Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 433–456 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 112-3M12 cooling tower (459 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-3M12 — an AT cooling tower, 459 nominal tons (2020 kW): rated to cool 1383 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1515–2525 kWEUOpen in the builder
Baltimore Aircoil VCA-1086A evaporative condenser (4.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1086A — a VCA evaporative condenser rejecting 4679 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 104.3 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3509–5848 kWEUOpen in the builder
EVAPCO ATWB 12-4M28 closed-circuit cooler (639 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4M28 — an ATWB closed-circuit cooler, 639 nominal tons (2810 kW): rated to cool 1603 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 91.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2107–3512 kWEUOpen in the builder
Baltimore Aircoil VRC-0271B-1212N-HA evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0271B-1212N-HA — a Vertex VRC evaporative condenser rejecting 1641 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 28.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1231–2052 kWEUOpen in the builder
EVAPCO AT 112-3M14 cooling tower (499 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-3M14 — an AT cooling tower, 499 nominal tons (2195 kW): rated to cool 1503 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1646–2744 kWEUOpen in the builder
Baltimore Aircoil CXVB-1161-1236-75 evaporative condenser (7.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-1161-1236-75 — a CXVB evaporative condenser rejecting 7034 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 131.9 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection5275–8792 kWEUOpen in the builder
EVAPCO ATWB 12-4M36 closed-circuit cooler (792 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4M36 — an ATWB closed-circuit cooler, 792 nominal tons (3480 kW): rated to cool 1986 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 113.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2610–4350 kWEUOpen in the builder
Baltimore Aircoil CXVT-1508-2424-120 evaporative condenser (9.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1508-2424-120 — a CXVT evaporative condenser rejecting 9160 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 196.9 m³/s of the maker's own printed air, with a 89.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection6870–11450 kWEUOpen in the builder
EVAPCO AT 112-3M18 cooling tower (612 tons, 2.7 MW) — modelled Example modelled from published data
EVAPCO's 112-3M18 — an AT cooling tower, 612 nominal tons (2690 kW): rated to cool 1842 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2018–3363 kWEUOpen in the builder
Baltimore Aircoil FXT-0709B-H cooling tower (115 tons, 504 kW) — modelled Example modelled from published data
BAC's FXT-0709B-H — an FXT cooling tower, 115 nominal tons (504 kW): rated to cool 345 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 16.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection378–630 kWEUOpen in the builder
EVAPCO ATWB 12-4M40 closed-circuit cooler (858 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4M40 — an ATWB closed-circuit cooler, 858 nominal tons (3773 kW): rated to cool 2153 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 121.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2830–4717 kWEUOpen in the builder
Baltimore Aircoil FXV-0806B-32D-L closed-circuit cooler (87 tons, 381 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0806B-32D-L — an FXV closed-circuit cooler, 87 nominal tons (381 kW): rated to cool 261 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 19.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection286–476 kWEUOpen in the builder
EVAPCO AT 112-3M20 cooling tower (621 tons, 2.7 MW) — modelled Example modelled from published data
EVAPCO's 112-3M20 — an AT cooling tower, 621 nominal tons (2730 kW): rated to cool 1869 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2047–3412 kWEUOpen in the builder
Baltimore Aircoil Nexus NXF-0603N-CS2TT-J4 closed-circuit cooler (120 tons, 526 kW) — modelled Example modelled from published data
BAC's NXF-0603N-CS2TT-J4 — a Nexus closed-circuit cooler, 120 nominal tons (526 kW): rated to cool 360 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 24.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection394–657 kWEUOpen in the builder
EVAPCO ATWB 12-4N14 closed-circuit cooler (352 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4N14 — an ATWB closed-circuit cooler, 352 nominal tons (1546 kW): rated to cool 882 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 49.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1160–1933 kWEUOpen in the builder
Baltimore Aircoil PCC-0122-0709N7.5 evaporative condenser (741 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0122-0709N7.5 — a PCC evaporative condenser rejecting 741 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 16.1 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection556–926 kWEUOpen in the builder
EVAPCO AT 112-3N14 cooling tower (546 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-3N14 — an AT cooling tower, 546 nominal tons (2401 kW): rated to cool 1644 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1801–3001 kWEUOpen in the builder
Baltimore Aircoil PFI-0412N-2D4DZ-G2 closed-circuit cooler (36 tons, 158 kW) — modelled Example modelled from published data
BAC's PFI-0412N-2D4DZ-G2 — a PFi closed-circuit cooler, 36 nominal tons (158 kW): rated to cool 108 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 11.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection118–197 kWEUOpen in the builder
EVAPCO ATWB 12-4N20 closed-circuit cooler (475 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4N20 — an ATWB closed-circuit cooler, 475 nominal tons (2088 kW): rated to cool 1191 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 66.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1566–2610 kWEUOpen in the builder
Baltimore Aircoil PT2-0809A-1L cooling tower (197 tons, 868 kW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0809A-1L — a PT2 cooling tower, 197 nominal tons (868 kW): rated to cool 594 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection651–1084 kWEUOpen in the builder
EVAPCO AT 112-3N18 cooling tower (673 tons, 3.0 MW) — modelled Example modelled from published data
EVAPCO's 112-3N18 — an AT cooling tower, 673 nominal tons (2957 kW): rated to cool 2025 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 69.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2218–3697 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-09KN-2 cooling tower (714 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-09KN-2 — a Series 1500 cooling tower, 714 nominal tons (3137 kW): rated to cool 2148 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2353–3921 kWEUOpen in the builder
EVAPCO ATWB 12-4N28 closed-circuit cooler (703 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4N28 — an ATWB closed-circuit cooler, 703 nominal tons (3093 kW): rated to cool 1765 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 99.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2319–3866 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1020-07N-2 cooling tower (910 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1020-07N-2 — a Series 3000 cooling tower, 910 nominal tons (4000 kW): rated to cool 2739 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 106.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3000–5000 kWEUOpen in the builder
‹ Previous1…1718192021…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers