Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 433–456 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 112-3M12 cooling tower (459 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 112-3M12 — an AT cooling tower, 459 nominal tons (2020 kW): rated to cool 1383 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1515–2525 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-1086A evaporative condenser (4.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-1086A — a VCA evaporative condenser rejecting 4679 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 104.3 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3509–5848 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4M28 closed-circuit cooler (639 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4M28 — an ATWB closed-circuit cooler, 639 nominal tons (2810 kW): rated to cool 1603 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 91.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2107–3512 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0271B-1212N-HA evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0271B-1212N-HA — a Vertex VRC evaporative condenser rejecting 1641 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 28.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1231–2052 kW | EU | Open in the builder |
| EVAPCO AT 112-3M14 cooling tower (499 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 112-3M14 — an AT cooling tower, 499 nominal tons (2195 kW): rated to cool 1503 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1646–2744 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-1161-1236-75 evaporative condenser (7.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-1161-1236-75 — a CXVB evaporative condenser rejecting 7034 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 131.9 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5275–8792 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4M36 closed-circuit cooler (792 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4M36 — an ATWB closed-circuit cooler, 792 nominal tons (3480 kW): rated to cool 1986 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 113.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2610–4350 kW | EU | Open in the builder |
| Baltimore Aircoil CXVT-1508-2424-120 evaporative condenser (9.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVT-1508-2424-120 — a CXVT evaporative condenser rejecting 9160 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 196.9 m³/s of the maker's own printed air, with a 89.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 6870–11450 kW | EU | Open in the builder |
| EVAPCO AT 112-3M18 cooling tower (612 tons, 2.7 MW) — modelled Example modelled from published data EVAPCO's 112-3M18 — an AT cooling tower, 612 nominal tons (2690 kW): rated to cool 1842 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2018–3363 kW | EU | Open in the builder |
| Baltimore Aircoil FXT-0709B-H cooling tower (115 tons, 504 kW) — modelled Example modelled from published data BAC's FXT-0709B-H — an FXT cooling tower, 115 nominal tons (504 kW): rated to cool 345 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 16.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 378–630 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4M40 closed-circuit cooler (858 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4M40 — an ATWB closed-circuit cooler, 858 nominal tons (3773 kW): rated to cool 2153 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 121.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2830–4717 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0806B-32D-L closed-circuit cooler (87 tons, 381 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0806B-32D-L — an FXV closed-circuit cooler, 87 nominal tons (381 kW): rated to cool 261 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 19.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 286–476 kW | EU | Open in the builder |
| EVAPCO AT 112-3M20 cooling tower (621 tons, 2.7 MW) — modelled Example modelled from published data EVAPCO's 112-3M20 — an AT cooling tower, 621 nominal tons (2730 kW): rated to cool 1869 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2047–3412 kW | EU | Open in the builder |
| Baltimore Aircoil Nexus NXF-0603N-CS2TT-J4 closed-circuit cooler (120 tons, 526 kW) — modelled Example modelled from published data BAC's NXF-0603N-CS2TT-J4 — a Nexus closed-circuit cooler, 120 nominal tons (526 kW): rated to cool 360 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 24.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 394–657 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4N14 closed-circuit cooler (352 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4N14 — an ATWB closed-circuit cooler, 352 nominal tons (1546 kW): rated to cool 882 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 49.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1160–1933 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0122-0709N7.5 evaporative condenser (741 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0122-0709N7.5 — a PCC evaporative condenser rejecting 741 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 16.1 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 556–926 kW | EU | Open in the builder |
| EVAPCO AT 112-3N14 cooling tower (546 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 112-3N14 — an AT cooling tower, 546 nominal tons (2401 kW): rated to cool 1644 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1801–3001 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0412N-2D4DZ-G2 closed-circuit cooler (36 tons, 158 kW) — modelled Example modelled from published data BAC's PFI-0412N-2D4DZ-G2 — a PFi closed-circuit cooler, 36 nominal tons (158 kW): rated to cool 108 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 11.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 118–197 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4N20 closed-circuit cooler (475 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4N20 — an ATWB closed-circuit cooler, 475 nominal tons (2088 kW): rated to cool 1191 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 66.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1566–2610 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-0809A-1L cooling tower (197 tons, 868 kW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-0809A-1L — a PT2 cooling tower, 197 nominal tons (868 kW): rated to cool 594 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 651–1084 kW | EU | Open in the builder |
| EVAPCO AT 112-3N18 cooling tower (673 tons, 3.0 MW) — modelled Example modelled from published data EVAPCO's 112-3N18 — an AT cooling tower, 673 nominal tons (2957 kW): rated to cool 2025 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 69.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2218–3697 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1212-09KN-2 cooling tower (714 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1212-09KN-2 — a Series 1500 cooling tower, 714 nominal tons (3137 kW): rated to cool 2148 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2353–3921 kW | EU | Open in the builder |
| EVAPCO ATWB 12-4N28 closed-circuit cooler (703 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-4N28 — an ATWB closed-circuit cooler, 703 nominal tons (3093 kW): rated to cool 1765 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 99.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2319–3866 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1020-07N-2 cooling tower (910 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1020-07N-2 — a Series 3000 cooling tower, 910 nominal tons (4000 kW): rated to cool 2739 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 106.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3000–5000 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers