EVAPCO AT 17-3L12 cooling tower (278 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-3L12 — an AT cooling tower, 278 nominal tons (1222 kW): rated to cool 837 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 31.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection917–1528 kWEUOpen in the builder
Baltimore Aircoil PT2-1009A-1L cooling tower (224 tons, 986 kW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1009A-1L — a PT2 cooling tower, 224 nominal tons (986 kW): rated to cool 675 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection739–1232 kWEUOpen in the builder
EVAPCO ATWB 20-4K36 closed-circuit cooler (1174 tons, 5.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4K36 — an ATWB closed-circuit cooler, 1174 nominal tons (5161 kW): rated to cool 2945 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 168.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3871–6452 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-11LC cooling tower (413 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-11LC — a Series 1500 cooling tower, 413 nominal tons (1814 kW): rated to cool 1242 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 44.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1360–2267 kWEUOpen in the builder
EVAPCO AT 17-3L14 cooling tower (269 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-3L14 — an AT cooling tower, 269 nominal tons (1183 kW): rated to cool 810 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection887–1479 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-07P cooling tower (605 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-07P — a Series 3000 cooling tower, 605 nominal tons (2659 kW): rated to cool 1821 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1995–3324 kWEUOpen in the builder
EVAPCO ATWB 20-4L18 closed-circuit cooler (662 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4L18 — an ATWB closed-circuit cooler, 662 nominal tons (2912 kW): rated to cool 1661 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 90.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2184–3640 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-1335-S cooling tower (1331 tons, 5.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-1335-S — a Series V cooling tower, 1331 nominal tons (5849 kW): rated to cool 4005 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 137.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4387–7311 kWEUOpen in the builder
EVAPCO AT 17-3M14 cooling tower (314 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-3M14 — an AT cooling tower, 314 nominal tons (1380 kW): rated to cool 945 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1035–1725 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-027-42J closed-circuit cooler (33 tons, 145 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-027-42J — a Series V closed circuit closed-circuit cooler, 33 nominal tons (145 kW): rated to cool 99 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 7.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection108–181 kWEUOpen in the builder
EVAPCO ATWB 20-4L36 closed-circuit cooler (1264 tons, 5.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4L36 — an ATWB closed-circuit cooler, 1264 nominal tons (5556 kW): rated to cool 3170 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 181.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4167–6944 kWEUOpen in the builder
Baltimore Aircoil VCL-299 evaporative condenser (1.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-299 — a Series V EC evaporative condenser rejecting 1288 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 25.3 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection966–1610 kWEUOpen in the builder
EVAPCO AT 17-4G18 cooling tower (288 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4G18 — an AT cooling tower, 288 nominal tons (1266 kW): rated to cool 867 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection950–1583 kWEUOpen in the builder
Baltimore Aircoil VCA-1327A evaporative condenser (5.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1327A — a VCA evaporative condenser rejecting 5717 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 91.9 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4288–7146 kWEUOpen in the builder
EVAPCO ATWB 20-4M18 closed-circuit cooler (703 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4M18 — an ATWB closed-circuit cooler, 703 nominal tons (3090 kW): rated to cool 1763 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 95.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2317–3862 kWEUOpen in the builder
Baltimore Aircoil VRC-0336B-1012N-LA evaporative condenser (2.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0336B-1012N-LA — a Vertex VRC evaporative condenser rejecting 2038 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.4 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1528–2547 kWEUOpen in the builder
EVAPCO AT 17-4G9 cooling tower (143 tons, 627 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4G9 — an AT cooling tower, 143 nominal tons (627 kW): rated to cool 429 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection470–783 kWEUOpen in the builder
Baltimore Aircoil CXVB-172-0812-7.5 evaporative condenser (1.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-172-0812-7.5 — a CXVB evaporative condenser rejecting 1042 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 25.2 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection782–1303 kWEUOpen in the builder
EVAPCO ATWB 20-4N18 closed-circuit cooler (771 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4N18 — an ATWB closed-circuit cooler, 771 nominal tons (3390 kW): rated to cool 1934 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 103.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2543–4238 kWEUOpen in the builder
Baltimore Aircoil CXVT-700-1224-40 evaporative condenser (4.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-700-1224-40 — a CXVT evaporative condenser rejecting 4250 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 86.0 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3188–5313 kWEUOpen in the builder
EVAPCO AT 17-4H12 cooling tower (200 tons, 881 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4H12 — an AT cooling tower, 200 nominal tons (881 kW): rated to cool 603 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection660–1101 kWEUOpen in the builder
Baltimore Aircoil FXV-0812A-16D-M closed-circuit cooler (122 tons, 535 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0812A-16D-M — an FXV closed-circuit cooler, 122 nominal tons (535 kW): rated to cool 366 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection401–668 kWEUOpen in the builder
EVAPCO ATWB 20-5I18 closed-circuit cooler (523 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-5I18 — an ATWB closed-circuit cooler, 523 nominal tons (2301 kW): rated to cool 1313 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 65.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1726–2876 kWEUOpen in the builder
Baltimore Aircoil PCC-0246-1012N010 evaporative condenser (1.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0246-1012N010 — a PCC evaporative condenser rejecting 1494 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 22.9 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1121–1868 kWEUOpen in the builder