Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 937–960 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 17-4K14 cooling tower (218 tons, 960 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4K14 — an AT cooling tower, 218 nominal tons (960 kW): rated to cool 657 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 31.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection720–1199 kWEUOpen in the builder
Baltimore Aircoil PFI-0709N-3D4DS-K1 closed-circuit cooler (61 tons, 267 kW) — modelled Example modelled from published data
BAC's PFI-0709N-3D4DS-K1 — a PFi closed-circuit cooler, 61 nominal tons (267 kW): rated to cool 183 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 16.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection200–334 kWEUOpen in the builder
EVAPCO ATWB 20-5N18 closed-circuit cooler (822 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-5N18 — an ATWB closed-circuit cooler, 822 nominal tons (3614 kW): rated to cool 2062 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 100.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2710–4517 kWEUOpen in the builder
Baltimore Aircoil PT2-1009A-4N cooling tower (306 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1009A-4N — a PT2 cooling tower, 306 nominal tons (1345 kW): rated to cool 921 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1009–1681 kWEUOpen in the builder
EVAPCO AT 17-4K18 cooling tower (444 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4K18 — an AT cooling tower, 444 nominal tons (1950 kW): rated to cool 1335 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1462–2437 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1212-11LN-2 cooling tower (865 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1212-11LN-2 — a Series 1500 cooling tower, 865 nominal tons (3803 kW): rated to cool 2604 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 93.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2852–4754 kWEUOpen in the builder
EVAPCO ATWB 20-6I18 closed-circuit cooler (567 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-6I18 — an ATWB closed-circuit cooler, 567 nominal tons (2491 kW): rated to cool 1422 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 63.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1868–3114 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-07Q-2 cooling tower (1299 tons, 5.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-07Q-2 — a Series 3000 cooling tower, 1299 nominal tons (5709 kW): rated to cool 3909 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 151.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4282–7136 kWEUOpen in the builder
EVAPCO AT 17-4K9 cooling tower (219 tons, 964 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4K9 — an AT cooling tower, 219 nominal tons (964 kW): rated to cool 660 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 22.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection723–1205 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-340-P cooling tower (339 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-340-P — a Series V cooling tower, 339 nominal tons (1490 kW): rated to cool 1020 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1117–1862 kWEUOpen in the builder
EVAPCO ATWB 20-6I24 closed-circuit cooler (835 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-6I24 — an ATWB closed-circuit cooler, 835 nominal tons (3670 kW): rated to cool 2094 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 95.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2752–4587 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-036-22J closed-circuit cooler (35 tons, 153 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-036-22J — a Series V closed circuit closed-circuit cooler, 35 nominal tons (153 kW): rated to cool 105 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 9.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection115–192 kWEUOpen in the builder
EVAPCO AT 17-4L12 cooling tower (289 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4L12 — an AT cooling tower, 289 nominal tons (1271 kW): rated to cool 870 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection953–1588 kWEUOpen in the builder
Baltimore Aircoil VCA-1414A evaporative condenser (6.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1414A — a VCA evaporative condenser rejecting 6092 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 88.9 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4569–7615 kWEUOpen in the builder
EVAPCO ATWB 20-6I36 closed-circuit cooler (1081 tons, 4.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-6I36 — an ATWB closed-circuit cooler, 1081 nominal tons (4751 kW): rated to cool 2711 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 126.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3563–5939 kWEUOpen in the builder
Baltimore Aircoil VRC-0347B-1212N-HB evaporative condenser (2.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0347B-1212N-HB — a Vertex VRC evaporative condenser rejecting 2105 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.7 m³/s of the maker's own printed air, with a 19.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1578–2631 kWEUOpen in the builder
EVAPCO AT 17-4L14 cooling tower (294 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4L14 — an AT cooling tower, 294 nominal tons (1293 kW): rated to cool 885 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection969–1616 kWEUOpen in the builder
Baltimore Aircoil CXVB-204-0812-7.5 evaporative condenser (1.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-204-0812-7.5 — a CXVB evaporative condenser rejecting 1236 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 21.0 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection927–1545 kWEUOpen in the builder
EVAPCO ATWB 20-6J18 closed-circuit cooler (647 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-6J18 — an ATWB closed-circuit cooler, 647 nominal tons (2844 kW): rated to cool 1623 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 72.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2133–3555 kWEUOpen in the builder
Baltimore Aircoil CXVT-741-1426-25 evaporative condenser (4.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-741-1426-25 — a CXVT evaporative condenser rejecting 4503 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 80.0 m³/s of the maker's own printed air, with a 18.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3377–5629 kWEUOpen in the builder
EVAPCO AT 17-4M14 cooling tower (332 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 17-4M14 — an AT cooling tower, 332 nominal tons (1459 kW): rated to cool 999 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 35.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1094–1824 kWEUOpen in the builder
Baltimore Aircoil FXV-0812A-23Q-M closed-circuit cooler (125 tons, 548 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0812A-23Q-M — an FXV closed-circuit cooler, 125 nominal tons (548 kW): rated to cool 375 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection411–685 kWEUOpen in the builder
EVAPCO ATWB 20-6J36 closed-circuit cooler (1235 tons, 5.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 20-6J36 — an ATWB closed-circuit cooler, 1235 nominal tons (5429 kW): rated to cool 3098 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 144.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4072–6786 kWEUOpen in the builder
Baltimore Aircoil PCC-0267-0718N030 evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0267-0718N030 — a PCC evaporative condenser rejecting 1622 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 42.0 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1216–2027 kWEUOpen in the builder
‹ Previous1…3839404142…145Next ›