Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 505–528 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 112-4L12 cooling tower (452 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 112-4L12 — an AT cooling tower, 452 nominal tons (1989 kW): rated to cool 1362 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 43.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1492–2486 kW | EU | Open in the builder |
| Baltimore Aircoil Nexus NXF-0603N-CS2TT-J6 closed-circuit cooler (179 tons, 789 kW) — modelled Example modelled from published data BAC's NXF-0603N-CS2TT-J6 — a Nexus closed-circuit cooler, 179 nominal tons (789 kW): rated to cool 540 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 36.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 591–986 kW | EU | Open in the builder |
| EVAPCO ATWB 12-5M40 closed-circuit cooler (913 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-5M40 — an ATWB closed-circuit cooler, 913 nominal tons (4014 kW): rated to cool 2291 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 117.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3011–5018 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0130-0709N7.5 evaporative condenser (790 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0130-0709N7.5 — a PCC evaporative condenser rejecting 790 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 15.6 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 592–987 kW | EU | Open in the builder |
| EVAPCO AT 112-4L14 cooling tower (492 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 112-4L14 — an AT cooling tower, 492 nominal tons (2164 kW): rated to cool 1482 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1623–2706 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0412N-3D2DZ-H2 closed-circuit cooler (49 tons, 215 kW) — modelled Example modelled from published data BAC's PFI-0412N-3D2DZ-H2 — a PFi closed-circuit cooler, 49 nominal tons (215 kW): rated to cool 147 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 13.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 161–268 kW | EU | Open in the builder |
| EVAPCO ATWB 12-5N14 closed-circuit cooler (382 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-5N14 — an ATWB closed-circuit cooler, 382 nominal tons (1681 kW): rated to cool 959 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 48.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1261–2102 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-0809A-3M cooling tower (257 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-0809A-3M — a PT2 cooling tower, 257 nominal tons (1130 kW): rated to cool 774 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 848–1413 kW | EU | Open in the builder |
| EVAPCO AT 112-4L18 cooling tower (604 tons, 2.7 MW) — modelled Example modelled from published data EVAPCO's 112-4L18 — an AT cooling tower, 604 nominal tons (2655 kW): rated to cool 1818 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1991–3319 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1212-09LC-2 cooling tower (763 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1212-09LC-2 — a Series 1500 cooling tower, 763 nominal tons (3356 kW): rated to cool 2298 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 81.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2517–4195 kW | EU | Open in the builder |
| EVAPCO ATWB 12-5N20 closed-circuit cooler (505 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-5N20 — an ATWB closed-circuit cooler, 505 nominal tons (2218 kW): rated to cool 1266 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 64.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1664–2773 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1020-07O-2 cooling tower (965 tons, 4.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1020-07O-2 — a Series 3000 cooling tower, 965 nominal tons (4241 kW): rated to cool 2904 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 112.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3181–5301 kW | EU | Open in the builder |
| EVAPCO AT 112-4L20 cooling tower (616 tons, 2.7 MW) — modelled Example modelled from published data EVAPCO's 112-4L20 — an AT cooling tower, 616 nominal tons (2708 kW): rated to cool 1854 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2031–3385 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT0-28-H cooling tower (28 tons, 123 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT0-28-H — a Series V cooling tower, 28 nominal tons (123 kW): rated to cool 84 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 3.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 92–153 kW | EU | Open in the builder |
| EVAPCO ATWB 12-5N28 closed-circuit cooler (765 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-5N28 — an ATWB closed-circuit cooler, 765 nominal tons (3363 kW): rated to cool 1919 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 96.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2522–4203 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-018-22J closed-circuit cooler (20 tons, 88 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-018-22J — a Series V closed circuit closed-circuit cooler, 20 nominal tons (88 kW): rated to cool 60 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 5.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 66–110 kW | EU | Open in the builder |
| EVAPCO AT 112-4M12 cooling tower (479 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 112-4M12 — an AT cooling tower, 479 nominal tons (2107 kW): rated to cool 1443 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1581–2634 kW | EU | Open in the builder |
| Baltimore Aircoil VCL-087 evaporative condenser (375 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCL-087 — a Series V EC evaporative condenser rejecting 375 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 9.1 m³/s of the maker's own printed air, with a 3.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 281–469 kW | EU | Open in the builder |
| EVAPCO ATWB 12-5N36 closed-circuit cooler (930 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-5N36 — an ATWB closed-circuit cooler, 930 nominal tons (4089 kW): rated to cool 2333 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 119.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3066–5111 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-1162A evaporative condenser (5.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-1162A — a VCA evaporative condenser rejecting 5006 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 96.9 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3754–6257 kW | EU | Open in the builder |
| EVAPCO AT 112-4M14 cooling tower (522 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 112-4M14 — an AT cooling tower, 522 nominal tons (2296 kW): rated to cool 1572 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1722–2870 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0286B-1012N-JA evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0286B-1012N-JA — a Vertex VRC evaporative condenser rejecting 1728 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 25.7 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1296–2160 kW | EU | Open in the builder |
| EVAPCO ATWB 12-5N40 closed-circuit cooler (1002 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 12-5N40 — an ATWB closed-circuit cooler, 1002 nominal tons (4406 kW): rated to cool 2514 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 128.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3304–5507 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-123-0806-10 evaporative condenser (745 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-123-0806-10 — a CXVB evaporative condenser rejecting 745 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 16.8 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 559–932 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers