Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 673–696 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 14-2F4 cooling tower (39 tons, 171 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-2F4 — an AT cooling tower, 39 nominal tons (171 kW): rated to cool 117 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 5.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection128–214 kWEUOpen in the builder
Baltimore Aircoil FXV-0809B-24D-M closed-circuit cooler (119 tons, 521 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0809B-24D-M — an FXV closed-circuit cooler, 119 nominal tons (521 kW): rated to cool 357 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 27.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection391–652 kWEUOpen in the builder
EVAPCO ATWB 14-3H9 closed-circuit cooler (176 tons, 775 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 14-3H9 — an ATWB closed-circuit cooler, 176 nominal tons (775 kW): rated to cool 442 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 32.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection581–969 kWEUOpen in the builder
Baltimore Aircoil PCC-0175-0709N020 evaporative condenser (1.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0175-0709N020 — a PCC evaporative condenser rejecting 1063 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 20.0 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection797–1329 kWEUOpen in the builder
EVAPCO AT 14-2F6 cooling tower (57 tons, 250 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-2F6 — an AT cooling tower, 57 nominal tons (250 kW): rated to cool 171 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 7.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection187–312 kWEUOpen in the builder
Baltimore Aircoil PFI-0412N-5D1EZ-J2 closed-circuit cooler (70 tons, 307 kW) — modelled Example modelled from published data
BAC's PFI-0412N-5D1EZ-J2 — a PFi closed-circuit cooler, 70 nominal tons (307 kW): rated to cool 210 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 14.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection230–383 kWEUOpen in the builder
EVAPCO ATWB 14-3I9 closed-circuit cooler (196 tons, 862 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 14-3I9 — an ATWB closed-circuit cooler, 196 nominal tons (862 kW): rated to cool 492 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 35.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection647–1078 kWEUOpen in the builder
Baltimore Aircoil PT2-0812A-4O cooling tower (368 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0812A-4O — a PT2 cooling tower, 368 nominal tons (1617 kW): rated to cool 1107 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1213–2021 kWEUOpen in the builder
EVAPCO AT 14-2F9 cooling tower (90 tons, 394 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-2F9 — an AT cooling tower, 90 nominal tons (394 kW): rated to cool 270 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 11.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection296–493 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-10LC-2 cooling tower (801 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-10LC-2 — a Series 1500 cooling tower, 801 nominal tons (3523 kW): rated to cool 2412 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2642–4403 kWEUOpen in the builder
EVAPCO ATWB 14-4I9 closed-circuit cooler (220 tons, 967 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 14-4I9 — an ATWB closed-circuit cooler, 220 nominal tons (967 kW): rated to cool 552 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 34.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection725–1208 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-06N-2 cooling tower (939 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-06N-2 — a Series 3000 cooling tower, 939 nominal tons (4127 kW): rated to cool 2826 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 113.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3095–5159 kWEUOpen in the builder
EVAPCO AT 14-2G12 cooling tower (137 tons, 600 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-2G12 — an AT cooling tower, 137 nominal tons (600 kW): rated to cool 411 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 17.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection450–750 kWEUOpen in the builder
Baltimore Aircoil Series V VT0-75-K cooling tower (75 tons, 329 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-75-K — a Series V cooling tower, 75 nominal tons (329 kW): rated to cool 225 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection246–411 kWEUOpen in the builder
EVAPCO ATWB 14-4J9 closed-circuit cooler (254 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 14-4J9 — an ATWB closed-circuit cooler, 254 nominal tons (1115 kW): rated to cool 636 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 38.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection836–1393 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-027-22H closed-circuit cooler (24 tons, 105 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-027-22H — a Series V closed circuit closed-circuit cooler, 24 nominal tons (105 kW): rated to cool 72 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 6.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection79–131 kWEUOpen in the builder
EVAPCO AT 14-2G6 cooling tower (67 tons, 294 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-2G6 — an AT cooling tower, 67 nominal tons (294 kW): rated to cool 201 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection220–367 kWEUOpen in the builder
Baltimore Aircoil VCL-155 evaporative condenser (668 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-155 — a Series V EC evaporative condenser rejecting 668 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 13.2 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection501–835 kWEUOpen in the builder
EVAPCO ATWB 14-5I9 closed-circuit cooler (250 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 14-5I9 — an ATWB closed-circuit cooler, 250 nominal tons (1101 kW): rated to cool 628 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 37.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection826–1376 kWEUOpen in the builder
Baltimore Aircoil VCA-122A evaporative condenser (525 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-122A — a VCA evaporative condenser rejecting 525 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 11.2 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection394–657 kWEUOpen in the builder
EVAPCO AT 14-3E4 cooling tower (37 tons, 162 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-3E4 — an AT cooling tower, 37 nominal tons (162 kW): rated to cool 111 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 4.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection122–203 kWEUOpen in the builder
Baltimore Aircoil VRC-0307B-1012N-JA evaporative condenser (1.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0307B-1012N-JA — a Vertex VRC evaporative condenser rejecting 1865 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 26.9 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1399–2332 kWEUOpen in the builder
EVAPCO ATWB 14-5J9 closed-circuit cooler (287 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 14-5J9 — an ATWB closed-circuit cooler, 287 nominal tons (1264 kW): rated to cool 721 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 37.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection948–1580 kWEUOpen in the builder
Baltimore Aircoil CXVB-137-0806-15 evaporative condenser (830 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-137-0806-15 — a CXVB evaporative condenser rejecting 830 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 18.8 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection622–1037 kWEUOpen in the builder
‹ Previous1…2728293031…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers