Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 769–792 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 17-2J14 cooling tower (218 tons, 960 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2J14 — an AT cooling tower, 218 nominal tons (960 kW): rated to cool 657 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 720–1199 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-027-32H closed-circuit cooler (26 tons, 114 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-027-32H — a Series V closed circuit closed-circuit cooler, 26 nominal tons (114 kW): rated to cool 78 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 6.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 85–142 kW | EU | Open in the builder |
| EVAPCO ATWB 17-5L14 closed-circuit cooler (513 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-5L14 — an ATWB closed-circuit cooler, 513 nominal tons (2254 kW): rated to cool 1286 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 65.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1690–2817 kW | EU | Open in the builder |
| Baltimore Aircoil VCL-223 evaporative condenser (961 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCL-223 — a Series V EC evaporative condenser rejecting 961 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 20.9 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 721–1201 kW | EU | Open in the builder |
| EVAPCO AT 17-2J18 cooling tower (345 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2J18 — an AT cooling tower, 345 nominal tons (1516 kW): rated to cool 1038 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 43.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1137–1895 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-1252A evaporative condenser (5.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-1252A — a VCA evaporative condenser rejecting 5394 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 80.4 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4045–6742 kW | EU | Open in the builder |
| EVAPCO ATWB 17-5M12 closed-circuit cooler (473 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-5M12 — an ATWB closed-circuit cooler, 473 nominal tons (2081 kW): rated to cool 1187 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 62.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1561–2601 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0323B-1012N-HB evaporative condenser (2.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0323B-1012N-HB — a Vertex VRC evaporative condenser rejecting 1955 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 29.5 m³/s of the maker's own printed air, with a 19.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1466–2444 kW | EU | Open in the builder |
| EVAPCO AT 17-2J9 cooling tower (170 tons, 749 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2J9 — an AT cooling tower, 170 nominal tons (749 kW): rated to cool 513 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 562–937 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-144-0809-7.5 evaporative condenser (872 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-144-0809-7.5 — a CXVB evaporative condenser rejecting 872 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 19.8 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 654–1091 kW | EU | Open in the builder |
| EVAPCO ATWB 17-5M14 closed-circuit cooler (544 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-5M14 — an ATWB closed-circuit cooler, 544 nominal tons (2390 kW): rated to cool 1364 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 69.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1793–2988 kW | EU | Open in the builder |
| Baltimore Aircoil CXVT-2114-2826-150 evaporative condenser (12.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVT-2114-2826-150 — a CXVT evaporative condenser rejecting 12841 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 225.4 m³/s of the maker's own printed air, with a 111.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 9631–16052 kW | EU | Open in the builder |
| EVAPCO AT 17-2K12 cooling tower (228 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2K12 — an AT cooling tower, 228 nominal tons (1003 kW): rated to cool 687 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 753–1254 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0809B-32D-M closed-circuit cooler (140 tons, 613 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0809B-32D-M — an FXV closed-circuit cooler, 140 nominal tons (613 kW): rated to cool 420 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 26.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 460–767 kW | EU | Open in the builder |
| EVAPCO ATWB 17-6K14 closed-circuit cooler (523 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-6K14 — an ATWB closed-circuit cooler, 523 nominal tons (2299 kW): rated to cool 1312 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 60.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1725–2874 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0214-0718N020 evaporative condenser (1.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0214-0718N020 — a PCC evaporative condenser rejecting 1300 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 39.1 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 975–1625 kW | EU | Open in the builder |
| EVAPCO AT 17-2K14 cooling tower (300 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2K14 — an AT cooling tower, 300 nominal tons (1319 kW): rated to cool 903 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 989–1648 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0709N-2D3DS-H1 closed-circuit cooler (39 tons, 171 kW) — modelled Example modelled from published data BAC's PFI-0709N-2D3DS-H1 — a PFi closed-circuit cooler, 39 nominal tons (171 kW): rated to cool 117 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 15.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 128–214 kW | EU | Open in the builder |
| EVAPCO ATWB 17-6L14 closed-circuit cooler (562 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-6L14 — an ATWB closed-circuit cooler, 562 nominal tons (2470 kW): rated to cool 1409 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 63.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1852–3087 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-0814A-3O cooling tower (400 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-0814A-3O — a PT2 cooling tower, 400 nominal tons (1757 kW): rated to cool 1203 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1318–2196 kW | EU | Open in the builder |
| EVAPCO AT 17-2L14 cooling tower (238 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-2L14 — an AT cooling tower, 238 nominal tons (1047 kW): rated to cool 717 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 785–1309 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1212-10MN-2 cooling tower (915 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1212-10MN-2 — a Series 1500 cooling tower, 915 nominal tons (4022 kW): rated to cool 2754 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 97.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3017–5028 kW | EU | Open in the builder |
| EVAPCO ATWB 17-6M14 closed-circuit cooler (595 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 17-6M14 — an ATWB closed-circuit cooler, 595 nominal tons (2617 kW): rated to cool 1493 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 67.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1963–3271 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-07N-2 cooling tower (1043 tons, 4.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-07N-2 — a Series 3000 cooling tower, 1043 nominal tons (4583 kW): rated to cool 3138 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 122.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3437–5729 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers