Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 457–480 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 112-3N20 cooling tower (696 tons, 3.1 MW) — modelled Example modelled from published data
EVAPCO's 112-3N20 — an AT cooling tower, 696 nominal tons (3058 kW): rated to cool 2094 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2294–3823 kWEUOpen in the builder
Baltimore Aircoil Series V VT0-19-G cooling tower (19 tons, 83 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-19-G — a Series V cooling tower, 19 nominal tons (83 kW): rated to cool 57 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 2.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection62–104 kWEUOpen in the builder
EVAPCO ATWB 12-4N36 closed-circuit cooler (870 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4N36 — an ATWB closed-circuit cooler, 870 nominal tons (3825 kW): rated to cool 2182 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 123.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2869–4781 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-018-12H closed-circuit cooler (14 tons, 61 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-018-12H — a Series V closed circuit closed-circuit cooler, 14 nominal tons (61 kW): rated to cool 42 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 5.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection46–77 kWEUOpen in the builder
EVAPCO AT 112-3O18 cooling tower (722 tons, 3.2 MW) — modelled Example modelled from published data
EVAPCO's 112-3O18 — an AT cooling tower, 722 nominal tons (3172 kW): rated to cool 2172 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2379–3965 kWEUOpen in the builder
Baltimore Aircoil VCL-073 evaporative condenser (314 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-073 — a Series V EC evaporative condenser rejecting 314 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 7.2 m³/s of the maker's own printed air, with a 3.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection236–393 kWEUOpen in the builder
EVAPCO ATWB 12-4N40 closed-circuit cooler (943 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4N40 — an ATWB closed-circuit cooler, 943 nominal tons (4146 kW): rated to cool 2366 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 132.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3110–5183 kWEUOpen in the builder
Baltimore Aircoil VCA-1120A evaporative condenser (4.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1120A — a VCA evaporative condenser rejecting 4825 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 90.3 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3619–6031 kWEUOpen in the builder
EVAPCO AT 112-3O20 cooling tower (754 tons, 3.3 MW) — modelled Example modelled from published data
EVAPCO's 112-3O20 — an AT cooling tower, 754 nominal tons (3317 kW): rated to cool 2271 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2488–4146 kWEUOpen in the builder
Baltimore Aircoil VRC-0279B-1012N-HA evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0279B-1012N-HA — a Vertex VRC evaporative condenser rejecting 1693 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 23.6 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1270–2116 kWEUOpen in the builder
EVAPCO ATWB 12-4O20 closed-circuit cooler (511 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4O20 — an ATWB closed-circuit cooler, 511 nominal tons (2244 kW): rated to cool 1281 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 70.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1683–2805 kWEUOpen in the builder
Baltimore Aircoil CXVB-117-0806-5 evaporative condenser (709 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-117-0806-5 — a CXVB evaporative condenser rejecting 709 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 13.1 m³/s of the maker's own printed air, with a 3.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection532–886 kWEUOpen in the builder
EVAPCO AT 112-4I12 cooling tower (336 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-4I12 — an AT cooling tower, 336 nominal tons (1477 kW): rated to cool 1011 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1107–1846 kWEUOpen in the builder
Baltimore Aircoil CXVT-1532-2826-60 evaporative condenser (9.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1532-2826-60 — a CXVT evaporative condenser rejecting 9306 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 170.1 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection6979–11632 kWEUOpen in the builder
EVAPCO ATWB 12-4O36 closed-circuit cooler (936 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4O36 — an ATWB closed-circuit cooler, 936 nominal tons (4113 kW): rated to cool 2347 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 130.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3085–5141 kWEUOpen in the builder
Baltimore Aircoil FXT-0709B-J cooling tower (130 tons, 571 kW) — modelled Example modelled from published data
A crossflow, axial-fan, forced-draft tower from the middle of BAC's FXT range, rated to cool 390 USGPM from 95 to 85 °F at a 78 °F entering wet bulb on 18.1 m³/s of air. The fan sits ahead of the fill, so its motor heat is in the air the fill sees — which is how BAC builds an FXT and how this model wires it. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection450–700 kWEUOpen in the builder
EVAPCO AT 112-4I14 cooling tower (369 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-4I14 — an AT cooling tower, 369 nominal tons (1621 kW): rated to cool 1110 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 35.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1216–2026 kWEUOpen in the builder
Baltimore Aircoil FXV-0806B-36D-L closed-circuit cooler (90 tons, 394 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0806B-36D-L — an FXV closed-circuit cooler, 90 nominal tons (394 kW): rated to cool 270 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 18.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection296–493 kWEUOpen in the builder
EVAPCO ATWB 12-4O40 closed-circuit cooler (1014 tons, 4.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-4O40 — an ATWB closed-circuit cooler, 1014 nominal tons (4457 kW): rated to cool 2543 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 141.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3343–5572 kWEUOpen in the builder
Baltimore Aircoil Nexus NXF-0603N-CS2TT-J5 closed-circuit cooler (150 tons, 657 kW) — modelled Example modelled from published data
BAC's NXF-0603N-CS2TT-J5 — a Nexus closed-circuit cooler, 150 nominal tons (657 kW): rated to cool 450 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection493–822 kWEUOpen in the builder
EVAPCO AT 112-4J12 cooling tower (386 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 112-4J12 — an AT cooling tower, 386 nominal tons (1696 kW): rated to cool 1161 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1272–2119 kWEUOpen in the builder
Baltimore Aircoil PCC-0128-0412N015 evaporative condenser (778 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0128-0412N015 — a PCC evaporative condenser rejecting 778 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 15.2 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection583–972 kWEUOpen in the builder
EVAPCO ATWB 12-5L14 closed-circuit cooler (328 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-5L14 — an ATWB closed-circuit cooler, 328 nominal tons (1440 kW): rated to cool 822 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 42.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1080–1801 kWEUOpen in the builder
Baltimore Aircoil PFI-0412N-3D1DZ-G2 closed-circuit cooler (43 tons, 188 kW) — modelled Example modelled from published data
BAC's PFI-0412N-3D1DZ-G2 — a PFi closed-circuit cooler, 43 nominal tons (188 kW): rated to cool 129 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 12.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection141–235 kWEUOpen in the builder
‹ Previous1…1819202122…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers