Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 601–624 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 114-3N24 cooling tower (889 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-3N24 — an AT cooling tower, 889 nominal tons (3908 kW): rated to cool 2676 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 92.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2931–4885 kWEUOpen in the builder
Baltimore Aircoil Series V VT0-52-J cooling tower (52 tons, 228 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-52-J — a Series V cooling tower, 52 nominal tons (228 kW): rated to cool 156 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 6.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection171–285 kWEUOpen in the builder
EVAPCO ATWB 12-6P20 closed-circuit cooler (615 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6P20 — an ATWB closed-circuit cooler, 615 nominal tons (2703 kW): rated to cool 1542 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 69.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2027–3379 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-018-32J closed-circuit cooler (22 tons, 96 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-018-32J — a Series V closed circuit closed-circuit cooler, 22 nominal tons (96 kW): rated to cool 66 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 5.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection72–120 kWEUOpen in the builder
EVAPCO AT 114-3O24 cooling tower (948 tons, 4.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-3O24 — an AT cooling tower, 948 nominal tons (4167 kW): rated to cool 2853 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 99.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3125–5208 kWEUOpen in the builder
Baltimore Aircoil VCL-115 evaporative condenser (496 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-115 — a Series V EC evaporative condenser rejecting 496 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 10.8 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection372–619 kWEUOpen in the builder
EVAPCO ATWB 12-6P36 closed-circuit cooler (1141 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6P36 — an ATWB closed-circuit cooler, 1141 nominal tons (5016 kW): rated to cool 2862 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 129.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3762–6270 kWEUOpen in the builder
Baltimore Aircoil VCA-1200A evaporative condenser (5.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1200A — a VCA evaporative condenser rejecting 5170 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 99.4 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3877–6462 kWEUOpen in the builder
EVAPCO AT 114-3P24 cooling tower (1005 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-3P24 — an AT cooling tower, 1005 nominal tons (4416 kW): rated to cool 3024 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 104.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3312–5521 kWEUOpen in the builder
Baltimore Aircoil VRC-0298B-1212N-JA evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0298B-1212N-JA — a Vertex VRC evaporative condenser rejecting 1809 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1357–2262 kWEUOpen in the builder
EVAPCO ATWB 12-6P40 closed-circuit cooler (1221 tons, 5.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-6P40 — an ATWB closed-circuit cooler, 1221 nominal tons (5369 kW): rated to cool 3064 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 139.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4027–6712 kWEUOpen in the builder
Baltimore Aircoil CXVB-126-0809-3 evaporative condenser (763 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-126-0809-3 — a CXVB evaporative condenser rejecting 763 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 12.6 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection573–954 kWEUOpen in the builder
EVAPCO AT 114-4K24 cooling tower (769 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-4K24 — an AT cooling tower, 769 nominal tons (3382 kW): rated to cool 2316 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2537–4228 kWEUOpen in the builder
Baltimore Aircoil CXVT-1688-2826-100 evaporative condenser (10.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1688-2826-100 — a CXVT evaporative condenser rejecting 10254 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 201.7 m³/s of the maker's own printed air, with a 74.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection7690–12817 kWEUOpen in the builder
EVAPCO ATWB 12-7L14 closed-circuit cooler (401 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-7L14 — an ATWB closed-circuit cooler, 401 nominal tons (1761 kW): rated to cool 1005 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 39.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1320–2201 kWEUOpen in the builder
Baltimore Aircoil FXT-0712B-L cooling tower (191 tons, 841 kW) — modelled Example modelled from published data
BAC's FXT-0712B-L — an FXT cooling tower, 191 nominal tons (841 kW): rated to cool 576 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 27.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection631–1052 kWEUOpen in the builder
EVAPCO AT 114-4L24 cooling tower (831 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-4L24 — an AT cooling tower, 831 nominal tons (3654 kW): rated to cool 2502 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2741–4568 kWEUOpen in the builder
Baltimore Aircoil FXV-0809B-16D-M closed-circuit cooler (99 tons, 434 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0809B-16D-M — an FXV closed-circuit cooler, 99 nominal tons (434 kW): rated to cool 297 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 27.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection325–542 kWEUOpen in the builder
EVAPCO ATWB 12-7L28 closed-circuit cooler (801 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-7L28 — an ATWB closed-circuit cooler, 801 nominal tons (3521 kW): rated to cool 2009 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 79.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2641–4401 kWEUOpen in the builder
Baltimore Aircoil PCC-0160-0709N020 evaporative condenser (972 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0160-0709N020 — a PCC evaporative condenser rejecting 972 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 22.3 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection729–1215 kWEUOpen in the builder
EVAPCO AT 114-4M24 cooling tower (869 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-4M24 — an AT cooling tower, 869 nominal tons (3821 kW): rated to cool 2616 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 82.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2865–4776 kWEUOpen in the builder
Baltimore Aircoil PFI-0412N-4D2EZ-J2 closed-circuit cooler (67 tons, 294 kW) — modelled Example modelled from published data
BAC's PFI-0412N-4D2EZ-J2 — a PFi closed-circuit cooler, 67 nominal tons (294 kW): rated to cool 201 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 14.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection220–367 kWEUOpen in the builder
EVAPCO ATWB 12-7M14 closed-circuit cooler (425 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-7M14 — an ATWB closed-circuit cooler, 425 nominal tons (1866 kW): rated to cool 1065 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 41.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1400–2333 kWEUOpen in the builder
Baltimore Aircoil PT2-0812A-2N cooling tower (325 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0812A-2N — a PT2 cooling tower, 325 nominal tons (1428 kW): rated to cool 978 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1071–1785 kWEUOpen in the builder
‹ Previous1…2425262728…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers