Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 649–672 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 114-5M26 cooling tower (1138 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-5M26 — an AT cooling tower, 1138 nominal tons (5004 kW): rated to cool 3426 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 107.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3753–6254 kWEUOpen in the builder
Baltimore Aircoil PFI-0412N-4D3EZ-H2 closed-circuit cooler (62 tons, 272 kW) — modelled Example modelled from published data
BAC's PFI-0412N-4D3EZ-H2 — a PFi closed-circuit cooler, 62 nominal tons (272 kW): rated to cool 186 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 12.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection204–340 kWEUOpen in the builder
EVAPCO ATWB 12-7N40 closed-circuit cooler (1160 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-7N40 — an ATWB closed-circuit cooler, 1160 nominal tons (5101 kW): rated to cool 2911 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 120.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3826–6376 kWEUOpen in the builder
Baltimore Aircoil PT2-0812A-3O cooling tower (361 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0812A-3O — a PT2 cooling tower, 361 nominal tons (1586 kW): rated to cool 1086 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 35.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1190–1983 kWEUOpen in the builder
EVAPCO AT 114-5N26 cooling tower (1243 tons, 5.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-5N26 — an AT cooling tower, 1243 nominal tons (5464 kW): rated to cool 3741 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 117.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4098–6829 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-10LC cooling tower (401 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-10LC — a Series 1500 cooling tower, 401 nominal tons (1761 kW): rated to cool 1206 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1321–2202 kWEUOpen in the builder
EVAPCO ATWB 12-7O20 closed-circuit cooler (626 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-7O20 — an ATWB closed-circuit cooler, 626 nominal tons (2753 kW): rated to cool 1571 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 64.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2065–3442 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-06N cooling tower (471 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's largest crossflow induced-draft range, here at 471 nominal tons: 1 413 USGPM cooled from 95 to 85 °F at a 78 °F entering wet bulb on 56.7 m³/s of air behind a 25 hp fan. At this size the tower is the plant's largest single air mover, and the fan motor is the figure that decides the condenser loop's part-load cost. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1700–2500 kWEUOpen in the builder
EVAPCO AT 114-5O26 cooling tower (1328 tons, 5.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 114-5O26 — an AT cooling tower, 1328 nominal tons (5836 kW): rated to cool 3996 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 125.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4377–7295 kWEUOpen in the builder
Baltimore Aircoil Series V VT0-65-J cooling tower (65 tons, 285 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-65-J — a Series V cooling tower, 65 nominal tons (285 kW): rated to cool 195 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection214–356 kWEUOpen in the builder
EVAPCO ATWB 12-7O36 closed-circuit cooler (1170 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-7O36 — an ATWB closed-circuit cooler, 1170 nominal tons (5142 kW): rated to cool 2934 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 119.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3857–6428 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-018-42J closed-circuit cooler (24 tons, 105 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-018-42J — a Series V closed circuit closed-circuit cooler, 24 nominal tons (105 kW): rated to cool 72 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 5.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection79–131 kWEUOpen in the builder
EVAPCO AT 14-2E4 cooling tower (33 tons, 145 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-2E4 — an AT cooling tower, 33 nominal tons (145 kW): rated to cool 99 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 4.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection108–181 kWEUOpen in the builder
Baltimore Aircoil VCL-134 evaporative condenser (577 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-134 — a Series V EC evaporative condenser rejecting 577 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 11.9 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection433–722 kWEUOpen in the builder
EVAPCO ATWB 12-7O40 closed-circuit cooler (1244 tons, 5.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-7O40 — an ATWB closed-circuit cooler, 1244 nominal tons (5470 kW): rated to cool 3121 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 128.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4102–6837 kWEUOpen in the builder
Baltimore Aircoil VCA-1218A evaporative condenser (5.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1218A — a VCA evaporative condenser rejecting 5247 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 77.2 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3936–6559 kWEUOpen in the builder
EVAPCO AT 14-2E9 cooling tower (76 tons, 333 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-2E9 — an AT cooling tower, 76 nominal tons (333 kW): rated to cool 228 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 10.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection250–416 kWEUOpen in the builder
Baltimore Aircoil VRC-0305B-1012N-KA evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0305B-1012N-KA — a Vertex VRC evaporative condenser rejecting 1848 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 28.3 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1386–2310 kWEUOpen in the builder
EVAPCO ATWB 12-7P20 closed-circuit cooler (663 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-7P20 — an ATWB closed-circuit cooler, 663 nominal tons (2914 kW): rated to cool 1663 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 67.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2185–3642 kWEUOpen in the builder
Baltimore Aircoil CXVB-134-0809-7.5 evaporative condenser (812 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-134-0809-7.5 — a CXVB evaporative condenser rejecting 812 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 20.0 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection609–1015 kWEUOpen in the builder
EVAPCO AT 14-2F12 cooling tower (115 tons, 504 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-2F12 — an AT cooling tower, 115 nominal tons (504 kW): rated to cool 345 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection378–630 kWEUOpen in the builder
Baltimore Aircoil CXVT-1788-2826-100 evaporative condenser (10.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1788-2826-100 — a CXVT evaporative condenser rejecting 10861 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 200.6 m³/s of the maker's own printed air, with a 74.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection8146–13576 kWEUOpen in the builder
EVAPCO ATWB 12-7P40 closed-circuit cooler (1317 tons, 5.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 12-7P40 — an ATWB closed-circuit cooler, 1317 nominal tons (5789 kW): rated to cool 3303 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 135.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4342–7236 kWEUOpen in the builder
Baltimore Aircoil FXT-0712C-K cooling tower (215 tons, 946 kW) — modelled Example modelled from published data
BAC's FXT-0712C-K — an FXT cooling tower, 215 nominal tons (946 kW): rated to cool 648 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection710–1183 kWEUOpen in the builder
‹ Previous1…2627282930…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers