Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 745–768 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 17-2H9 cooling tower (135 tons, 591 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2H9 — an AT cooling tower, 135 nominal tons (591 kW): rated to cool 405 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 17.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 444–739 kW | EU | Open in the builder |
| Baltimore Aircoil VCL-185 evaporative condenser (797 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCL-185 — a Series V EC evaporative condenser rejecting 797 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 19.6 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 598–996 kW | EU | Open in the builder |
| EVAPCO ATWB 17-4M14 closed-circuit cooler (502 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-4M14 — an ATWB closed-circuit cooler, 502 nominal tons (2205 kW): rated to cool 1258 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 71.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1654–2757 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-1246A evaporative condenser (5.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-1246A — a VCA evaporative condenser rejecting 5368 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 106.7 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4026–6710 kW | EU | Open in the builder |
| EVAPCO AT 17-2I12 cooling tower (179 tons, 789 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2I12 — an AT cooling tower, 179 nominal tons (789 kW): rated to cool 540 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 591–986 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0320B-1212N-KA evaporative condenser (1.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0320B-1212N-KA — a Vertex VRC evaporative condenser rejecting 1943 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 34.5 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1457–2429 kW | EU | Open in the builder |
| EVAPCO ATWB 17-5J12 closed-circuit cooler (377 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-5J12 — an ATWB closed-circuit cooler, 377 nominal tons (1655 kW): rated to cool 945 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 51.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1242–2069 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-138-0809-5 evaporative condenser (836 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-138-0809-5 — a CXVB evaporative condenser rejecting 836 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 17.1 m³/s of the maker's own printed air, with a 3.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 627–1045 kW | EU | Open in the builder |
| EVAPCO AT 17-2I14 cooling tower (246 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2I14 — an AT cooling tower, 246 nominal tons (1082 kW): rated to cool 741 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 812–1353 kW | EU | Open in the builder |
| Baltimore Aircoil CXVT-2010-2826-150 evaporative condenser (12.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVT-2010-2826-150 — a CXVT evaporative condenser rejecting 12210 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 229.7 m³/s of the maker's own printed air, with a 111.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 9157–15262 kW | EU | Open in the builder |
| EVAPCO ATWB 17-5J14 closed-circuit cooler (434 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-5J14 — an ATWB closed-circuit cooler, 434 nominal tons (1907 kW): rated to cool 1088 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 56.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1430–2383 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0809B-30T-M closed-circuit cooler (130 tons, 570 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0809B-30T-M — an FXV closed-circuit cooler, 130 nominal tons (570 kW): rated to cool 390 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 26.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 427–712 kW | EU | Open in the builder |
| EVAPCO AT 17-2I18 cooling tower (300 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2I18 — an AT cooling tower, 300 nominal tons (1319 kW): rated to cool 903 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 989–1648 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0208-1012N010 evaporative condenser (1.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0208-1012N010 — a PCC evaporative condenser rejecting 1263 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 27.4 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 948–1579 kW | EU | Open in the builder |
| EVAPCO ATWB 17-5K12 closed-circuit cooler (414 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-5K12 — an ATWB closed-circuit cooler, 414 nominal tons (1822 kW): rated to cool 1040 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 55.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1366–2277 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0412N-6D1EZ-J2 closed-circuit cooler (76 tons, 333 kW) — modelled Example modelled from published data BAC's PFI-0412N-6D1EZ-J2 — a PFi closed-circuit cooler, 76 nominal tons (333 kW): rated to cool 228 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 14.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 250–416 kW | EU | Open in the builder |
| EVAPCO AT 17-2I9 cooling tower (149 tons, 653 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2I9 — an AT cooling tower, 149 nominal tons (653 kW): rated to cool 447 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 18.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 490–816 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-0814A-2O cooling tower (379 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-0814A-2O — a PT2 cooling tower, 379 nominal tons (1665 kW): rated to cool 1140 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1249–2081 kW | EU | Open in the builder |
| EVAPCO ATWB 17-5K14 closed-circuit cooler (477 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-5K14 — an ATWB closed-circuit cooler, 477 nominal tons (2096 kW): rated to cool 1196 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 61.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1572–2620 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1212-10MN cooling tower (457 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1212-10MN — a Series 1500 cooling tower, 457 nominal tons (2011 kW): rated to cool 1377 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 48.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1508–2514 kW | EU | Open in the builder |
| EVAPCO AT 17-2J12 cooling tower (207 tons, 911 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2J12 — an AT cooling tower, 207 nominal tons (911 kW): rated to cool 624 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 27.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 683–1139 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-07N cooling tower (521 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-07N — a Series 3000 cooling tower, 521 nominal tons (2291 kW): rated to cool 1569 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1719–2864 kW | EU | Open in the builder |
| EVAPCO ATWB 17-5L12 closed-circuit cooler (446 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-5L12 — an ATWB closed-circuit cooler, 446 nominal tons (1961 kW): rated to cool 1119 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 59.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1470–2451 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-1020-P cooling tower (1017 tons, 4.5 MW) — modelled Example modelled from published data BAC's VT1-1020-P — a Series V cooling tower, 1017 nominal tons (4469 kW): rated to cool 3060 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 115.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3352–5586 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers