Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 817–840 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 17-3I12 cooling tower (202 tons, 889 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-3I12 — an AT cooling tower, 202 nominal tons (889 kW): rated to cool 609 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 667–1112 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-07O cooling tower (552 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-07O — a Series 3000 cooling tower, 552 nominal tons (2427 kW): rated to cool 1662 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1820–3034 kW | EU | Open in the builder |
| EVAPCO ATWB 20-3J36 closed-circuit cooler (1008 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 20-3J36 — an ATWB closed-circuit cooler, 1008 nominal tons (4430 kW): rated to cool 2528 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 158.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3322–5537 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-1200-Q cooling tower (1196 tons, 5.3 MW) — modelled Example modelled from published data BAC's VT1-1200-Q — a Series V cooling tower, 1196 nominal tons (5258 kW): rated to cool 3600 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 120.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3943–6572 kW | EU | Open in the builder |
| EVAPCO AT 17-3I14 cooling tower (265 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-3I14 — an AT cooling tower, 265 nominal tons (1165 kW): rated to cool 798 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 874–1457 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-027-32K closed-circuit cooler (35 tons, 153 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-027-32K — a Series V closed circuit closed-circuit cooler, 35 nominal tons (153 kW): rated to cool 105 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 8.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 115–192 kW | EU | Open in the builder |
| EVAPCO ATWB 20-3K18 closed-circuit cooler (583 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 20-3K18 — an ATWB closed-circuit cooler, 583 nominal tons (2561 kW): rated to cool 1462 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 87.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1921–3202 kW | EU | Open in the builder |
| Baltimore Aircoil VCL-257 evaporative condenser (1.1 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCL-257 — a Series V EC evaporative condenser rejecting 1107 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 22.6 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 830–1384 kW | EU | Open in the builder |
| EVAPCO AT 17-3I18 cooling tower (338 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-3I18 — an AT cooling tower, 338 nominal tons (1485 kW): rated to cool 1017 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1114–1857 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-1306A evaporative condenser (5.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-1306A — a VCA evaporative condenser rejecting 5626 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 85.0 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4220–7033 kW | EU | Open in the builder |
| EVAPCO ATWB 20-3K36 closed-circuit cooler (1111 tons, 4.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 20-3K36 — an ATWB closed-circuit cooler, 1111 nominal tons (4882 kW): rated to cool 2786 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 173.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3662–6103 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0330B-1012N-KA evaporative condenser (2.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0330B-1012N-KA — a Vertex VRC evaporative condenser rejecting 1999 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 29.6 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1499–2499 kW | EU | Open in the builder |
| EVAPCO AT 17-3I9 cooling tower (167 tons, 736 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-3I9 — an AT cooling tower, 167 nominal tons (736 kW): rated to cool 504 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 18.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 552–920 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-158-0809-5 evaporative condenser (957 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-158-0809-5 — a CXVB evaporative condenser rejecting 957 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 16.7 m³/s of the maker's own printed air, with a 3.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 718–1196 kW | EU | Open in the builder |
| EVAPCO ATWB 20-3L18 closed-circuit cooler (627 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 20-3L18 — an ATWB closed-circuit cooler, 627 nominal tons (2758 kW): rated to cool 1574 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 93.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2069–3448 kW | EU | Open in the builder |
| Baltimore Aircoil CXVT-650-1224-20 evaporative condenser (3.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVT-650-1224-20 — a CXVT evaporative condenser rejecting 3946 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 67.8 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2959–4932 kW | EU | Open in the builder |
| EVAPCO AT 17-3J12 cooling tower (233 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-3J12 — an AT cooling tower, 233 nominal tons (1025 kW): rated to cool 702 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 769–1282 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0809B-36T-M closed-circuit cooler (138 tons, 605 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0809B-36T-M — an FXV closed-circuit cooler, 138 nominal tons (605 kW): rated to cool 414 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 26.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 453–756 kW | EU | Open in the builder |
| EVAPCO ATWB 20-3L36 closed-circuit cooler (1197 tons, 5.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 20-3L36 — an ATWB closed-circuit cooler, 1197 nominal tons (5260 kW): rated to cool 3001 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 187.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3945–6575 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0232-0718N015 evaporative condenser (1.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0232-0718N015 — a PCC evaporative condenser rejecting 1409 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.5 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1057–1762 kW | EU | Open in the builder |
| EVAPCO AT 17-3J14 cooling tower (251 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 17-3J14 — an AT cooling tower, 251 nominal tons (1104 kW): rated to cool 756 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 828–1380 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0709N-3D1DS-J1 closed-circuit cooler (54 tons, 237 kW) — modelled Example modelled from published data BAC's PFI-0709N-3D1DS-J1 — a PFi closed-circuit cooler, 54 nominal tons (237 kW): rated to cool 162 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 17.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 177–296 kW | EU | Open in the builder |
| EVAPCO ATWB 20-3M18 closed-circuit cooler (666 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 20-3M18 — an ATWB closed-circuit cooler, 666 nominal tons (2929 kW): rated to cool 1671 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 98.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2197–3661 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-0814A-5O cooling tower (422 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-0814A-5O — a PT2 cooling tower, 422 nominal tons (1853 kW): rated to cool 1269 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1390–2317 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers