Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 409–432 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 112-3K18 cooling tower (544 tons, 2.4 MW) — modelled Example modelled from published data EVAPCO's 112-3K18 — an AT cooling tower, 544 nominal tons (2392 kW): rated to cool 1638 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1794–2990 kW | EU | Open in the builder |
| Baltimore Aircoil CXVT-1482-2826-50 evaporative condenser (9.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVT-1482-2826-50 — a CXVT evaporative condenser rejecting 9002 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 160.1 m³/s of the maker's own printed air, with a 37.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 6752–11253 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4L20 closed-circuit cooler (407 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4L20 — an ATWB closed-circuit cooler, 407 nominal tons (1789 kW): rated to cool 1021 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 57.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1342–2236 kW | EU | Open in the builder |
| Baltimore Aircoil FXT-0709B-G cooling tower (97 tons, 425 kW) — modelled Example modelled from published data BAC's FXT-0709B-G — an FXT cooling tower, 97 nominal tons (425 kW): rated to cool 291 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 13.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 319–531 kW | EU | Open in the builder |
| EVAPCO AT 112-3K20 cooling tower (534 tons, 2.3 MW) — modelled Example modelled from published data EVAPCO's 112-3K20 — an AT cooling tower, 534 nominal tons (2348 kW): rated to cool 1608 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1761–2936 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0806B-28D-L closed-circuit cooler (83 tons, 364 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0806B-28D-L — an FXV closed-circuit cooler, 83 nominal tons (364 kW): rated to cool 249 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 19.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 273–455 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4L28 closed-circuit cooler (601 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4L28 — an ATWB closed-circuit cooler, 601 nominal tons (2642 kW): rated to cool 1508 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 87.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1981–3302 kW | EU | Open in the builder |
| Baltimore Aircoil Nexus NXF-0603N-CS2TT-J3 closed-circuit cooler (90 tons, 394 kW) — modelled Example modelled from published data BAC's NXF-0603N-CS2TT-J3 — a Nexus closed-circuit cooler, 90 nominal tons (394 kW): rated to cool 270 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 18.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 296–493 kW | EU | Open in the builder |
| EVAPCO AT 112-3L12 cooling tower (433 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 112-3L12 — an AT cooling tower, 433 nominal tons (1902 kW): rated to cool 1302 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 44.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1426–2377 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0118-0412N010 evaporative condenser (717 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0118-0412N010 — a PCC evaporative condenser rejecting 717 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 13.2 m³/s of the maker's own printed air, with a 0.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 538–896 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4L36 closed-circuit cooler (745 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4L36 — an ATWB closed-circuit cooler, 745 nominal tons (3275 kW): rated to cool 1869 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 106.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2456–4094 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0406N-6D2DZ-J1 closed-circuit cooler (35 tons, 153 kW) — modelled Example modelled from published data BAC's PFI-0406N-6D2DZ-J1 — a PFi closed-circuit cooler, 35 nominal tons (153 kW): rated to cool 105 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 7.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 115–192 kW | EU | Open in the builder |
| EVAPCO AT 112-3L14 cooling tower (469 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 112-3L14 — an AT cooling tower, 469 nominal tons (2064 kW): rated to cool 1413 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 48.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1548–2580 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-0709A-5L cooling tower (222 tons, 977 kW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-0709A-5L — a PT2 cooling tower, 222 nominal tons (977 kW): rated to cool 669 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 20.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 733–1221 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4L40 closed-circuit cooler (808 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4L40 — an ATWB closed-circuit cooler, 808 nominal tons (3553 kW): rated to cool 2027 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 114.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2664–4441 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1212-09KN cooling tower (357 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1212-09KN — a Series 1500 cooling tower, 357 nominal tons (1569 kW): rated to cool 1074 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1176–1961 kW | EU | Open in the builder |
| EVAPCO AT 112-3L18 cooling tower (579 tons, 2.5 MW) — modelled Example modelled from published data EVAPCO's 112-3L18 — an AT cooling tower, 579 nominal tons (2546 kW): rated to cool 1743 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1909–3182 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1020-07N cooling tower (455 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1020-07N — a Series 3000 cooling tower, 455 nominal tons (2002 kW): rated to cool 1371 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1502–2503 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4M14 closed-circuit cooler (320 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4M14 — an ATWB closed-circuit cooler, 320 nominal tons (1405 kW): rated to cool 802 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 45.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1054–1756 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT0-176-O cooling tower (175 tons, 771 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT0-176-O — a Series V cooling tower, 175 nominal tons (771 kW): rated to cool 528 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 17.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 578–964 kW | EU | Open in the builder |
| EVAPCO AT 112-3L20 cooling tower (583 tons, 2.6 MW) — modelled Example modelled from published data EVAPCO's 112-3L20 — an AT cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1922–3204 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-018-12G closed-circuit cooler (11 tons, 48 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-018-12G — a Series V closed circuit closed-circuit cooler, 11 nominal tons (48 kW): rated to cool 33 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 4.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 36–60 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4M20 closed-circuit cooler (432 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4M20 — an ATWB closed-circuit cooler, 432 nominal tons (1900 kW): rated to cool 1084 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 60.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1425–2375 kW | EU | Open in the builder |
| Baltimore Aircoil VCL-065 evaporative condenser (280 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCL-065 — a Series V EC evaporative condenser rejecting 280 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 7.4 m³/s of the maker's own printed air, with a 3.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 210–350 kW | EU | Open in the builder |