Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 721–744 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 14-3G6 cooling tower (74 tons, 324 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 14-3G6 — an AT cooling tower, 74 nominal tons (324 kW): rated to cool 222 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection243–405 kWEUOpen in the builder
Baltimore Aircoil VRC-0314B-1212N-HB evaporative condenser (1.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0314B-1212N-HB — a Vertex VRC evaporative condenser rejecting 1905 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 40.2 m³/s of the maker's own printed air, with a 19.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1429–2381 kWEUOpen in the builder
EVAPCO ATWB 17-3L14 closed-circuit cooler (441 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 17-3L14 — an ATWB closed-circuit cooler, 441 nominal tons (1941 kW): rated to cool 1107 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 70.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1456–2426 kWEUOpen in the builder
Baltimore Aircoil CXVB-138-0809-3 evaporative condenser (836 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-138-0809-3 — a CXVB evaporative condenser rejecting 836 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 14.3 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection627–1045 kWEUOpen in the builder
EVAPCO AT 17-2G18 cooling tower (227 tons, 999 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-2G18 — an AT cooling tower, 227 nominal tons (999 kW): rated to cool 684 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection749–1249 kWEUOpen in the builder
Baltimore Aircoil CXVT-1930-2826-120 evaporative condenser (11.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-1930-2826-120 — a CXVT evaporative condenser rejecting 11723 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 213.3 m³/s of the maker's own printed air, with a 89.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection8793–14654 kWEUOpen in the builder
EVAPCO ATWB 17-4J14 closed-circuit cooler (399 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 17-4J14 — an ATWB closed-circuit cooler, 399 nominal tons (1753 kW): rated to cool 1000 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 58.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1315–2191 kWEUOpen in the builder
Baltimore Aircoil FXT-0712C-M cooling tower (256 tons, 1.1 MW) — modelled Example modelled from published data
BAC's FXT-0712C-M — an FXT cooling tower, 256 nominal tons (1126 kW): rated to cool 771 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection845–1408 kWEUOpen in the builder
EVAPCO AT 17-2G9 cooling tower (113 tons, 495 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-2G9 — an AT cooling tower, 113 nominal tons (495 kW): rated to cool 339 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 15.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection371–619 kWEUOpen in the builder
Baltimore Aircoil FXV-0809B-28D-M closed-circuit cooler (135 tons, 591 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0809B-28D-M — an FXV closed-circuit cooler, 135 nominal tons (591 kW): rated to cool 405 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 26.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection444–739 kWEUOpen in the builder
EVAPCO ATWB 17-4K12 closed-circuit cooler (376 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 17-4K12 — an ATWB closed-circuit cooler, 376 nominal tons (1655 kW): rated to cool 944 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 57.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1241–2069 kWEUOpen in the builder
Baltimore Aircoil PCC-0184-0709N020 evaporative condenser (1.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0184-0709N020 — a PCC evaporative condenser rejecting 1118 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 17.9 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection838–1397 kWEUOpen in the builder
EVAPCO AT 17-2H12 cooling tower (163 tons, 719 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-2H12 — an AT cooling tower, 163 nominal tons (719 kW): rated to cool 492 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection539–898 kWEUOpen in the builder
Baltimore Aircoil PFI-0412N-6D1DZ-H2 closed-circuit cooler (65 tons, 285 kW) — modelled Example modelled from published data
BAC's PFI-0412N-6D1DZ-H2 — a PFi closed-circuit cooler, 65 nominal tons (285 kW): rated to cool 195 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 12.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection214–356 kWEUOpen in the builder
EVAPCO ATWB 17-4K14 closed-circuit cooler (439 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 17-4K14 — an ATWB closed-circuit cooler, 439 nominal tons (1930 kW): rated to cool 1101 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 63.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1447–2412 kWEUOpen in the builder
Baltimore Aircoil PT2-0814A-1N cooling tower (320 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-0814A-1N — a PT2 cooling tower, 320 nominal tons (1406 kW): rated to cool 963 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1055–1758 kWEUOpen in the builder
EVAPCO AT 17-2H14 cooling tower (173 tons, 762 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-2H14 — an AT cooling tower, 173 nominal tons (762 kW): rated to cool 522 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection572–953 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-10LN-2 cooling tower (839 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-10LN-2 — a Series 1500 cooling tower, 839 nominal tons (3689 kW): rated to cool 2526 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 89.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2767–4611 kWEUOpen in the builder
EVAPCO ATWB 17-4L12 closed-circuit cooler (406 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 17-4L12 — an ATWB closed-circuit cooler, 406 nominal tons (1784 kW): rated to cool 1018 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 60.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1338–2230 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-06O-2 cooling tower (996 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-06O-2 — a Series 3000 cooling tower, 996 nominal tons (4377 kW): rated to cool 2997 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 119.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3283–5471 kWEUOpen in the builder
EVAPCO AT 17-2H18 cooling tower (271 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-2H18 — an AT cooling tower, 271 nominal tons (1192 kW): rated to cool 816 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection894–1490 kWEUOpen in the builder
Baltimore Aircoil Series V VT0-88-L cooling tower (88 tons, 386 kW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT0-88-L — a Series V cooling tower, 88 nominal tons (386 kW): rated to cool 264 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 9.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection289–482 kWEUOpen in the builder
EVAPCO ATWB 17-4L14 closed-circuit cooler (473 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 17-4L14 — an ATWB closed-circuit cooler, 473 nominal tons (2077 kW): rated to cool 1185 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 67.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1558–2597 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-027-22K closed-circuit cooler (32 tons, 140 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-027-22K — a Series V closed circuit closed-circuit cooler, 32 nominal tons (140 kW): rated to cool 96 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 8.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection105–175 kWEUOpen in the builder
‹ Previous1…2930313233…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers