Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 553–576 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 112-4O18 cooling tower (754 tons, 3.3 MW) — modelled Example modelled from published data
EVAPCO's 112-4O18 — an AT cooling tower, 754 nominal tons (3317 kW): rated to cool 2271 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 73.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2488–4146 kWEUOpen in the builder
Baltimore Aircoil VRC-0287B-1212N-KA evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0287B-1212N-KA — a Vertex VRC evaporative condenser rejecting 1741 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 35.5 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1305–2176 kWEUOpen in the builder
EVAPCO ATWB 12-6L28 closed-circuit cooler (722 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6L28 — an ATWB closed-circuit cooler, 722 nominal tons (3174 kW): rated to cool 1811 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 81.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2380–3967 kWEUOpen in the builder
Baltimore Aircoil CXVB-124-0809-5 evaporative condenser (751 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-124-0809-5 — a CXVB evaporative condenser rejecting 751 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 17.5 m³/s of the maker's own printed air, with a 3.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection563–939 kWEUOpen in the builder
EVAPCO AT 112-4O20 cooling tower (785 tons, 3.5 MW) — modelled Example modelled from published data
EVAPCO's 112-4O20 — an AT cooling tower, 785 nominal tons (3453 kW): rated to cool 2364 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2589–4316 kWEUOpen in the builder
Baltimore Aircoil CXVT-1626-2424-100 evaporative condenser (9.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1626-2424-100 — a CXVT evaporative condenser rejecting 9877 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 184.6 m³/s of the maker's own printed air, with a 74.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection7408–12346 kWEUOpen in the builder
EVAPCO ATWB 12-6M14 closed-circuit cooler (383 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6M14 — an ATWB closed-circuit cooler, 383 nominal tons (1684 kW): rated to cool 961 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 43.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1263–2105 kWEUOpen in the builder
Baltimore Aircoil FXT-0712B-J cooling tower (159 tons, 701 kW) — modelled Example modelled from published data
BAC's FXT-0712B-J — an FXT cooling tower, 159 nominal tons (701 kW): rated to cool 480 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 22.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection526–876 kWEUOpen in the builder
EVAPCO AT 112-4P18 cooling tower (782 tons, 3.4 MW) — modelled Example modelled from published data
EVAPCO's 112-4P18 — an AT cooling tower, 782 nominal tons (3439 kW): rated to cool 2355 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 77.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2580–4299 kWEUOpen in the builder
Baltimore Aircoil FXV-0809A-20D-L closed-circuit cooler (91 tons, 399 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0809A-20D-L — an FXV closed-circuit cooler, 91 nominal tons (399 kW): rated to cool 273 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 22.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection299–498 kWEUOpen in the builder
EVAPCO ATWB 12-6M28 closed-circuit cooler (766 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6M28 — an ATWB closed-circuit cooler, 766 nominal tons (3367 kW): rated to cool 1921 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 86.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2526–4209 kWEUOpen in the builder
Baltimore Aircoil PCC-0142-0709N015 evaporative condenser (863 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0142-0709N015 — a PCC evaporative condenser rejecting 863 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 20.8 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection647–1078 kWEUOpen in the builder
EVAPCO AT 112-4P20 cooling tower (814 tons, 3.6 MW) — modelled Example modelled from published data
EVAPCO's 112-4P20 — an AT cooling tower, 814 nominal tons (3580 kW): rated to cool 2451 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2685–4474 kWEUOpen in the builder
Baltimore Aircoil PFI-0412N-4D1DZ-H2 closed-circuit cooler (55 tons, 241 kW) — modelled Example modelled from published data
BAC's PFI-0412N-4D1DZ-H2 — a PFi closed-circuit cooler, 55 nominal tons (241 kW): rated to cool 165 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 13.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection181–301 kWEUOpen in the builder
EVAPCO ATWB 12-6M36 closed-circuit cooler (915 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6M36 — an ATWB closed-circuit cooler, 915 nominal tons (4024 kW): rated to cool 2296 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 106.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3018–5030 kWEUOpen in the builder
Baltimore Aircoil PT2-0809A-5M cooling tower (271 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0809A-5M — a PT2 cooling tower, 271 nominal tons (1192 kW): rated to cool 816 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection894–1490 kWEUOpen in the builder
EVAPCO AT 114-2K24 cooling tower (617 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-2K24 — an AT cooling tower, 617 nominal tons (2712 kW): rated to cool 1857 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2034–3390 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-09LN-2 cooling tower (799 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-09LN-2 — a Series 1500 cooling tower, 799 nominal tons (3514 kW): rated to cool 2406 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 86.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2635–4392 kWEUOpen in the builder
EVAPCO ATWB 12-6N14 closed-circuit cooler (420 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6N14 — an ATWB closed-circuit cooler, 420 nominal tons (1847 kW): rated to cool 1054 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 46.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1385–2309 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1020-07P-2 cooling tower (1056 tons, 4.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1020-07P-2 — a Series 3000 cooling tower, 1056 nominal tons (4644 kW): rated to cool 3180 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 123.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3483–5805 kWEUOpen in the builder
EVAPCO AT 114-2L24 cooling tower (682 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-2L24 — an AT cooling tower, 682 nominal tons (2997 kW): rated to cool 2052 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 80.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2248–3746 kWEUOpen in the builder
Baltimore Aircoil Series V VT0-41-J cooling tower (41 tons, 180 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-41-J — a Series V cooling tower, 41 nominal tons (180 kW): rated to cool 123 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 6.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection135–225 kWEUOpen in the builder
EVAPCO ATWB 12-6N20 closed-circuit cooler (541 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6N20 — an ATWB closed-circuit cooler, 541 nominal tons (2378 kW): rated to cool 1357 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 62.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1784–2973 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-018-32H closed-circuit cooler (19 tons, 83 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-018-32H — a Series V closed circuit closed-circuit cooler, 19 nominal tons (83 kW): rated to cool 57 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 5.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection62–104 kWEUOpen in the builder
‹ Previous1…2223242526…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers