Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 937–960 of 3346

Baltimore Aircoil PFI-2012N-3D4ES-O2 closed-circuit cooler (293 tons, 1.3 MW) — modelled

BAC's PFI-2012N-3D4ES-O2 — a PFi closed-circuit cooler, 293 nominal tons (1288 kW): rated to cool 882 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 72.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 966–1610 kW · EU

Baltimore Aircoil PFI-2418N-3D4DS-Q2 closed-circuit cooler (535 tons, 2.4 MW) — modelled

BAC's PFI-2418N-3D4DS-Q2 — a PFi closed-circuit cooler, 535 nominal tons (2353 kW): rated to cool 1611 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 134.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1765–2941 kW · EU

Baltimore Aircoil PFI-0718N-4D2ES-M2 closed-circuit cooler (190 tons, 837 kW) — modelled

BAC's PFI-0718N-4D2ES-M2 — a PFi closed-circuit cooler, 190 nominal tons (837 kW): rated to cool 573 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 42.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 628–1046 kW · EU

Baltimore Aircoil PFI-1218N-4D2ES-Q1 closed-circuit cooler (308 tons, 1.4 MW) — modelled

BAC's PFI-1218N-4D2ES-Q1 — a PFi closed-circuit cooler, 308 nominal tons (1354 kW): rated to cool 927 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 66.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1015–1692 kW · EU

Baltimore Aircoil PFI-2012N-4D4ES-O2 closed-circuit cooler (335 tons, 1.5 MW) — modelled

BAC's PFI-2012N-4D4ES-O2 — a PFi closed-circuit cooler, 335 nominal tons (1472 kW): rated to cool 1008 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 68.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1104–1840 kW · EU

Baltimore Aircoil PFI-2418N-2D4ES-P2 closed-circuit cooler (424 tons, 1.9 MW) — modelled

BAC's PFI-2418N-2D4ES-P2 — a PFi closed-circuit cooler, 424 nominal tons (1862 kW): rated to cool 1275 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 130.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1397–2328 kW · EU

Baltimore Aircoil PFI-0718N-5D1ES-M2 closed-circuit cooler (198 tons, 872 kW) — modelled

BAC's PFI-0718N-5D1ES-M2 — a PFi closed-circuit cooler, 198 nominal tons (872 kW): rated to cool 597 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 41.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 654–1090 kW · EU

Baltimore Aircoil PFI-1218N-4D2ES-R1 closed-circuit cooler (321 tons, 1.4 MW) — modelled

BAC's PFI-1218N-4D2ES-R1 — a PFi closed-circuit cooler, 321 nominal tons (1411 kW): rated to cool 966 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 70.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1058–1764 kW · EU

Baltimore Aircoil PFI-2012N-6D1ES-O2 closed-circuit cooler (370 tons, 1.6 MW) — modelled

BAC's PFI-2012N-6D1ES-O2 — a PFi closed-circuit cooler, 370 nominal tons (1625 kW): rated to cool 1113 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 71.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1219–2032 kW · EU

Baltimore Aircoil PFI-2418N-3D1ES-R2 closed-circuit cooler (543 tons, 2.4 MW) — modelled

BAC's PFI-2418N-3D1ES-R2 — a PFi closed-circuit cooler, 543 nominal tons (2388 kW): rated to cool 1635 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 152.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1791–2985 kW · EU

Baltimore Aircoil PFI-0718N-6D2ES-M2 closed-circuit cooler (213 tons, 938 kW) — modelled

BAC's PFI-0718N-6D2ES-M2 — a PFi closed-circuit cooler, 213 nominal tons (938 kW): rated to cool 642 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 703–1172 kW · EU

Baltimore Aircoil PFI-1218N-4D4ES-R1 closed-circuit cooler (333 tons, 1.5 MW) — modelled

BAC's PFI-1218N-4D4ES-R1 — a PFi closed-circuit cooler, 333 nominal tons (1463 kW): rated to cool 1002 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 65.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1098–1829 kW · EU

