rated to cool 1965 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-10O — a Series 3000 cooling tower, 691 nominal tons (3036 kW): rated to cool 2079 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-12K — a Series 3000 cooling tower, 526 nominal tons (2313 kW): rated to cool 1584 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-12L — a Series 3000 cooling tower, 598 nominal tons (2629 kW): rated to cool 1800 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-12M — a Series 3000 cooling tower, 655 nominal tons (2879 kW): rated to cool 1971 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-12N — a Series 3000 cooling tower, 701 nominal tons (3080 kW): rated to cool 2109 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-12O — a Series 3000 cooling tower, 742 nominal tons (3260 kW): rated to cool 2232 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 83.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-13K — a Series 3000 cooling tower, 543 nominal tons (2388 kW): rated to cool 1635 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 62.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-13L — a Series 3000 cooling tower, 618 nominal tons (2716 kW): rated to cool 1860 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-13M — a Series 3000 cooling tower, 676 nominal tons (2971 kW): rated to cool 2034 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-13N — a Series 3000 cooling tower, 725 nominal tons (3185 kW): rated to cool 2181 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 81.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-13O — a Series 3000 cooling tower, 766 nominal tons (3369 kW): rated to cool 2307 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-14L — a Series 3000 cooling tower, 643 nominal tons (2826 kW): rated to cool 1935 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-14M — a Series 3000 cooling tower, 704 nominal tons (3093 kW): rated to cool 2118 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-14N — a Series 3000 cooling tower, 753 nominal tons (3312 kW): rated to cool 2268 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 84.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1222-14O — a Series 3000 cooling tower, 796 nominal tons (3501 kW): rated to cool 2397 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 88.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1424-07J — a Series 3000 cooling tower, 395 nominal tons (1735 kW): rated to cool 1188 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1424-07K — a Series 3000 cooling tower, 434 nominal tons (1906 kW): rated to cool 1305 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1424-07L — a Series 3000 cooling tower, 495 nominal tons (2178 kW): rated to cool 1491 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
BAC's XES3E-1424-07M — a Series 3000 cooling tower, 543 nominal tons (2388 kW): rated to cool 1635 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers