EVAPCO AT 17-3J18 cooling tower (388 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-3J18 — an AT cooling tower, 388 nominal tons (1704 kW): rated to cool 1167 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1278–2130 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-11KN-2 cooling tower (771 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-11KN-2 — a Series 1500 cooling tower, 771 nominal tons (3391 kW): rated to cool 2322 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 82.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2543–4239 kWEUOpen in the builder
EVAPCO ATWB 20-3N18 closed-circuit cooler (732 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-3N18 — an ATWB closed-circuit cooler, 732 nominal tons (3216 kW): rated to cool 1835 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 106.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2412–4021 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-07O-2 cooling tower (1105 tons, 4.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-07O-2 — a Series 3000 cooling tower, 1105 nominal tons (4859 kW): rated to cool 3327 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 129.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3644–6074 kWEUOpen in the builder
EVAPCO AT 17-3J9 cooling tower (192 tons, 846 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-3J9 — an AT cooling tower, 192 nominal tons (846 kW): rated to cool 579 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection634–1057 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-1245-R cooling tower (1241 tons, 5.5 MW) — modelled Example modelled from published data
BAC's VT1-1245-R — a Series V cooling tower, 1241 nominal tons (5455 kW): rated to cool 3735 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 127.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4091–6819 kWEUOpen in the builder
EVAPCO ATWB 20-4I18 closed-circuit cooler (488 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4I18 — an ATWB closed-circuit cooler, 488 nominal tons (2146 kW): rated to cool 1224 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 67.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1609–2682 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-027-42H closed-circuit cooler (28 tons, 123 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-027-42H — a Series V closed circuit closed-circuit cooler, 28 nominal tons (123 kW): rated to cool 84 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 6.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection92–153 kWEUOpen in the builder
EVAPCO AT 17-3K12 cooling tower (257 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-3K12 — an AT cooling tower, 257 nominal tons (1130 kW): rated to cool 774 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection848–1413 kWEUOpen in the builder
Baltimore Aircoil VCL-271 evaporative condenser (1.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCL-271 — a Series V EC evaporative condenser rejecting 1168 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 22.4 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection876–1460 kWEUOpen in the builder
EVAPCO ATWB 20-4I36 closed-circuit cooler (929 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4I36 — an ATWB closed-circuit cooler, 929 nominal tons (4086 kW): rated to cool 2331 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 134.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3064–5107 kWEUOpen in the builder
Baltimore Aircoil VCA-1321A evaporative condenser (5.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1321A — a VCA evaporative condenser rejecting 5691 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 86.7 m³/s of the maker's own printed air, with a 74.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4268–7114 kWEUOpen in the builder
EVAPCO AT 17-3K14 cooling tower (320 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-3K14 — an AT cooling tower, 320 nominal tons (1406 kW): rated to cool 963 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 31.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1055–1758 kWEUOpen in the builder
Baltimore Aircoil VRC-0332B-1012N-JB evaporative condenser (2.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0332B-1012N-JB — a Vertex VRC evaporative condenser rejecting 2016 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.3 m³/s of the maker's own printed air, with a 30.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1512–2520 kWEUOpen in the builder
EVAPCO ATWB 20-4J18 closed-circuit cooler (560 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4J18 — an ATWB closed-circuit cooler, 560 nominal tons (2460 kW): rated to cool 1404 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 76.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1845–3075 kWEUOpen in the builder
Baltimore Aircoil CXVB-163-0809-7.5 evaporative condenser (988 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-163-0809-7.5 — a CXVB evaporative condenser rejecting 988 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 19.4 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection741–1235 kWEUOpen in the builder
EVAPCO AT 17-3K18 cooling tower (429 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-3K18 — an AT cooling tower, 429 nominal tons (1884 kW): rated to cool 1290 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1413–2355 kWEUOpen in the builder
Baltimore Aircoil CXVT-676-1224-25 evaporative condenser (4.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-676-1224-25 — a CXVT evaporative condenser rejecting 4107 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 73.0 m³/s of the maker's own printed air, with a 18.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3080–5134 kWEUOpen in the builder
EVAPCO ATWB 20-4J36 closed-circuit cooler (1067 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4J36 — an ATWB closed-circuit cooler, 1067 nominal tons (4689 kW): rated to cool 2675 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 153.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3516–5861 kWEUOpen in the builder
Baltimore Aircoil FXV-0812A-12D-M closed-circuit cooler (108 tons, 473 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0812A-12D-M — an FXV closed-circuit cooler, 108 nominal tons (473 kW): rated to cool 324 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 31.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection355–591 kWEUOpen in the builder
EVAPCO AT 17-3K9 cooling tower (212 tons, 933 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-3K9 — an AT cooling tower, 212 nominal tons (933 kW): rated to cool 639 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection700–1167 kWEUOpen in the builder
Baltimore Aircoil PCC-0233-1012N015 evaporative condenser (1.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0233-1012N015 — a PCC evaporative condenser rejecting 1415 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 30.9 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1061–1769 kWEUOpen in the builder
EVAPCO ATWB 20-4K18 closed-circuit cooler (616 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-4K18 — an ATWB closed-circuit cooler, 616 nominal tons (2706 kW): rated to cool 1544 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 84.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2030–3383 kWEUOpen in the builder
Baltimore Aircoil PFI-0709N-3D1ES-J1 closed-circuit cooler (58 tons, 254 kW) — modelled Example modelled from published data
BAC's PFI-0709N-3D1ES-J1 — a PFi closed-circuit cooler, 58 nominal tons (254 kW): rated to cool 174 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 16.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection191–318 kWEUOpen in the builder