Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 409–432 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 112-3K18 cooling tower (544 tons, 2.4 MW) — modelled Example modelled from published data
EVAPCO's 112-3K18 — an AT cooling tower, 544 nominal tons (2392 kW): rated to cool 1638 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1794–2990 kWEUOpen in the builder
Baltimore Aircoil CXVT-1482-2826-50 evaporative condenser (9.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1482-2826-50 — a CXVT evaporative condenser rejecting 9002 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 160.1 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection6752–11253 kWEUOpen in the builder
EVAPCO ATWB 12-4L20 closed-circuit cooler (407 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4L20 — an ATWB closed-circuit cooler, 407 nominal tons (1789 kW): rated to cool 1021 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 57.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1342–2236 kWEUOpen in the builder
Baltimore Aircoil FXT-0709B-G cooling tower (97 tons, 425 kW) — modelled Example modelled from published data
BAC's FXT-0709B-G — an FXT cooling tower, 97 nominal tons (425 kW): rated to cool 291 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 13.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection319–531 kWEUOpen in the builder
EVAPCO AT 112-3K20 cooling tower (534 tons, 2.3 MW) — modelled Example modelled from published data
EVAPCO's 112-3K20 — an AT cooling tower, 534 nominal tons (2348 kW): rated to cool 1608 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1761–2936 kWEUOpen in the builder
Baltimore Aircoil FXV-0806B-28D-L closed-circuit cooler (83 tons, 364 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0806B-28D-L — an FXV closed-circuit cooler, 83 nominal tons (364 kW): rated to cool 249 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 19.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection273–455 kWEUOpen in the builder
EVAPCO ATWB 12-4L28 closed-circuit cooler (601 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4L28 — an ATWB closed-circuit cooler, 601 nominal tons (2642 kW): rated to cool 1508 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 87.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1981–3302 kWEUOpen in the builder
Baltimore Aircoil Nexus NXF-0603N-CS2TT-J3 closed-circuit cooler (90 tons, 394 kW) — modelled Example modelled from published data
BAC's NXF-0603N-CS2TT-J3 — a Nexus closed-circuit cooler, 90 nominal tons (394 kW): rated to cool 270 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 18.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection296–493 kWEUOpen in the builder
EVAPCO AT 112-3L12 cooling tower (433 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-3L12 — an AT cooling tower, 433 nominal tons (1902 kW): rated to cool 1302 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 44.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1426–2377 kWEUOpen in the builder
Baltimore Aircoil PCC-0118-0412N010 evaporative condenser (717 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0118-0412N010 — a PCC evaporative condenser rejecting 717 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 13.2 m³/s of the maker's own printed air, with a 0.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection538–896 kWEUOpen in the builder
EVAPCO ATWB 12-4L36 closed-circuit cooler (745 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4L36 — an ATWB closed-circuit cooler, 745 nominal tons (3275 kW): rated to cool 1869 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 106.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2456–4094 kWEUOpen in the builder
Baltimore Aircoil PFI-0406N-6D2DZ-J1 closed-circuit cooler (35 tons, 153 kW) — modelled Example modelled from published data
BAC's PFI-0406N-6D2DZ-J1 — a PFi closed-circuit cooler, 35 nominal tons (153 kW): rated to cool 105 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 7.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection115–192 kWEUOpen in the builder
EVAPCO AT 112-3L14 cooling tower (469 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-3L14 — an AT cooling tower, 469 nominal tons (2064 kW): rated to cool 1413 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 48.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1548–2580 kWEUOpen in the builder
Baltimore Aircoil PT2-0709A-5L cooling tower (222 tons, 977 kW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0709A-5L — a PT2 cooling tower, 222 nominal tons (977 kW): rated to cool 669 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 20.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection733–1221 kWEUOpen in the builder
EVAPCO ATWB 12-4L40 closed-circuit cooler (808 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4L40 — an ATWB closed-circuit cooler, 808 nominal tons (3553 kW): rated to cool 2027 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 114.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2664–4441 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-09KN cooling tower (357 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-09KN — a Series 1500 cooling tower, 357 nominal tons (1569 kW): rated to cool 1074 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1176–1961 kWEUOpen in the builder
EVAPCO AT 112-3L18 cooling tower (579 tons, 2.5 MW) — modelled Example modelled from published data
EVAPCO's 112-3L18 — an AT cooling tower, 579 nominal tons (2546 kW): rated to cool 1743 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1909–3182 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1020-07N cooling tower (455 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1020-07N — a Series 3000 cooling tower, 455 nominal tons (2002 kW): rated to cool 1371 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1502–2503 kWEUOpen in the builder
EVAPCO ATWB 12-4M14 closed-circuit cooler (320 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4M14 — an ATWB closed-circuit cooler, 320 nominal tons (1405 kW): rated to cool 802 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 45.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1054–1756 kWEUOpen in the builder
Baltimore Aircoil Series V VT0-176-O cooling tower (175 tons, 771 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-176-O — a Series V cooling tower, 175 nominal tons (771 kW): rated to cool 528 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 17.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection578–964 kWEUOpen in the builder
EVAPCO AT 112-3L20 cooling tower (583 tons, 2.6 MW) — modelled Example modelled from published data
EVAPCO's 112-3L20 — an AT cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1922–3204 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-018-12G closed-circuit cooler (11 tons, 48 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-018-12G — a Series V closed circuit closed-circuit cooler, 11 nominal tons (48 kW): rated to cool 33 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 4.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection36–60 kWEUOpen in the builder
EVAPCO ATWB 12-4M20 closed-circuit cooler (432 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4M20 — an ATWB closed-circuit cooler, 432 nominal tons (1900 kW): rated to cool 1084 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 60.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1425–2375 kWEUOpen in the builder
Baltimore Aircoil VCL-065 evaporative condenser (280 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-065 — a Series V EC evaporative condenser rejecting 280 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 7.4 m³/s of the maker's own printed air, with a 3.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection210–350 kWEUOpen in the builder
‹ Previous1…1617181920…145Next ›