Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 889–912 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 17-4H14 cooling tower (222 tons, 977 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4H14 — an AT cooling tower, 222 nominal tons (977 kW): rated to cool 669 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection733–1221 kWEUOpen in the builder
Baltimore Aircoil PFI-0709N-3D2ES-L1 closed-circuit cooler (69 tons, 302 kW) — modelled Example modelled from published data
BAC's PFI-0709N-3D2ES-L1 — a PFi closed-circuit cooler, 69 nominal tons (302 kW): rated to cool 207 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 20.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection227–378 kWEUOpen in the builder
EVAPCO ATWB 20-5I36 closed-circuit cooler (998 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-5I36 — an ATWB closed-circuit cooler, 998 nominal tons (4385 kW): rated to cool 2502 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 130.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3289–5482 kWEUOpen in the builder
Baltimore Aircoil PT2-1009A-2M cooling tower (270 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1009A-2M — a PT2 cooling tower, 270 nominal tons (1187 kW): rated to cool 813 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection891–1484 kWEUOpen in the builder
EVAPCO AT 17-4H18 cooling tower (331 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4H18 — an AT cooling tower, 331 nominal tons (1455 kW): rated to cool 996 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1091–1818 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-11LC-2 cooling tower (825 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-11LC-2 — a Series 1500 cooling tower, 825 nominal tons (3628 kW): rated to cool 2484 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 88.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2721–4535 kWEUOpen in the builder
EVAPCO ATWB 20-5J18 closed-circuit cooler (599 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-5J18 — an ATWB closed-circuit cooler, 599 nominal tons (2633 kW): rated to cool 1502 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 74.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1975–3291 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-07P-2 cooling tower (1211 tons, 5.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-07P-2 — a Series 3000 cooling tower, 1211 nominal tons (5323 kW): rated to cool 3645 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 141.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3993–6654 kWEUOpen in the builder
EVAPCO AT 17-4H9 cooling tower (163 tons, 719 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4H9 — an AT cooling tower, 163 nominal tons (719 kW): rated to cool 492 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 16.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection539–898 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-275-P cooling tower (274 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-275-P — a Series V cooling tower, 274 nominal tons (1205 kW): rated to cool 825 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection904–1506 kWEUOpen in the builder
EVAPCO ATWB 20-5J36 closed-circuit cooler (1142 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-5J36 — an ATWB closed-circuit cooler, 1142 nominal tons (5021 kW): rated to cool 2865 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 148.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3766–6277 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-027-42K closed-circuit cooler (37 tons, 162 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-027-42K — a Series V closed circuit closed-circuit cooler, 37 nominal tons (162 kW): rated to cool 111 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 8.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection122–203 kWEUOpen in the builder
EVAPCO AT 17-4I12 cooling tower (219 tons, 964 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4I12 — an AT cooling tower, 219 nominal tons (964 kW): rated to cool 660 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection723–1205 kWEUOpen in the builder
Baltimore Aircoil VCA-1376A evaporative condenser (5.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1376A — a VCA evaporative condenser rejecting 5928 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 103.5 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4446–7410 kWEUOpen in the builder
EVAPCO ATWB 20-5K18 closed-circuit cooler (658 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-5K18 — an ATWB closed-circuit cooler, 658 nominal tons (2892 kW): rated to cool 1650 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 81.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2169–3616 kWEUOpen in the builder
Baltimore Aircoil VRC-0346B-1012N-HB evaporative condenser (2.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0346B-1012N-HB — a Vertex VRC evaporative condenser rejecting 2101 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 30.5 m³/s of the maker's own printed air, with a 19.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1576–2626 kWEUOpen in the builder
EVAPCO AT 17-4I14 cooling tower (196 tons, 863 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4I14 — an AT cooling tower, 196 nominal tons (863 kW): rated to cool 591 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection647–1079 kWEUOpen in the builder
Baltimore Aircoil CXVB-190-0809-15 evaporative condenser (1.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-190-0809-15 — a CXVB evaporative condenser rejecting 1151 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 24.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection863–1439 kWEUOpen in the builder
EVAPCO ATWB 20-5K36 closed-circuit cooler (1256 tons, 5.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-5K36 — an ATWB closed-circuit cooler, 1256 nominal tons (5520 kW): rated to cool 3150 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 163.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4140–6900 kWEUOpen in the builder
Baltimore Aircoil CXVT-712-1426-20 evaporative condenser (4.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-712-1426-20 — a CXVT evaporative condenser rejecting 4326 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 74.3 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3245–5408 kWEUOpen in the builder
EVAPCO AT 17-4I18 cooling tower (361 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4I18 — an AT cooling tower, 361 nominal tons (1586 kW): rated to cool 1086 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1190–1983 kWEUOpen in the builder
Baltimore Aircoil FXV-0812A-16Q-M closed-circuit cooler (103 tons, 451 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0812A-16Q-M — an FXV closed-circuit cooler, 103 nominal tons (451 kW): rated to cool 309 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection338–564 kWEUOpen in the builder
EVAPCO ATWB 20-5L12 closed-circuit cooler (511 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-5L12 — an ATWB closed-circuit cooler, 511 nominal tons (2247 kW): rated to cool 1282 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 65.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1685–2808 kWEUOpen in the builder
Baltimore Aircoil PCC-0249-1212N010 evaporative condenser (1.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0249-1212N010 — a PCC evaporative condenser rejecting 1513 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 30.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1134–1891 kWEUOpen in the builder