Baltimore Aircoil PFI-2412N-3D1DS-M2 closed-circuit cooler (271 tons, 1.2 MW) — modelled

BAC's PFI-2412N-3D1DS-M2 — a PFi closed-circuit cooler, 271 nominal tons (1192 kW): rated to cool 816 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 84.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 894–1490 kW · EU

Baltimore Aircoil PFI-2418N-3D2ES-R2 closed-circuit cooler (562 tons, 2.5 MW) — modelled

BAC's PFI-2418N-3D2ES-R2 — a PFi closed-circuit cooler, 562 nominal tons (2471 kW): rated to cool 1692 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 147.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1853–3089 kW · EU

Baltimore Aircoil PFI-1012N-3D2DS-M1 closed-circuit cooler (119 tons, 521 kW) — modelled

BAC's PFI-1012N-3D2DS-M1 — a PFi closed-circuit cooler, 119 nominal tons (521 kW): rated to cool 357 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 35.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 391–652 kW · EU

Baltimore Aircoil PFI-1218N-6D3ES-R1 closed-circuit cooler (351 tons, 1.5 MW) — modelled

BAC's PFI-1218N-6D3ES-R1 — a PFi closed-circuit cooler, 351 nominal tons (1542 kW): rated to cool 1056 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 61.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1157–1928 kW · EU

Baltimore Aircoil PFI-2412N-3D1DS-N2 closed-circuit cooler (284 tons, 1.2 MW) — modelled

BAC's PFI-2412N-3D1DS-N2 — a PFi closed-circuit cooler, 284 nominal tons (1249 kW): rated to cool 855 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 90.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 937–1561 kW · EU

Baltimore Aircoil PFI-2418N-3D4ES-R2 closed-circuit cooler (592 tons, 2.6 MW) — modelled

BAC's PFI-2418N-3D4ES-R2 — a PFi closed-circuit cooler, 592 nominal tons (2603 kW): rated to cool 1782 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 138.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1952–3253 kW · EU

Baltimore Aircoil PFI-1012N-3D4DS-M1 closed-circuit cooler (126 tons, 552 kW) — modelled

BAC's PFI-1012N-3D4DS-M1 — a PFi closed-circuit cooler, 126 nominal tons (552 kW): rated to cool 378 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 32.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 414–690 kW · EU

Baltimore Aircoil PFI-1218N-6D1ES-R1 closed-circuit cooler (359 tons, 1.6 MW) — modelled

BAC's PFI-1218N-6D1ES-R1 — a PFi closed-circuit cooler, 359 nominal tons (1577 kW): rated to cool 1080 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 68.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1183–1972 kW · EU

Baltimore Aircoil PFI-2412N-3D2DS-N2 closed-circuit cooler (295 tons, 1.3 MW) — modelled

BAC's PFI-2412N-3D2DS-N2 — a PFi closed-circuit cooler, 295 nominal tons (1297 kW): rated to cool 888 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 87.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 973–1621 kW · EU

Baltimore Aircoil PFI-2418N-4D2ES-Q2 closed-circuit cooler (616 tons, 2.7 MW) — modelled

BAC's PFI-2418N-4D2ES-Q2 — a PFi closed-circuit cooler, 616 nominal tons (2708 kW): rated to cool 1854 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 133.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 2031–3385 kW · EU

Baltimore Aircoil PFI-1012N-3D3DS-N1 closed-circuit cooler (130 tons, 570 kW) — modelled

BAC's PFI-1012N-3D3DS-N1 — a PFi closed-circuit cooler, 130 nominal tons (570 kW): rated to cool 390 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 36.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 427–712 kW · EU

Baltimore Aircoil PFI-1024N-3D2DS-M2 closed-circuit cooler (237 tons, 1.0 MW) — modelled

BAC's PFI-1024N-3D2DS-M2 — a PFi closed-circuit cooler, 237 nominal tons (1043 kW): rated to cool 714 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 70.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published data